Product catalog summary
Specifications:
Instrument Transformers: CTO 15 and CTSO 38 adhere to ČSN EN 60044-1 and GOST 15 150 standards, with insulation voltages of 25 kV and 40.5 kV, respectively. They support test voltages up to 95 kV and impulse voltages up to 220 kV. Nominal primary currents range from 5–600 A for CTO 15 and 5–2000 A for CTSO 38, with a frequency of 50 Hz and power ratings between 5–60 VA. Voltage Transformers: VPPT 38.2 is suitable for high-voltage networks from 1 kV to 38.5 kV, with a test voltage up to 95 kV and a maximum output of 2 kVA. VTDOR 38 is designed for 6 kV systems, offering a power take-off of 220 V, 0-1.2 kVA at 50-75 Hz. Sensors: VSO 25 and CSO 25 are for 22 kV networks, with insulating voltages of 25 kV and test voltages of 50 kV. VSO 25 is a capacitive voltage sensor, while CSO 25 is a current sensor with a nominal primary current of 100–400 A.
Procedures:
Mounting involves using screws (M10 or M12) for the basic frame, with primary terminals connected using screws at recommended torque settings. Earthing requires the metal base of transformers to be earthed, and unused secondary outlets should be short-circuited and earthed. Switching allows for range adjustments on both secondary and primary sides using provided jumpers and screws.
Standards and Compliance:
All devices comply with relevant ČSN EN and GOST standards, ensuring safety and performance under specified conditions.
Recommendations:
Use terminal ends matching the conductor's cross-section for secure connections. Clean transformers and ensure tight connections during shutdowns. Consult the producer for additional technical parameters and official calibration if needed.
Mounting Instructions:
Detailed specifications for mounting and connecting single-pole and double-pole instrument transformers, including torque specifications: Primary terminal (M10, 20 Nm), Ground terminal (M8, 10 Nm), and Secondary terminal (M5, 2.7 Nm).
Connection Procedures:
Single-pole transformers are used in three-phase systems with two secondary windings for measurement/protection and earth connection signaling. Proper earthing is crucial to prevent instrument destruction.
Switchable Transformer Ratios:
Details on switchable single-pole transformers with ratios 6600-11000/√3//100/√3 V, including connection schemes and terminal assignments.
Double-Pole Transformers:
These have isolated primary windings and require earthing of one secondary terminal during operation. Wiring diagrams for indoor and outdoor settings are provided.
Ferroresonance Protection:
Warns about ferroresonance in inadequately earthed HV networks, recommending a dump resistor in the open delta of additional secondary windings to prevent damage.
Contact Information:
Contact details for ZEZ SILKO, s.r.o., the manufacturer, are provided for further inquiries or orders.
See more

Catalog excerpts

HV current transformers CT-2

Supporting current instrument transformers CTS

 Open the catalog to page 2
HV current transformers CT-3

Supporting current instrument transformers CTS are designed for the measurement and protection of the distributingfacilities of high voltage for inner settings. Current transformers CTS 12 are produced in two arrangements: CTS 12.S and CTS 12.L. The difference of these two arrangements is only the length of the instrument (see the picture). (Dimension in brackets is for CTS 12.L.) The bigger dimensions of CTS 12.L allow to fulll the more demandingtasks of the customer for the parameters of the instrument (3-cores arrangement, higher performance, higherovercurrent number, etc.). made of the alloyof...

 Open the catalog to page 3
HV current transformers CT-5

screw M5-12 with hexagon head CTS 38X Sch Transformers CTS 25 Schneider and CTS 38 are only made with terminals up to 1250 A. Transformers CTS 25X (Sch) and CTS 38X (Sch) are only made with terminals up to 600 A.

 Open the catalog to page 5
HV current transformers CT-6

WIRING DIAGRAM Primary terminals Double core version Three core version It is possible to consult other technical parameters with the producer.

 Open the catalog to page 6
HV current transformers CT-7

Current instrument transformers CTB Current instrument transformers CTB 25 and CTT 25 are designed for measurement and protection of high voltage distributing equipment for indoor design for the highest voltage of system of 25 kV. The value of secondary current is 5 A or 1 A with the possibility of combination. The accuracy classes for the circuits of measurement are 0.2, 0.5, 1, 3, for the circuits of protection are 5P, 10P. The transformers fulll the required accuracyclass at intervals from 25 % to 100 % of rated load. The terminal working current is 120 % IN, in case of the agreement of the...

