Product catalog summary
E7 Drive Design Benefits
The E7 drive is a compact and cost-effective variable torque AC drive designed for the Building Automation System (BAS) market. It is optimized for HVAC applications such as VAV air handlers, exhaust fans, and pumps, offering features like quiet motor operation, integral setpoint control, and improved power quality.
Quiet Motor Operation
IGBT technology in the E7 drive reduces motor noise through variable switching frequency and low harmonic content.
Integral Setpoint Control
The drive's internal PI controller eliminates the need for BAS closed-loop output signals and includes a Sleep function for energy efficiency.
Improved Power Quality
Advanced microprocessor logic ensures low EMI/RFI emissions, meeting power quality standards and often negating the need for additional protection devices.
Easy Setup
Built-in program storage and copying features facilitate easy parameter transfer across multiple drives.
HVAC-Specific Features
Includes H-O-A functionality, embedded network communications, PI control, sleep function, and motor auto-tuning.
Communications and Keypad
Supports protocols like Johnson Controls Metasys N2 and Siemens APOGEE FLN, with an optional LonWorks interface. The keypad has a large LCD display with multilingual support.
E7/Bypass Package
Allows motors to operate from the drive or directly across the AC line, providing redundancy. Includes safety interlocks and does not require additional branch circuit protection.
Switch Selectable Features
Includes Smoke Purge, Auto Transfer to Bypass, and Remote Transfer to Bypass.
Bypass Operator Control
Offers HAND, OFF, AUTO, BYPASS, DRIVE, NORMAL, and TEST modes for flexible operation.
Additional Packages
Custom drive packages available for various HVAC needs, including "And" Bypass, "Or" Bypass, and Soft-Start Bypass packages.
Enclosures
Available in NEMA Type 1, Type 12, and Type 3R for different environmental conditions.
Performance Features
Includes VT ratings, overload capacity, starting torque, DC injection braking, and energy-saving controls.
Protective Features
Features current limited stall prevention, heat sink over-temperature protection, and short circuit protection.
Design Features
Incorporates a 32-bit microprocessor, flash upgradeable firmware, and various control and monitoring capabilities.
Service Conditions
Suitable for ambient temperatures from -10°C to 40°C, with humidity up to 95% RH, and altitudes up to 3300 ft.
Bypass Features
Standard package supports up to 250 HP with input, output, and bypass contactors, and includes a circuit breaker disconnect.
Selector Switches:
  • Hand/Off/Auto selector switch
  • Normal/Test selector switch
Pilot Lights:
  • 22mm LED indicators for Control Power, Drive Run, Drive Fault, Bypass Run, Motor OL/Safety Fault, and Smoke Purge
Switch Functions:
  • Auto transfer to bypass on drive fault
  • Remote transfer to bypass via contact closure
  • Smoke purge function
Contacts and Circuits:
  • Run mode and Fault contacts
  • Control and safety circuit terminal strip
  • Damper circuit safety interlock
Customer Use:
  • 115V, 100VA
Options:
  • Remote digital operator kit
  • Input fuses, I2t; circuit breakers
  • Oversized control transformer
  • NEMA 3R and 12 enclosures
  • Input and/or output reactor
  • Twelve-pulse rectification with input transformer for various HP and VAC
  • Communication Interface: LonWorks
  • RFI/EMI filter
  • Pressure transducer, 3-15 PSI
  • Multiple motor operation logic
  • Speed potentiometer
  • Run/Stop push buttons
  • Motor protection load reactor
  • Engraved nameplates
  • Analog outputs: programmable, two, 4-20 mA
  • DriveWizard™ upload/download and monitoring/graphing software
Document Information:
  • Bulletin BL.E7.01
  • © 2002 Yaskawa Electric America, Inc.
  • Contact: (800) YASKAWA (927-5292), Fax (262) 782-3418
  • Website: www.drives.com
See more

Catalog excerpts

Bulletin E7 Drive and E7 Bypass Packages for HVAC Fan and Pump Applications-1

E7 Drive and E7 Bypass Packages for HVAC Fan and Pump Applications

 Open the catalog to page 1
Bulletin E7 Drive and E7 Bypass Packages for HVAC Fan and Pump Applications-2

E7 Drive Design Benefits The E7 drive is an application-specific, variable torque, ac drive designed to meet the needs of the Building Automation System (BAS) marketplace. This drive continues the trend to reduce size and cost while increasing performance and quality. The right solution for centrifugal loads on applications such as: VAV air handler supply and return air fans, outdoor air injection fans, exhaust fans, cooling tower fans, chilled and hot water distribution pumps, constant air volume fan conversions, DX condenser fans, clean room circulating fans, condenser water pumps, variable...

