Continuous level measuring system NivoBob® 3000 - 1

Continuous level measuring system NB 3000 Technical information / Instruction manual Page Safety notes/ Technical support 2 --------------------------------------------------------------------------------------------------------------------------- Technical data Electrical Data 7 Mechanical Data 8 Operating conditions 9 Transport and Storage 9 Approvals 10 Sensor weight guide 11 --------------------------------------------------------------------------------------------------------------------------- Electrical installation 15 --------------------------------------------------------------------------------------------------------------------------Signal overview 20 --------------------------------------------------------------------------------------------------------------------------- Programming Quickset menu 22 Output adjustment menu 25 Diagnostics menu 28 Communication menu 30 Modbus register 31 --------------------------------------------------------------------------------------------------------------------------Commissioning Interface measurement 33 --------------------------------------------------------------------------------------------------------------------------Maintenance General items 34 Diagnostics Maintenance 35 Diagnostics Failure 37 --------------------------------------------------------------------------------------------------------------------------Notes for use in Hazardous Locations Subject to technical change. We assume no liability for typing errors. Different variations to those specified are possible. Please contact our technical consultants.

Abrir o catálogo na página 1
Continuous level measuring system NivoBob® 3000 - 2

Continuous level measuring system NB 3000 Technical information / Instruction manual Safety notes / Technical support Installation, maintenance and commissioning must be carried out only by qualified technical personnel. The product must be used only in the manner outlined in this instruction manual. 3 Special attention must be paid to warnings and notes as follows: WARNING Relates to a caution symbol on the product and means, that a failure to observe the necessary precautions can result in death, serious injury and/ or considerable material damage. Relates to a caution symbol on the...

Abrir o catálogo na página 2
Continuous level measuring system NivoBob® 3000 - 3

Continuous level measuring system NB 3000 Technical information / Instruction manual The NivoBob® NB 3000 is an electromechanic level measuring instrument for continuous measuring of level or volumes in silos, hoppers or tanks. Applications • Powder, granulate, small or coarse bulk goods • Interface measurement (solids in water) Available for industries such as • Chemistry • Food • Cement • Mining • Plastics • others Features Process • Suitable for most types of bulk goods • Independent of bulk material properties, such as: Dielectricity and conductivity of the bulk good Dusty atmosphere in...

Abrir o catálogo na página 3
Continuous level measuring system NivoBob® 3000 - 4

Continuous level measuring system NB 3000 Technical information / Instruction manual Basic type Flange version DN100/ 4" Thread version Flange version 2"/ 3" Housing extension Housing extension Flange Socket pipe Flange version, bottom view Rope/ tape Rope/ tape Dimensions X = Length to bottom of sensor weight (in upper stop position): see next page 8 A = Length of socket pipe 200 mm (7.9") Optional 500 mm (19.7")/ 1,000 mm (39.4") B = Diameter of socket pipe Rope version with Flange DN100/ 4" C = Housing extension Flange version DN100/ 4" Materials Housing outside Aluminium, powder coated...

Abrir o catálogo na página 4
Continuous level measuring system NivoBob® 3000 - 5

Continuous level measuring system NB 3000 Technical information / Instruction manual Window in lid and outside start button Outside start button Sensor weights Solids measurement: Rope version All weights ca. 1,0 kg (2.2 lbs) Stainless steel Material: 1.4305 (303) ø81 mm (ø3.2" ) X = 137 mm (5.4") Material: PVC ø81 mm (ø3.2") X = 137 mm (5.4") Pin: 130 mm (5.1") Material: PVC (pin POM) Version with Flange DN100/ 4" ø75 mm (ø3.0") X = 25 mm (1.0") Pin: 130 mm (5.1") Folding cover ø190 mm (ø7.5" ) X = 175 mm (6.9") Material: Float PP, Cone: aluminium ø95 mm (ø3.7") X = 460 mm (18.1")...

Abrir o catálogo na página 5
Continuous level measuring system NivoBob® 3000 - 6

Continuous level measuring system NB 3000 Technical information / Instruction manual Solids measurement: Tape version All weights ca. 2.1 kg (4.6 lbs) Stainless steel Folding cover Aluminium Float Interface measurement: Rope version Interface measurement: Tape version including additional disks to adjust to the application ø81 mm (ø3.2" ) X = 82 mm (3.22") Material: PVC with plastic/ metal disks

Abrir o catálogo na página 6
Continuous level measuring system NivoBob® 3000 - 7

Continuous level measuring system NB 3000 Technical information / Instruction manual Technical data Electrical data Power supply AC version 98 .. 253 V 50 - 60 Hz DC version 20 .. 28 V (voltages incl. 10% of EN 61010) Installed load 150 VA (including internal heater (80 W)) DC version: One unit: 150 W (with or without internal heater) * Further units which are connected to the same power supply: 25 W per unit (without internal heater, motor off) ** 50 W per unit (without internal heater, motor running) 80 W per unit (with internal heater, supply voltage 20 V DC) 100 W per unit (with...

Abrir o catálogo na página 7
Continuous level measuring system NivoBob® 3000 - 8

Continuous level measuring system NB 3000 Technical information / Instruction manual Technical data Non-volatile (no backup battery required) > 10 years data retention Connection terminals Cable entry According to selection: Screwed cable gland: 2x M20 x 1.5 and 1x M25 x 1.5 Blindplug: 2x M20 x 1.5 or Blindplug: 2x NPT 1/2" Conduit ANSI B1.20.1: 1x NPT 3/4" and 2x NPT 1/2" Clamping range (diameter) of the factory provided cable glands: M20 x 1.5: 6 .. 12 mm (0.24 .. 0.47") M25 x 1.5: 8 .. 17 mm (0.31 .. 0.67") Extension cables for Profibus DP/ Modbus Use common recommended cables Power...

Abrir o catálogo na página 8
Continuous level measuring system NivoBob® 3000 - 9

Continuous level measuring system NB 3000 Technical information / Instruction manual Technical data Operating conditions Process overpressure -0.3 .. +0.3 bar (-4.4 .. +4.4 psi) -0.5 .. + 1.7 bar (-7.3 .. +25 psi) optional for CE + UKCA + ATEX + UKEX + TR-CU -0.5 .. + 1.1 bar (-7.3 .. +16 psi) optional for FM general purpose Process temperature Ambient temperature -20°C .. +60°C (-4 .. +140°F) -40°C .. +60°C (-40 .. +140°F) CE, UKCA, FM General Purpose with internal heater -40°C .. +60°C (-40 .. +140°F) ATEX, UKEX, FM Class II, TR-CU on request possible max. +40°C (104°F) Version with...