 Open the catalog to page 7
HV current transformers CT-8

Insert of fixing of primary winding High voltage outlet with pin and epoxy

 Open the catalog to page 8
HV current transformers CT-9

WIRING DIAGRAM Double core version Three core version It is possible to consult other technical parameters with the producer.

 Open the catalog to page 9
HV current transformers CT-10

Cumulative instrument transformer CTR-1 Drawing cumulative instrument current transformer CTR1is designed for the protection of distributive arrangementsof high voltage of the inner design. The primary currents are currents of difference of the individual parts within the states of disorders, for example earth connection.The primary currents can have the value of 10 A and more according to the request of customer. The value of the secondary current is min. 0.08 A (it can be higher according to the request of customer).The transformers CTR-1 are designed as drawingtransformers. The inner hole...

 Open the catalog to page 10
HV current transformers CT-11

Split-core current transformers For outside application – GSKF, for inside application – GSK - Primary current from 50 A up to 10 kA - For measurement, protection and billing purposes - Very exible in dimensions - Split-core, applicable in existing installations - Various window sizes Ø 90….350 mm Model range GSKF: 170, 200, 250, 300, 350 and 400. Model range GSK: 100, 125, 135, 150, 200, 260, 300, 400 and 500. Detail information on http://www.kpbintra.cz/eu/produkty/GSKF.html and http://www.kpbintra.cz/eu/produkty/GSK.html

 Open the catalog to page 11
HV current transformers CT-12

Voltage instrument transformers VTS

 Open the catalog to page 12
HV current transformers CT-13

Voltage instrument transformers VTS are single-phase transformers isolated with one pole. They are designed for the use in the high voltage systems. They are designed for measuring and protection of high voltage distributing equipment for indoor design. The instruments can be equipped with high voltage fuse protecting the surrounding distributing system. The instrument transformers VTS 25 Sch are modied for the use in the distributors SM6 of the rm SCHNEIDER ELECTRIC. The values of secondary voltage are 100/√3, 110/√3, 120/√3, 100/3, 110/3, 120/3 V. The accuracy classes for measuring winding...

 Open the catalog to page 13
HV current transformers CT-14

insulated cable with cable lug for M8 fuse case view from bellow:

 Open the catalog to page 14
HV current transformers CT-15

WIRING DIAGRAM One end of primary winding is isolated from ground, the other is earthed during the operation. Before starting of the operation it is necessary to assure the earth connecti- on of one of the secondary terminals of every outlet (See „The Instructions for the operation and mounting"). In case of connection of auxiliary winding in the open tri- angle terminal has to be earthed at only one instrument The diagram of connection of three single-poled transformers ATTENTION! After every connection it is necessary to check if the secondary winding is not earthed by the me- ans of one terminal...

 Open the catalog to page 15
HV current transformers CT-16

Instrument voltage transformers VTS 38 P is necessary to accurately specify the version in the order.) If the xed contact is used, a cable eye is recommended according to the cross section of the used conductor. The magnetic circuit of the voltage transformers is made of oriented transformer strips in the shape of the “C” core. All active parts of transformer are compound-insulated with epoxy-mixture. This material performs both the electrical insulating and the mechanical functions. The secondary terminal board is equipped with a cover and a sealing screw. There is an additional pack inside...

 Open the catalog to page 16
HV current transformers CT-17

SECONDARY TERMINAL ORIENTATION Code X = 2 Instrument voltage transformers VTS 12P and VTS 38P comply with all tests according to ČSN EN 60044-2 and GOST 15 150 for U3 and T3. It is possible to consult other technical parameters with the producer.

 Open the catalog to page 17
HV current transformers CT-18

Voltage instrument transformer VTD Voltage instrument transformers VTD 12 and VTD 25 are single-phase transformers isolated with double-poles. They are designed for the use in the high voltage systems. They are designed for measuring and protection of high voltage distributing equipment for indoor design. The instruments can be provided with high voltage protectors protecting the surrounding distributing system.The values of secon- dary voltage are 100, 110, 120 V. The accuracy classes for measuring winding are 0.2, 0.5, 1, for the securing winding is 3P. The transformers satisfy required accuracy...

 Open the catalog to page 18
HV current transformers CT-19

Magnetic circuit of voltage transformers is made of oriented transformer strips in the shape of “C” of core. All active parts of transformer are compound-insulated with epoxy-mixture. This material performs both the electrical insulating and the mechanical functions. Transformers are xed by the means of four screws M10 in the holes in the basic plate. The primary terminals of transformers are brought out by the means of nuts M10. We recommend use terminal ends corresponding to the used cross-section of the conductor for attaching to the secondary outlets. The secondary terminal plate is provided...

 Open the catalog to page 19
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.