Standby UPS Overview
This document provides a selection guide for Voltronic Power's Standby UPS models, ranging from 350VA to 800VA. These UPS systems are designed for flexibility in both stand and mounting configurations and feature auto-restart capabilities during AC recovery, simulated sine wave output, and a cold start function.
Specifications- Models: AKA 350, AKA 400, AKA 550, AKA 600, AKA 750, AKA 800
- Capacity: Ranges from 350VA/210W to 800VA/480W
- Input Voltage: 110/120 VAC or 220/230/240 VAC
- Acceptable Voltage Range: 90 - 145 VAC or 180 - 270 VAC
- Frequency Range: 60 Hz / 50 Hz (Auto sensing)
- Output Voltage: 110/120 VAC or 220/230/240 VAC
- AC Voltage Regulation (Battery Mode): ±10%
- Frequency Range (Battery Mode): 60 Hz or 50 Hz ±1 Hz
- Transfer Time: Typical 2-6 ms, Max. 10ms
- Waveform (Battery Mode): Simulated Sinewave
Battery Details- Battery Type & Number: Varies by model, ranging from 12V/4Ah to 12V/5Ah
- Typical Recharge Time: 8 hours to recover to 90% capacity
Indicators and Alarms- AC Mode: Green lighting
- Battery Mode: Yellow flashing
- Fault: Red lighting
- Battery Mode Alarm: Sounds every 10 seconds
- Low Battery Alarm: Sounds every second
- Overload Alarm: Sounds every 0.5 second
- Fault Alarm: Continuously sounding
Protection Features- Full Protection: Overload, discharge, and overcharge protection
Physical and Environmental Specifications- Dimensions (D x W x H): 305 x 158.5 x 95 mm
- Net Weight: Ranges from 2.5 kg to 2.9 kg depending on the model
- Humidity: 0-90% RH @ 0-40°C (Non-condensing)
- Noise Level: Less than 40dB
Optional Features- USB communication port
- 5V USB charger
- RJ11 and coax surge protection
- LCD version available upon request
- Bypass Surge Protection Outlets
- Easy Battery Replacement
- HID Power Device USB port
See more