LX3V-4AD Module
9Pages

{{requestButtons}}

Catalog excerpts

LX3V-4AD Module - 1

Wecon Technology Co.Ltd., SITE: http://en.we-con.com.cn Technical Support: liux@we-con.com.cn Skype: fcwkkj PHONE: 86-591-87868869

Open the catalog to page 1
LX3V-4AD Module - 2

The LX3V-4AD special module has four input channels.The input channels receive analog signals and convert them into a digital value.This is called an A/D conversion, the maximum resolution is 12 bits. The selection of voltage or current based input/output is by user wiring.Analog ranges of -10 to 10V DC Data transfer between the LX3V-4AD and the LX3V main unit is by buffer memory exchange. There are 32 buffer memories (each of 16 bits) in the LX3V-4AD. LX3V-4AD consume 5V voltage from LX3V main unit or active extension unit,90mA current of power © Extension cable and connector © Com...

Open the catalog to page 2
LX3V-4AD Module - 3

The analog input is received through a twisted pair shielded cable. This cable should be wired separately from power lines or any other lines which may induce electrical noise. If a voltage ripple occurs during input, or there is electrically induced noise on the external wiring, connect a smoothing capacitor of 0.1 to 0.47uF, If you are using current input, connect the V+ and l+ terminals to each other. If there is excessive electrical noise, connect the FG frame ground terminal with the grounded Connect the ground terminal on the LX3V-4AD unit with the grounded terminal on the main unit....

Open the catalog to page 3
LX3V-4AD Module - 4

Analog Inputs continued. Current input Current input Preset ranges are selected by an appropriate setting in buffer memory of the analog block. Current/Voltage input selection must match the correct input terminal connections.

Open the catalog to page 4
LX3V-4AD Module - 5

Reserved Reset to Defaults and Preset. Default = 0 Offset, Gain Adjust Prohibit. Default = (0, 1) Permit Offset, Gain Adjust G4 O4 Offset Value Default = 0 Gain Value Default = 5,000 Reserved Error status Identification code K2010 Cannot be used In buffer memory locations (BFM’s)marked with an “*” data can be written from the PC using the TO command. For buffer memories (BFM’s) without “*”mark, data can be read to the PC using the FROM command. Before reading from the analog special function block, ensure these settings have been sent to the analog special function block. Otherwise, the...

Open the catalog to page 5
LX3V-4AD Module - 6

(c) Gain and offset values of BFM #23 and #24 are sent to non-volatile memory gain and offset registers of the specified input channels. Input channels to be adjusted are specified by the appropriate G-O (gain-offset) bits of BFM #22. Example:If bits G1 and O1 are set to 1,input channel 1 will be adjusted when BFM #22 is written to by a TO instruction. (d) Channels can be adjusted individually or together with the same gain and offset values. (e) Gain and offset values in BFM #23 #24 are in units of mV or µA. Due to the resolution of the unit the actual response will be in steps of 5mV or...

Open the catalog to page 6
LX3V-4AD Module - 7

5. Defining gain and offset Gain determines the angle or slope of the calibration line,identified at a digital value of 1000. (a) Small gain Large steps in digital readings (b) Zero gain default : 5V or 20mA. (c) Large gain Small steps in digital readings. Offset is the ‘Position of the calibrated line, identified at a digital value of 0. (d) Negative offset. (e) Zero offset default : 0V or 4mA. (f) Positive offset. Offset and gain can be set independently or together. Reasonable offset ranges are -5 to +5V or -20mA to 20mA, and gain values 1V to 15V or 4mA to 32mA. Gain and offset can be...

Open the catalog to page 7
LX3V-4AD Module - 8

The ID code for the special function block at position "0" is read from BFM #30 of that block and stored at D4 in the main unit. This is compared to check the block is a LX3V-4AD, if OK M1 is turned ON. These two program steps are not strictly needed to perform an analog read. They are however a useful check and are recommended as good practice. The analog input channels (CH1, CH2) are setup by The number of averaged samples for CH1 and CH2 is The operational status of the LX3V-4AD is read from BFM #29 and output as bit devices at the LX3V main If there are no errors in the operation of the...

Open the catalog to page 8
LX3V-4AD Module - 9

(HOOOO) -> BFM #0 (initialize input channels) Enter the instructions on the left and RUN the PC. BFM #21 (gain/offset adjust prohibit) must be set to permit with Reset adjust bits. Therefore channel 1 is adjusted. BFM #21 gain/offset adjust prohibit. I.Check whether the input wiring and/or extension cables are properly connected on LX3V-4AD analog special function block. II.Check that the LX3V system configuration rules have not been broken, i.e. the number of special function blocks does not exceed 8 and the total system I/O is equal or less than 256 I/O. III.Ensure that the correct...

Open the catalog to page 9