JOVYSTAR hp

JOVYSTAR hp

JOVYSTAR hp

Product catalog summary
Overview: The JOVYSTAR hp series is part of the JOVY-ATLAS UPS line, designed for high-performance power supply protection in environments such as stadiums, data centers, and industrial plants. These systems offer outputs ranging from 200 to 800 kVA and utilize dual transducer technology (VFI-SS-111) with a static bypass, ensuring optimal protection for critical devices.
Key Features:
  • Dual independent microprocessors control the rectifier, inverter, and static bypass.
  • Parallel connection of up to 6 systems for redundancy or increased output.
  • Modern IGBT rectifiers reduce supply network interruptions and improve power factor, consuming up to 30% less input power than standard systems.
  • Low harmonic oscillations protect against overloading of on-site supply systems.
  • Easy maintenance with front-side access to major components and a user-friendly operating panel.
Technical Specifications:
  • Input Voltage: 3 x 400/230 V with a tolerance of +15% to -20%.
  • Input Frequency: 50 Hz / 60 Hz ± 5Hz.
  • Efficiency: > 93% at nominal load, > 98% in Eco-Mode.
  • Overload Capacity: 100% - 125% for 10 minutes, <150% for 1 minute, 150% for 10 seconds.
  • Operating Temperature: 0 - 40°C, with optional battery temperature of 20°C ± 5°C.
  • Humidity: <95% (no condensation).
Model Variants and Dimensions:
  • JOVYSTAR HP 200-0: 1220 x 1905 x 895 mm, 870 kg, Autonomy: 0 - 6 - 13 - 20 - 27 - 40 - 60 min.
  • JOVYSTAR HP 250-0: 1220 x 1905 x 895 mm, 1020 kg, Autonomy: 0 - 6 - 14 - 25 - 50 - 70 min.
  • JOVYSTAR HP 300-0: 1220 x 1905 x 895 mm, 1200 kg, Autonomy: 0 - 6 - 11 - 15 - 27 - 40 - 55 min.
  • JOVYSTAR HP 400-0: 1990 x 1920 x 990 mm, 1820 kg, Autonomy: 0 - 5 - 12 - 20 min.
  • JOVYSTAR HP 500-0: 2440 x 2020 x 990 mm, 2220 kg, Autonomy: 0 - 6 - 10 - 15 min.
  • JOVYSTAR HP 600-0: 2440 x 2020 x 990 mm, 2400 kg, Autonomy: 0 - 5 - 10 min.
  • JOVYSTAR HP 800-0: 3640 x 1920 x 990 mm, 3600 kg, Autonomy: 0 - 5 - 10 min.
Additional Information: The JOVYSTAR hp series is suitable for emergency power operations with power generators. The systems feature a clear text display for measurements, alarms, and status reports, and offer both automatic and manual battery testing options.
See more

Catalog excerpts

JOVYSTAR hp-1

Product Range www.jovyatlas.de www.jovyatlas.de www.jovyatlas.de Power Supply Protection for Entertainment (e.g. stadiums) data centers, industrial plants etc. JOVYSTAR hp UPS-systems out of the JOVYSTAR hp - series rounds off the JOVYATLAS UPS line in the high performance range. JOVYSTAR hp series systems offer optimal protection for critical devices and are available with outputs of 200 up to 800 kVA. JOVYSTAR hp systems work with dual transducer technology (VFI-SS-111 in accordance with EN 62040-3) and they are equipped with a static bypass. An optional external manual bypass is also available. A significant security feature is provided by the two independent microprocessors, controlling the rectifier, inverter and static bypass. Up to 6 systems can be connected parallel to provide for redundant operation (half load parallel operation, n+1 operation) or to increase the output – this allows the UPS system to be augmented to answer increasing power requirements. The use of modern IGBT rectifiers significantly reduces interruptions in the supply network. The innovative IGBT rectifier ensures nearly sinusoidal power consumption. The advantages of this technology are obvious: due to the improved power factor at the input of the rectifier, this UPS system consumes up to 30% less input power than standard UPS systems with a the thyristor rectifier. The reduced power at the input of the rectifier in the network supply allows for significant savings in the dimensioning of the distribution, fuses and cable. The excellent power factor of this series and the low proportion of harmonic oscillations ensure lasting protection against an overloading of the onsite supply systems, such as power generators, fuses and switches. JOVYSTAR HP series systems are very well suited for operation in emergency power in conjunction with power generators. JOVYSTAR hp systems are very easy to maintain: All major components can be easily reached from the front side. The operating panel allows all functions to be easily operated and the program control menu easily directs the user to all display and operational functions of the system. An clear text display shows all measurements, alarms and status reports.

 Open the catalog to page 1
JOVYSTAR hp-2

Product Range www.jovyatlas.de www.jovyatlas.de www.jovyatlas.de Technical Data:: Technical Data JOVYSTAR HP input voltage input frequency input power factor at UE=400 V, 100 % load input harmonic distortion THDI at 100 % load UN number of battery cells battery charging voltage ripple of DC-voltage ( battery disconnected) battery test automatic / manual / standard output voltage (IEC 62040-3, class 1) settling time harmonic distortion <1% linear load < 5% (crest-factor 3:1, 75 % of the nominal power, linear load) acceptable crest factor / output frequency overload capacity inverter overload capacity...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.