FE180/E90
12Pages

{{requestButtons}}

Catalog excerpts

FE180/E90 - 1

Specially designed for safety installations Flat Cable System pyroLINE E90 Swiss made

Open the catalog to page 1
FE180/E90 - 2

pyroLINE 2 3G2.5mm Thanks to this installation system based upon at cable, all the components related to safety are continuously supplied, even in case of re. The high degree of protection enables this system to be used even under stringent conditions. End piece IP68, No. 48510/08 • New end piece with IP66/68 protection degree • Quick and safe mounting without the cable insulation having to be stripped. Tools are not necessary. Flat cable 3x2.5mm2, No. 48250/FE180/NS/OR • Cables are running in parallel to increase installation safety • Insulation is maintained during 180 minutes: the exible...

Open the catalog to page 2
FE180/E90 - 3

Mounting procedure of connecting box No. 48253/L/68/E90 (may be used for both feeding and branching) Remove the cover plate of the box. The cable gland has to be prepared and mounted on the branching cable (round cable). Cut the latter to the desired length and dismantle it. Introduce the stripped leads. 1 Tighten up the 3 screws. Once the O-ring positions correctly in the cable gland, tighten up the latter. Philips No.1 0.7Nm 6.2lb-in 2 1 Position the at cable in the right position. The lug in the base acts as a reference point. It has to match the lug of the at cable. In case of incorrect...

Open the catalog to page 3
FE180/E90 - 4

Woertz pyroLINE 3G2.5mm2, at cable FE180 for E90 applications - parallel conductors - asymmetric at cable to avoid reverse polarity - ceramic insulated cores (re blocking barrier) - sheath with additives to keep away rodents Flat cable FE180, halogen-free L+N+PE No. Orange sheath Yellow sheath 48250/FE180/NS/OR 48250/FE180/NS/GE Technical data Sheath Colour of the sheath Dimensions Weight Fire load No. of leads x cross-section Copper conductors Insulation of the leads Colour of the leads Test voltage Rated voltage Properties of material Polyolene thermoplastic compound according to HD...

Open the catalog to page 4
FE180/E90 - 5

Woertz at cable box for E90 applications - E90 system component - no source of possible error: cable never has to be interrupted - protected against reverse polarity - marking eld on the cover - IP68 protection E90 box for feeding and branching E90 3x2.5mm2 No. 48253/L/68/E90 Technical data Weight Dimensions ~330g 137x50x49mm (without cable gland) Norms connecting material according to IEC 60998-1 connecting terminal according to IEC 60998-2-1 sheath piercing technology according to IEC 60998-2-3 IP protection according to IEC 60529 Function integrity E90 according to DIN 4102 Part 12...

Open the catalog to page 5
FE180/E90 - 6

Flat cable accessories End piece without cable stripping 48510/08 Of polycarbonate, halogen-free, with silicone gel Dimensions: 40x36x16mm Weight: non specied Fire load: non specied Packing unit: 5 pieces Note: The cable has to be stripped at both ends for a distance of 19mm so that the conductors can be inserted properly in the end pieces. Shears 49930 For cutting neatly and easily every type of at cables (max. width 32mm). With sliding anvil. Teon coated blades. Packing unit: 1 piece 49960 To reinsulate correctly the holes due to pointed screws or cutting teeth when removing or displacing...

Open the catalog to page 6
FE180/E90 - 7

Woertz duct system for E90 applications - E90 system component insulated support plates avoid short-circuits earthing unnecessary great distance between fastening points of the bracket - high corrosion resistance E90 duct system No. Technical data Material glass ber reinforced polyester resin provided with a re proof fabric tape Marking E30 - E90 Woertz duct production date, order number, meter marks Colour Dimensions Weight Properties of material yellow 80x55x2400mm 545g/m E90 NC = non-corrosive gas on the basis of IEC 60754-2 LS = low smoke on the basis of IEC 61034-2 0H = halogen-free on...

Open the catalog to page 7
FE180/E90 - 8

Duct accessories Bracket 130 - Dimensions approx. 130x65x30mm Weight approx. 100g E30–E90 function integrity, according to DIN 4102 part 12 Metal parts of V4A steel (corrosion-resistant) - Dimensions approx. 300x65x30mm Weight approx. 210g E30-E90 function integrity, according to DIN 4102 part 12 Metal parts of V4A steel (corrosion-resistant) - Dimensions approx. 300x20x32mm Weight approx. 390g E30-E90 function integrity, according to DIN 4102 part 12 Metal parts of V4A steel (corrosion-resistant) - Dimensions approx. 130x117x80mm Weight approx. 575g E30-E90 function integrity, according to...

Open the catalog to page 8
FE180/E90 - 9

Gotthard base tunnel Emergency lighting in railway tunnel Get ready for every eventuality. Emergency lighting may save lifes. Safety rst even in the longest tunnel in the world. Great attention is paid to workers safety and not only through the building phase. In the Gotthard base tunnel everybody has to get ready in the eventuality something unforeseen happens. Even after several years of operation a visible and good working emergency lighting is essential. The Woertz at cable has to meet new requirements thus. Thanks to the recently designed at cable with insulation integrity up to 180...

Open the catalog to page 9
FE180/E90 - 10

Basic norms and concepts The requirements in terms of function integrity are very high. And norms and system concepts are extensive. All Woertz halogen-free cables (FRLS/0H) are conforming to following norms: Features of at cable system Norms Halogen-free (0H), non-corrosive gas IEC 60754-2 EN 50267 Self-extinguishing (FR) IEC 60332-1 EN 60332-1 Low heat conductivity IEC 60332-3 CAT.C EN 50266-2-4 Low smoke (LS) IEC 61034 EN 50268 Structure of the cable, on basis of DIN VDE 250-214 and DIN VDE 0281 The Woertz pyroLINE at cable is also conforming to following norms: Features of at cable...

Open the catalog to page 10
FE180/E90 - 11

Selection criteria for cables Cables have to be chosen early enough. The size of the project and the building‘s use for instance should be known. In a at cable installation, additionnal loads may be connected anytime at any point. The Woertz at cable is an interesting, reliable and worthwhile investment thus. Safety cables Safety cables prevent from re propagation. The electrical function of the cable is not taken into account - only its passive behavior in the event of re is important. Compared to usual halogen-free cables, safety cables only burn close to the ignition source. Safety...

Open the catalog to page 11

All Woertz catalogs and technical brochures

  1. ATEX-Sortiment

    15 Pages

Archived catalogs

  1. Junction Boxes

    19 Pages

  2. Screw terminals

    140 Pages