Product IntroductionThe UHV-341
Transformer Tan Delta Tester is a precision instrument designed for measuring the dielectric loss tangent and capacitance of high-voltage power equipment. It is suitable for use in power plants, substations, workshops, laboratories, and research units. The tester uses frequency conversion technology to ensure accurate measurements even under strong electric field interference. It features an automated measurement process with a user-friendly Chinese menu interface.
Product Features- High voltage short circuit protection
- CVT overvoltage protection
- Protection for equipment not well grounded
Technical Parameters- High voltage output: 0.5~10kV, increasing by 500V per level, with a total of 20 levels and a capacity of 1500VA
- Accuracy: tgδ: ± (reading *1.5% +0.06%), Cx: ± (reading * 1.5% +5 PF)
- Resolution: tgδ: 0.01%
- Measuring range: 0.01% < tgδ < 100%, 3PF < Cx < 60000PF
- Power supply: AC 220V ± 10%, 50 ± 1Hz
- Measuring method: 50Hz working frequency, 45Hz/55Hz automatic frequency conversion
- Harmonic adaptation: ≤ 3%
- Application condition: -15 ℃ to 50 ℃, relative humidity <80%
- Dimensions: 460 (L) × 345 (W) × 350 (H) mm
- Weight: 35 kg
Additional InformationThe UHV-341 is equipped with a high-voltage step-up transformer and safety features such as zero-crossing and lightning protection. It can measure high-voltage equipment that is not grounded and the tgδ of capacitive voltage transformers, as well as the capacitance of main capacitors C1 and C2.