 Open the catalog to page 2
Bulletin E7 Drive and E7 Bypass Packages for HVAC Fan and Pump Applications-3

Communications and Keypad The E7 drive has embedded network communications capabilities, including Johnson Controls Metasys N2 and Siemens APOGEE FLN, with optional interface for the LonWorks® protocol. Extensive parameter selection via serial communication allows efficient management of BAS applications for energy efficiency and closed loop control, without consuming building automation system points. Serial communication allows customers to save wiring costs and BAS points while providing access to all the information accumulated by the drive's internal logic. Commissioning, control supervision...

 Open the catalog to page 3
Bulletin E7 Drive and E7 Bypass Packages for HVAC Fan and Pump Applications-4

E7/Bypass Building Automation Ready Package The E7 Bypass packages are designed for optimum performance when used with today’s Building Automation Systems (BAS). The E7 drive with bypass allows motors to be operated from either the drive or directly across the AC line. Bypass capability is selected for any critical application that must have redundant motor control to insure continued operation. The bypass function transfers motor operation from the drive to the AC line via drive isolation contactors and a bypass contactor. Our Safety Interlock enables building safety devices (i.e. Freeze-stat,...

 Open the catalog to page 4
Bulletin E7 Drive and E7 Bypass Packages for HVAC Fan and Pump Applications-5

• Input Fuses Digital Outputs [ I J Customer Supplied Interface

 Open the catalog to page 5
Bulletin E7 Drive and E7 Bypass Packages for HVAC Fan and Pump Applications-6

E7 and E7/Bypass Packaging Additional Packages Yaskawa can design and build drive packages to meet any HVAC application need, from custom panels to drives in NEMA 3R enclosures. Contact us for configuration assistance. Common package designs include: Soft-Start Bypass Package Allows one drive to control two or more motors simultaneously. Note: all motors will run at the same speed. Drive must be sized to handle the total full load amps of all connected motors. Controls two motors in lead / lag scenarios allowing the operator to specify which motor is to be operated via selector switch or contact...

 Open the catalog to page 6
Bulletin E7 Drive and E7 Bypass Packages for HVAC Fan and Pump Applications-7

E7 Drive Rated Input Voltage Protected Chassis Protected Chassis Note that weight represents drive weight only, not shipping weight (2) All NEMA 1 Enclosures (3) Weight may vary with options; maximum weight of bypass with all options is listed (1) Rated Input Voltage

 Open the catalog to page 7
Bulletin E7 Drive and E7 Bypass Packages for HVAC Fan and Pump Applications-8

Specifications Performance Features Design Features Service Conditions • VT Ratings: 1/2-150 HP, 208 VAC 1/2-150 HP, 230/240 VAC 1/2-500 HP, 480 VAC • Overload capacity: 110% for 60 sec (150% peak) • Starting torque: 100% at 3 Hz • DC injection braking: at start or stop, adjustable, current limited (antiwindmilling) • Motor preheat function • Adjustable accel/decel: 0.1 to 6000 sec. • Controlled speed range: 40:1 • Critical frequency rejection: 3 selectable, adjustable bands • Energy $aving control • Power loss ride-thru: 2 sec • Auto restart after power loss or resettable fault, programmable...

 Open the catalog to page 8

All Yaskawa America, Inc. - Drives & Motion Division catalogs and technical brochures

  1. U1000

    17  Pages

  2. MV1000NEMA 3R

    5  Pages

  3. MV1000

    13  Pages

  4. SG400

    2  Pages

  5. GP7 AND GP8

    2  Pages

  6. SIGMA TRAC II

    9  Pages

  7. R1000

    11  Pages

  8. iQPUMP AC DRIVE

    13  Pages

  9. FP605

    15  Pages

  10. iQrise

    2  Pages

  11. HV600

    19  Pages

  12. D1000

    2  Pages

  13. GA500

    9  Pages

  14. Sigma SD

    60  Pages

  15. GA800

    2  Pages

  16. L1000A

    2  Pages

  17. Deming Award

    2  Pages

  18. Z1000 Bypass

    2  Pages

  19. MP3200iec

    2  Pages

  20. P1000 Catalog

    52  Pages

  21. SGMMV

    20  Pages

  22. Bestact

    64  Pages

  23. A1000 Catalog

    58  Pages

  24. YASNAC 3000G

    203  Pages

  25. YASNAG 2000G

    58  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.