Excertos do catálogo

TCM-2 Thyristor Control Module TCM-2 Thyristor Control Module DATA SHEET DATA SHEET DATA SHEET Multi differential protection relay, MDR-2 Relay for generators/electric motors 3-phase AC measurements Dynamic compensation for ext. failures Short response time (70 ms) Display indicating all measurements
Abrir o catálogo na página 1
Data sheet Multi differential protection relay, MDR-2 The MDR-2 differential protection relay is a microprocessor-based control unit containing all necessary functions for monitoring of the differential currents for a synchronous/asynchronous generator or motor (the object). Via current transformers the MDR-2 measures each phase current on both sides of the object. The current transformers determine the limits of the protection area. Any failure within these limits (2- or 3-phase short circuits or earth leaks) will be detected as an error Id: Differential currents, the currents flowing...
Abrir o catálogo na página 2
Data sheet Multi differential protection relay, MDR-2 Principle diagram, option C4 AC CURRENT MEASUREMENT SECONDARY SIDE AC CURRENT MEASUREMENT SECONDARY SIDE AC CURRENT MEASUREMENT PRIMARY SIDE AC CURRENT MEASUREMENT PRIMARY SIDE
Abrir o catálogo na página 3
Data sheet Multi differential protection relay, MDR-2 Available variants MDR-2 with display and display cable MDR-2 with display, display cable and option C3 MDR-2 with display, display cable and option C4 Generator add-on protection package Available options Overcurrent/short circuit protection (option C3): - Option type 2 x definite time or inverse time (curve with six programmable points) overcurrent protection (400% overcurrent max.) 1 x definite time short circuit protection (500% short circuit current max.) Block differential current protection (option C4): The block differential...
Abrir o catálogo na página 4
Data sheet Multi differential protection relay, MDR-2 Technical specifications Galv. separation: Between AC inputs and others: 3250V AC – 50 Hz – 1 min. EMC/CE: Current: Max. 4 mm2 (multi-stranded) 6 mm2 (single-stranded) (UL/cUL Listed: Max. surrounding air temp.: 55°C/131°F) Climate: Tightening torque: 0.5-0.6 Nm (4.4-5.3 lb-in) Meas. frequency: 30...70 Hz (nominal 50 Hz or 60 Hz) Aux. supply: Tightening torque: 0.5-0.6 Nm (4.4-5.3 lb-in) The aux. supply inputs are to be protected by a 2 A slow blow fuse (UL/cUL Listed: AWG 24) Binary inputs: Input voltage: 6...32V DC (bi-directional)...
Abrir o catálogo na página 5
Data sheet Multi differential protection relay, MDR-2 Dimensions Order specifications Variants Mandatory information Item no. Additional options to the standard variant Variant no. Example: Mandatory information Additional options to the standard variant Accessories Mandatory information Item no. Example: Mandatory information Item no. Due to our continuous development we reserve the right to supply equipment which may vary from the described. DEIF A/S, Frisenborgvej 33 DK-7800 Skive, Denmark Tel.: +45 9614 9614, Fax: +45 9614 9615 E-mail: deif@deif.com, URL: www.deif.com
Abrir o catálogo na página 6Todos os catálogos e folhetos técnicos DEIF
-
TRI-2
9 Páginas
-
EQ96-sw4, EQ96-sw7, VDQ96-sw
4 Páginas
-
CGC 400
10 Páginas
-
Automatic Genset Controller, AGC 100
1 Páginas
-
AGC-4 Mk II
4 Páginas
-
IMD 100
12 Páginas
-
KBU
9 Páginas
-
ASR
77 Páginas
-
DCP2
4 Páginas
-
DBC-1
15 Páginas
-
Battery chargers TOP
3 Páginas
-
AGC-4
30 Páginas
-
Multi Differential Relay, MDR-2
2 Páginas
-
Overload relays – type RMP-111D
2 Páginas
-
Loss of Mains Relay – type LMR-111D
2 Páginas
-
Alarm panel – type AL8-2
8 Páginas
-
Shunt resistors
2 Páginas
-
Insulation monitor – type AAL-111Q96
4 Páginas
-
Renewable Energy Controls - HYDRO
8 Páginas
-
Renewable Energy & Controls - WIND
8 Páginas
-
Engine & Gen-Set Controls - MARINE
8 Páginas
-
ENGINE & GEN-SET CONTROLS
2 Páginas
-
G59 protection relay package
3 Páginas