Specifications and Environmental Conditions:
  • Altitude: Maximum of 1000m; adjustments needed if exceeded.
  • Ambient Temperature: -5℃ to +40℃; adjustments required if exceeded.
  • Installation: Must be in a location free from fire, explosion hazards, conductive dust, corrosive gases, and severe vibrations.
Construction and Materials:
  • Iron Core: Made from high-quality cold-rolled silicon steel sheets, sealed with insulating resin paint to prevent moisture and rust.
  • High Voltage Windings: Vacuum pressure cast with epoxy resin, reducing partial discharge and enhancing electrical strength.
  • Low Voltage Windings: Foil structure with axial cooling air duct for improved heat dissipation.
  • Insulation: Epoxy resin, providing flame retardant, fireproof, explosion-proof, and pollution-free characteristics.
Performance Characteristics:
  • Low partial discharge, noise, and loss.
  • Strong heat dissipation and overload capacity.
  • Equipped with an intelligent temperature controller for fault and overtemperature alarms, and connected to a computer for monitoring.
Applications:
  • Suitable for power transmission and transformation systems in hotels, airports, high-rise buildings, commercial centers, residential areas, subways, smelting power plants, ships, and offshore platforms.
Product Characteristics:
  • SCB serial dry type transformer is maintenance-free, pollution-free, and compact, suitable for direct installation in load centers.
  • Operates at 140% of rated load under forced air cooling.
Technical Data:
  • Rated Capacities range from 30 kVA to 2500 kVA.
  • Voltage and Tapping Range: HV (Input) 6-11 kV with ±5% or ±2×2.5% tapping range; LV (Output) 0.4 kV.
  • Vector Group: Yyno, Dyn11.
  • No-load and Load Losses, Short-circuit Impedance, and No-load Current values provided for each capacity.
See more

Catalog excerpts

SCB dry type transformer-1

Dry type transformer Product description SCB serial dry type transformer is an epoxy resin casting dry type transformer. Due to the coil being encapsulated by epoxy resin, it has the characteristics of flame retardancy, fire resistance, explosion resistance, maintenance free, pollution-free, and small size, and can be directly installed in the load center. Under the condition of forced air cooling, it can operate for a long time at 140% of the rated load and is equipped with an intelligent temperature controller with functions such as fault alarm, overtemperature alarm, overtemperature trip. It is connected to a computer through an RS485 serial interface for centralized monitoring and control. Due to the above characteristics, our dry-type transformers are widely used in power transmission and transformation systems, such as hotels, airports, high-rise buildings, commercial centers, residential quarters. And also the environment, such as subways, smelting power plants, ships, offshore drilling platforms and other harsh places. • The iron core is made of high-quality cold-rolled silicon steel sheets, and the surface of the iron core is sealed with insulating resin paint to prevent moisture and rust, reducing no-load losses, no-load currents, and iron core noise. • The high voltage windings are vacuum pressure cast with filled epoxy resin, greatly reducing the partial discharge and improving the electrical strength of the coil. The inner and outer walls of the winding are filled with glass fiber mesh boards to enhance the mechanical strength of the coil and improve the product's ability to resist sudden short circuits. • The low-voltage winding adopts a foil structure, which solves the problem of axial helix angle during winding and makes the ampere-turns more balanced. At the same time, the coil adopts an axial cooling air duct to enhance the heat dissipation capability. • The insulation material is epoxy resin, and the transformer has the characteristics of flame retardant, fireproof, explosion-proof, and pollution-free. • The partial discharge is smaller, the noise is low, the loss is low, the heat dissipation capacity is strong, and the overload capacity is strong. • Altitude: not more than 1000m; • If the altitude exceeds 1000m, or the ambient temperature is higher than 40°C , appropriate quota adjustments should be made according to GB6450-1986 standard and relevant regulations. • Installation place: a place without fire, explosion hazard, conductive dust, chemical corrosive gas and severe vibration. SCB11 serial dry type transformer Voltage & Tapping range Tapping range Vector group load loss Short-circuit impedance (%) No-load current (%)

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.
About DirectIndustry
DirectIndustry is a marketplace that offers B2B players a complete experience, from product sourcing to purchase. DirectIndustry is an entity of VirtualExpo Group.