The gas-insulated switchgear is a fully sealed and insulated SF6 gas-filled ring main switchgear. It consists of modules such as load switch units, load switch fuse combination units, vacuum circuit breaker units, and busbar incoming line units. It features advanced technology and materials, offering excellent electrical and mechanical properties, minimal environmental impact, compact size, easy installation, and maintenance-free operation. The design allows for flexible combinations and large feeder wiring capacity suitable for various systems.
| Item | Description | Unit | C Module | F Module | V Module | CB Module |
|---|---|---|---|---|---|---|
| Rated Voltage | kV | 12 | 12 | 12 | 12 | |
| Rated Frequency | Hz | 50 | 50 | 50 | 50 | |
| Power Frequency Withstand Voltage | kV | 42/48 | 42/48 | 42/48 | 42/48 | |
| Lightning Impulse Withstand Voltage | kV | 75/85 | 75/85 | 75/85 | 75/85 | |
| Rated Current | A | 630 | Depends on fuse | 630 | 1250/630 | |
| Rated Closed-loop Breaking Current | A | 630 | ||||
| Rated Cable Charging Breaking Current | A | 135/135 | ||||
| Rated Short-circuit Making Current (Peak) | kA | 50 | 80 | |||
| Rated Peak Withstand Current | kA | 50 | ||||
| Rated Short-time Withstand Current | kA/3s | 20 | ||||
| Rated Short-circuit Breaking Current | kA | 31.5 | 20 | 25 | 25 | |
| Rated Transfer Current | A | 1750 | ||||
| Maximum Current of Fuse Used | A | 125 | ||||
| Loop Resistance | Ω | ≤ 300 | ≤ 600 | |||
| Mechanical Life | times | 5000 | 3000 | 5000 | 2000 | 5000 |
Gas insulated switchgear Product description Fully sealed and fully insulated gas-filled ring main switchgear is a SF6 gas-insulated metal common box enclosed switchgear. This device can be composed of modules of load switch unit, load switch fuse combination electrical unit, vacuum circuit breaker unit and busbar incoming line unit. It adopts a series of advanced technologies and materials, has excellent electrical and mechanical properties, is less affected by the environment and climate, is small in size, easy to install, easy to operate, maintenance-free, and has flexible combination methods. The clear and intuitive design ensures simple and direct operation. The feeder wiring capacity is large and suitable for a variety of wiring systems. • Integrated three-position load switch, the circuit breaker uses load switch instead of isolating switch, which is safer and more reliable. The fully enclosed design on the primary side provides protection against accidental contact and meets the mechanical interlocking requirements of the five protections. • Fully enclosed design, all 10kV switches and busbar live parts are sealed in a gas box welded from 3mm stainless steel plates. • Equipped with silicone rubber cable plugs, the cable head is fully insulated and sealed, so that the spring energy storage operating mechanism is not affected by external environments such as dust, moisture, and small animals. • Pressure gauge monitors the safe pressure range of SF6 gas in the box. • Economical: maintenance-free, highly reliable, and service life can reach 20 years. • Multiple combinations can be realized, and any combination between units can be realized. • Altitude: not more than 1000m; • If the altitude exceeds 1000m, or the ambient temperature is higher than 40°C , appropriate quota adjustments should be made according to GB6450-1986 standard and relevant regulations. • Installation place: a place without fire, explosion hazard, conductive dust, chemical corrosive gas and severe vibration. General specifications