MTKD-M-FA

MTKD-M-FA

MTKD-M-FA

Product catalog summary
Overview: The MTKD-M-FA is a multi-jet dry dial water meter designed for downpipe installation, ensuring easy calibration replacement. It features an 8-digit dry dial meter register and a modulator disc for electronic scanning and remote data reading via LoRaWAN® or wM-Bus.
Specifications:
  • Multi-jet dry dial meter with shielded magnetic coupling.
  • UV-resistant polymer plastic register cap.
  • Available with glass/copper register (IP68).
  • Brass body compliant with UBA standards.
  • Register rotatable 355°.
  • Operating pressure MAP 16.
  • Approved according to MID.
Applications: Suitable for measuring consumption of cold and clean drinking or service water up to 50°C.
AMR Options:
  • EDC LPWAN radio module for LoRaWAN®.
  • EDC wireless M-Bus radio module according to OMS standard.
  • EDC combined M-Bus and pulse module.
Technical Data:
  • Permanent Flowrate Q3: 4 m³/h.
  • Measuring range Q3/Q1: R 160H.
  • Overload Flowrate Q4: 5 m³/h.
  • Transitional Flowrate Q2: 80 l/h.
  • Minimum Flowrate Q1: 50 l/h.
  • Start-up Flow Rate: <10 l/h.
  • Display range: 0.02 l to 99,999,999 m³.
  • Temperature range: 0.1°C to 50°C.
  • Operating pressure: 0.3 to 16 bar.
  • Pulse value: 1 l/pulse.
  • Pressure loss class at Q3: ∆0.63 bar.
  • Mechanical environmental condition: M2.
  • Climatic condition: 5°C to 55°C.
  • Flow profile sensitivity: U0/D0.
Dimensions and Weights:
  • Nominal diameter: 20 mm (3/4 inch).
  • Overall length without connectors: 105 mm.
  • Overall length with connectors: approx. 201 mm.
  • Thread meter: 1 inch.
  • Thread connector: 3/4 inch.
  • Width: approx. 95 mm.
  • Height: approx. 140 mm.
  • Weight: approx. 1.6 kg.
Additional Notes: Not all versions are available in all markets. The document includes typical error and pressure loss curves.
See more

Catalog excerpts

MTKD-M-FA-1

Technical data sheet MTKD-M-FA Multi-jet dry dial meter for cold water in a downpipe design The MTKD-M-FA water meter is designed for downpipe installation and guarantees an uncomplicated calibration replacement. The register of the FA variants also works in horizontal position. The meter is equipped with an 8-digit dry dial meter register and a modulator disc. This enables electronic, non-reactive scanning and is the basis for remote reading of meter data via radio with LoRaWAN® or wM-Bus (according to OMS). A combined M-Bus/pulse module is also possible. Performance characteristics at a glance ■ Multi-jet dry dial meter with shielded magnetic coupling Water meter for downpipe installation Register cap made of UV-resistant polymer plastic Available with glass/copper register (IP68) Brass body according to UBA (Federal Environment Approved in accordance with MID For the consumption measurement of cold and clean drinking water or service water up to 50 °C As standard with communication interface for EDC modules (Electronic Data Capture): – EDC LPWAN radio module (868 MHz) for LoRaWAN® – EDC wireless M-Bus radio module according to OMS standard (868 MHz), EN 13757-4

 Open the catalog to page 1
MTKD-M-FA-2

Technical data Permanent Flowrate Attainable measuring range Standard measuring range 1 Overload Flowrate Transitional Flowrate Start-up flow rate Display range Temperature range Operating pressure Pulse value Pressure loss class at Q3 Mechanical environmental condition Flow profile sensitivity Dimensions and weights: Nominal diameter Overall length without connectors Overall length with connectors approx. Width approx. Height approx. Weight approx. Other measuring ranges (R) on request The data refer to the standard measuring range 3 Condensation possible Attention: Attention: not all versions...

 Open the catalog to page 2

All Zenner InternationalGmbH & Co.KG catalogs and technical brochures

  1. MTKD-M-ST

    2  Pages

  2. MTWD-M-CC-ST

    2  Pages

  3. MTWD-M-CC-FA

    2  Pages

  4. MNK-RP-N

    4  Pages

  5. MNK-L-RP-N

    2  Pages

  6. Minomess®

    4  Pages

  7. RNK-RP-N

    4  Pages

  8. multidata

    2  Pages

  9. AMR Systems

    22  Pages

  10. PDC

    4  Pages

  11. Gas Meters

    40  Pages

Archived catalogs

  1. caltos E

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.