1. Catalogs
  2. West Control Solutions
  3. 2-phase with heatsink

2-phase with heatsink

2-phase with heatsink

2-phase with heatsink

Product catalog summary
Main Characteristics:
  • Two-phase controlled with zero switching and LED display.
  • Various connection technologies available.
  • Plug-in control terminal with degree of protection IP 20.
  • Insulated mounting foot.
Standards / Approvals:
  • Complies with DIN EN 60947-4-3, UL 508 / CSA1, CE, and C-Tick standards.
Ordering Key:
  • Model: 3RF24 10 - 1 A B 4 5.
  • Max load current options: 10.5 A, 22 A, 30 A, 40 A, 50 A.
  • Connection technology: Screw, Spring-loaded, or Ring cable connection.
  • Switching function: Zero-point switching.
  • Controlled phases: Two-phase.
  • Control voltage: 4 - 30 VDC or 190 - 230 VAC.
  • Operating voltage: 48 - 600 V.
Main Circuit:
  • Values provided for 40°C ambient temperature.
  • Power loss and leakage current details for different models.
Control Circuit A1-A2:
  • Control voltage range: AC 190-230 V, DC 4-30 V.
  • Typical operating current: 15 mA (AC), 30 mA (DC).
  • Switching times: ON delay 40 ms, OFF delay 40 ms.
General Data:
  • Operating temperature: -25°C to 60°C.
  • Storage temperature: -55°C to 80°C.
  • Mounting altitude: 0 to 1000 m.
  • Impact and vibration resistance specified.
  • Degree of protection: IP20.
  • Electromagnetic compatibility: Class A for industrial applications.
Connection Details:
  • Various connection options with specified conductor cross-sections and stripping lengths.
Fused Design with Semiconductor Protection:
  • Details on semiconductor protection fuses for different models.
Accessories:
  • Function module converter available for specific versions.
Characteristic Curves:
  • Graphs provided for thermal limit current, rated current, and power loss across different ambient temperatures.
Mounting Instructions:
  • Includes device and example circuit diagram.
Dimension Drawings:
  • Dimensions provided in mm for stand-alone and side-by-side mounting.
See more

Catalog excerpts

2-phase with heatsink-1

PMA ProzeB- und Maschinen-Automation GmbH Solid State Relays, 2-phase controlled Zero-Point switching, heatsink intgrated Main Characteristics: Two-phase controlled Zero switching Various connection technologies Plug-in control terminal Insulated mounting foot_ Standards / Approvals: Not all possible versions are available ex stock! 1 Use overvoltage protection device; max cut-off-voltage 6.000 V; min energy handling capability 100 J

 Open the catalog to page 1
2-phase with heatsink-2

Control Circuit A1-A2: Type Control voltage Us Max. control voltage Us Typical operating current Response voltage Drop-out voltage Rated frequency of the control supply voltage Switching times ON delay OFF delay V V mA V V 3RF24. . - . A B 5 . AC 190 ... 230 253 15 180 <40 3RF24. . - . A B 4 . DC 4 ... 30 30 30 4 <1 Hz 50/60 ± 10 % -- ms ms 40 + Max. one half-wave 40 + Max. one add. half-wave 1 + Max. one half-wave 1 + Max. one add. half-wave General Data: Ambient temperature During operation During storage Mounting altitude Impact resistance acc. to DIN IEC 68 Vibration resistance Degree of...

 Open the catalog to page 2
2-phase with heatsink-3

Type 3RF24. . - 1 . Connection, main contacts Screw connection 3RF24. . - 2 . Spring-loaded connection 3RF24 . . - 3 . Ring cable connection Conductor cross-section mm2 o Solid o Finely stranded with end sleeve mm2 Finely stranded w/o end sleeve Solid or stranded Stripping length Terminal screw o Tightening torque D 5...6 mm / PZ 2 Cable lug DIN JIS Connection, control contacts o o Conductor cross-section with or without end sleeve Stripping length Terminal screw o Tightening torque D 3.5 / PZ 1 2 x (1.5 ... 2.5), 2 x (2.5 ... 6) 2 x (1.5 ... 2.5), 2 x (2.5 ... 6), 1 x 10 2 mm AWG mm Nm lb.in...

 Open the catalog to page 3
2-phase with heatsink-5

3RF2440-. 3 50 110 45 100 40 90 80 Power loss in W 35 Ie in A Upper curves: Imax thermal limit current Middle curves: Rated current Ie acc. to UL Lower curves: Rated current Ie acc. to DIN EN 60947-4-3 30 25 20 70 60 50 40 15 10 20 5 10 0 For: Stand-alone and side-byside mounting 30 0 0 20 40 Ambient temperature Ta in °C 0 60 8 16 24 32 40 48 Ie in A 3RF2450-. 3 60 120 55 100 50 Power loss in W 45 Ie in A 40 35 30 25 20 80 60 40 15 20 10 5 0 0 0 3 20 40 Ambient temperature Ta in °C 0 10 20 30 40 50 Ie in A 60 Identical current/temperature curves for Stand-alone and side by side mounting. Subject...

 Open the catalog to page 5
2-phase with heatsink-8

PMA Your local representative: ProzeB- und M as chine n- Automation GmbH E-mail: [email protected] Internet: http://www.pma-online.de Printed in Germany - Edition 0 /200 - Subject to alteration without notice - 9498 737 53 13

 Open the catalog to page 8
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.