Naming Rule
The LX3V I/O output extension module follows a specific naming convention: LX3V - 16 E X. The components of the name are as follows: ① Wecon series programming logic controller, ② Extension input point, ③ Extension module, ④ Extension input (X), ⑤ Type of output (T for transistor, R for relay).
External Dimensions
The module weighs approximately 0.3 kg (0.661 lbs) and includes several key features: an extension cable and connector, power LED (lights when connected to 24V), state LED (lights under normal conditions), module name, analog signal output terminal, extension module interface, DIN rail mounting slot, DIN rail hook, and mounting holes (φ4.5).
Output Specification
The LX3V-16EX module operates with a DC input voltage of ±24V±10% and an input current of 5mA at DC24V. The input ON current is less than 3.5mA, and the input OFF current is less than 1.5mA. The input response time is approximately 10ms, with a built-in digital filter for X0~X7, allowing a setting time of 0 to 60ms. The input signal can be either contactor NPN or PNP, and circuit insulation is achieved through photo coupling. The LED indicator lights up when the input is ON. It is important to adhere to the specified voltage range for DC power supply.
See more

Catalog excerpts

WECON PLC Extend module LX3V-EX-1

Wecon Technology Co.Ltd., SITE: http://en.we-con.com.cn Technical Support: [email protected] Skype: fcwkkj PHONE: 86-591-87868869

 Open the catalog to page 1
WECON PLC Extend module LX3V-EX-2

Naming rule of LX3V I/O output extension module: © Wecon series programming logic controller © Extension input point Dimensions:mm (inches) © Extension cable and connector © Power LED: Light when connect to 24V © State LED:Light when normal condition ©Analog signal output terminal © Extension module interface © DIN rail mounting slot 2.1 Using crimp terminations less than less than Use crimp terminations of the type indicated on the left. Secure the termination using a tightening torque of between 5 and 8 Wire only to the module terminals discussed in this manual. Leave

 Open the catalog to page 2
WECON PLC Extend module LX3V-EX-3

Output circuit Input voltage Input current Input response time About 10ms X0~X7 built-in digital filter,setting time 0 ~ 60ms Input signal Circuit insulation Photo coupling * When power supply is DC, please follow the instruction of voltage range in each unit.