Overview: The document provides technical specifications and installation guidelines for the Watts Series 007 Double Check Valve Assemblies, designed for non-health hazard applications to prevent backflow of polluted water into potable water supplies.
Specifications: The valve assemblies are available in sizes ranging from 1/2" to 3" (15-80mm). They consist of two positive seating check modules with replaceable seats and rubber seat discs. The assemblies include resilient seated isolation valves and top-mounted test cocks. They meet ASSE Std. 1015 and AWWA Std. C510 standards and are approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California.
Features: Key features include ease of maintenance with a single cover, top entry, modular construction, compact design, and no special tools required for servicing. The body construction varies with size, using cast bronze for 1/2" to 2" and fused epoxy-coated cast iron for 2 1/2" to 3".
Installation Requirements: Installation should comply with local authority guidelines, particularly regarding vertical orientation and testing frequency. The assemblies are suitable for cross-connections identified as non-health hazards by local inspection authorities.
Pressure and Temperature Ratings: For sizes 1/2" to 2", the temperature range is 33°F to 180°F with a maximum working pressure of 175 psi. For sizes 2 1/2" to 3", the continuous temperature range is 33°F to 110°F, with intermittent up to 140°F, and the same maximum pressure.
Approvals and Standards: The assemblies are approved by ASSE, AWWA, IAPMO, CSA, and UPC. UL classification applies to certain models and configurations.
Dimensions and Weights: Detailed dimensions and weights are provided for various models and sizes, highlighting the compact and efficient design of the assemblies.
Flow and Pressure Drop: Graphs and data tables illustrate the pressure drop across different flow rates for various sizes, indicating the efficiency and performance of the valve assemblies under typical conditions.
See more

Catalog excerpts

Series 007-1

ES-007 For Non-Health Hazard Applications Job Name ––––––––––––––––––––––––––––––––––––––––––– Contractor –––––––––––––––––––––––––––––––––––––––––––– Job Location ––––––––––––––––––––––––––––––––––––––––– Approval Engineer ––––––––––––––––––––––––––––––––––––––––––––– Contractor’s P.O. No. ––––––––––––––––––––––––––––––––––– Approval ––––––––––––––––––––––––––––––––––––––––––––– Representative ––––––––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––– Series 007 Double Check Valve Assemblies Sizes: 1⁄2" – 3" (15 – 80mm) Series 007 Double Check Valve Assemblies shall be installed at referenced cross-connections to prevent the backflow of polluted water into the potable water supply. Only those cross-connections identified by local inspection authorities as non-health hazard shall be allowed the use of an approved double check valve assembly. 34 ⁄ " (20mm) 007M3QT Check with local authority having jurisdiction regarding vertical orientation, frequency of testing or other installation requirements. The valve shall meet the requirements of ASSE Std. 1015 and AWWA Std. C510. Approved by the Foundation for CrossConnection Control and Hydraulic Research at the University of Southern California. Features • Ease of maintenance — only one cover • Top entry • Replaceable seats and seat discs 2" (50mm) 007M1QT HC Test Cocks • Modular construction • Compact design • Cast bronze body construction — 1⁄2" – 2" (15 – 50mm) • Fused epoxy coated cast iron body — 21⁄2" – 3" (65 – 80mm) • Top mounted ball valve test cocks • Low pressure drop • No special tools required for servicing • 1⁄2" – 1" (15 – 25mm) have tee handles Specifications A Double Check Valve Assembly shall be installed at each noted location. The assembly shall consist of two positive seating check modules with captured springs and rubber seat discs. The check module seats and seat discs shall be replaceable. Service of all internal components shall be through a single bronze or stainless steel access cover secured with stainless steel bolts. The assembly shall also include two resilient seated isolation valves; four top mounted, resilient seated test cocks. The assembly shall meet the requirements of ASSE Std. 1015 and AWWA Std. C510. Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. Assembly shall be a Watts Series 007. First Check Module Assembly Second Check Module Assembly The 007 Series features a modular design concept which facilitates complete maintenance and assembly by retaining the spring load. Now Available WattsBox Insulated Enclosures. For more information, send for literature ES-WB. IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES FOR LOCAL INSTALLATION REQUIREMENTS Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

 Open the catalog to page 1

All Watts Water Technologies catalogs and technical brochures

  1. Ball Valves

    28  Pages

  2. Solar Solutions

    20  Pages

  3. Series X65B

    2  Pages

  4. Steam Products

    24  Pages

  5. 008 PCQT

    2  Pages

  6. Series 17

    1  Page

  7. Series 152SS

    2  Pages

  8. Series 152A

    2  Pages

  9. Series 150A

    2  Pages

  10. Series 1450F

    1  Page

  11. Series 144

    2  Pages

  12. Series 142

    2  Pages

  13. Model 127W

    2  Pages

  14. ES-127

    2  Pages

  15. Series 123LP

    1  Page

  16. Series 1156F

    2  Pages

  17. Series 100DT

    1  Page

  18. Series 05

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.