1. Catalogs
  2. weber Sensors GmbH
  3. Data sheet supply unit 802x

Data sheet supply unit 802x

Data sheet supply unit 802x

Data sheet supply unit 802x

Product catalog summary
Overview: The document provides technical specifications and operational details for supply units designed for 24 VDC sensors, specifically vent- and flow-captors, with AC supply voltage. It includes information on two types of supply units, Type 8020 and Type 8021, each catering to different sensor outputs.
Specifications:
  • Type 8020: Suitable for PNP-switching sensors or sensors with an analog output signal. It activates a switch signal when a fixed threshold of 50% of the max input signal is reached, allowing for adjustable switching points.
  • Type 8021: Designed for NPN-switching sensors, triggering the output relay directly from the sensor's switching output.
Technical Data:
  • Sensor Output: Type 8020 supports PNP or Analog, while Type 8021 supports NPN.
  • Connecting Data: 9 - 36 VDC, 18 - 75 VDC, 24 VDC max. 125 mA with short circuit detection.
  • Signal Input: UE on ≤ 6 V, UE off ≤ 18.5 V, with a resistance of approximately 500 Ω and a threshold switch of 12 mA.
  • Relay Contact Data: Maximum switching voltage of 30 VDC/240 VAC and a maximum switching current of 2.5 A AC/DC.
  • Mechanical Data: Protection standard IP 40 for clamp housing, with dimensions of 55 x 75 x 110 mm and a mass of 350g.
  • Electrical Data: Operates on 85 - 264 VAC, with a power consumption of max. 5.5VA.
Housing and Installation: The supply units are housed in a clamp housing suitable for standard bars as per DIN 46277 and DIN EN 50022, making them ideal for installation in switch cabinets.
Order Description: The document lists various configurations for ordering, including different voltage ranges for both Type 8020 and Type 8021.
See more

Catalog excerpts

Data sheet supply unit 802x-1

supply unit Type 8020, 8021 This supply unit is allowed for the operation of 24 VDC sensors, such as vent- and flow-captors, with AC supply voltage. The supply unit contains a 24 VDC transformer rectifier and a switching circuit with output relay with potential free single pole double throw switching contact. An integrated LED plays the actual switching situation. Housing: Clamp housing for standard bar as per DIN 46277 and DIN EN 50022 for the installation in switch cabinets or similar. Supply Unit Variations: Type 8020 : For PNP-switching sensors or sensors with analog output signal. On connection of an analog signal to the input of the supply unit a switch signal is activated which controls an integrated relay when a fixed threshold of 50 % of the max. input signal is reached. This provides the possibility, when connecting flow· and vent-captors with adjustable measuring range, to vary the switching point on a large scale; e.g. for the flow-captor 4114.30 related to water at flow velocity between 10 cm/s and 100 cm/s, resp. for the vent·captor 3202.30 related to air between 50 cm/s and 25 m/s. Type 8021 : For NPN-switching sensors. These units trigger the output relay directly from lhe switching output of the sensor. Technical data Type Sensor output Connecting data for captor supply Signal input 9 - 36 VDC, 18 - 75 VDC 24 VDC max. 125 mA, short circuit detected 85 - 264 VAC 24 VDC max. 230 mA, short circuit detected Ri approx. 500 Ω, UE on ≤ 6 V Ie limited to 15 mA UE off ≤ 18.5 V threshold switch 12 mA, hysteresis ± 0.8 mA Contact data of relay Switching voltage max. Switching current max. Mechanical data Protection standard Sizes (l x w x h) and mass Electrical data Power consumption 30 VDC/240 VAC 2.5 A AC/DC clamp housing IP 40* *(clamps: IP20 and contact protected accord to VDE 100 Teil 750 und VBG 4) Airgap and creepage distance according to VDE 0110 Gruppe C, 380 VE clamp housing: 55 x 75 x 110 mm, 350g 9 - 36 VDC max. 4W www.captor.de [email protected] Tel.: +49 (0)4128 - 591· Fax: - 593 DE-25377 Kollmar Sensors GmbH Strohdeich 32 [email protected] Tel.: +44 (1704) - 551684 · Fax: - 551297 Merseyside PR8 4DU, UK 66 Eastbourne Road, Southport Sensors Ltd. Sensors LLC. 4462 Bretton Court, Building 1, Suite 7 Acworth, Georgia 30101, USA Tel.: +1 (770) 592 - 6630 · Fax: - 592 6640 [email protected] Technical data subject to alteration! Rev. AD

 Open the catalog to page 1
Data sheet supply unit 802x-2

weber supply units Dimensioned Drawing Type 8020, 8021 Rapid– clamping for standard bar as per DIN 46277 DIN EN 50022 possible Order Description www.captor.de [email protected] Tel.: +49 (0)4128 - 591· Fax: - 593 DE-25377 Kollmar Sensors GmbH Strohdeich 32 [email protected] Tel.: +44 (1704) - 551684 · Fax: - 551297 Merseyside PR8 4DU, UK 66 Eastbourne Road, Southport Sensors Ltd. Sensors LLC. 4462 Bretton Court, Building 1, Suite 7 Acworth, Georgia 30101, USA Tel.: +1 (770) 592 - 6630 · Fax: - 592 6640 [email protected] Technical data subject to alteration! Rev. AD 03.02.

 Open the catalog to page 2