ATS controller (VITAC200)
7Pages

{{requestButtons}}

Catalog excerpts

ATS controller (VITAC200) - 1

Electronic Automatic Transfer Switch Controller CONTENTS Features······················································································ 7-02 A Rating ························································································· A7-04 A Front Configuration··································································· 7-05 A Rear Configuration···································································· 7-06 A Performance········································································

Open the catalog to page 1
ATS controller (VITAC200) - 2

Electronic Automatic Transfer Switch Controller Electronic Automatic Transfer Switch Controller VITAC 200 VITAC 200 is equipment connected to the Automatic Transfer Switch (hereafter ATS), which monitors two power supplies and controls the ATS. VITAC 200 is an electronic controller that controls the Automatic Transfer Switch (ATS); it has the following characteristics. Resumes power supply to load by controlling the ATS when power fails, by always monitoring the commercial and emergency power. Reflects the power characteristics of the product installation site by setting the level of...

Open the catalog to page 2
ATS controller (VITAC200) - 3

Electronic Automatic Transfer Switch Controller Rating & Front Configuration Rating Specification Rating: AC 220[V] (input range: AC 130[V] ~ 270[V]) Type: Self-power using the power transformer Control Power Power Consumption Frequency Front Configuration and Name of Each Unit Ordinary: Under 4[W] In switchover: Under 5[W] - A-phase voltage of the commercial power - A-phase voltage of the emergency power Measurement Scope Rating Voltage Type Input contact Number of Contacts (3 EA) Type Dry Contact - Switch on state of the commercial power side - Switch on state of the emergency power side...

Open the catalog to page 3
ATS controller (VITAC200) - 4

Electronic Automatic Transfer Switch Controller Rear Configuration & Performance Rear Configuration and Name of Each Unit Measurement Range and Precision Item Display Range Commercial Power Voltage Emergency Power Voltage Commercial Power Frequency Emergency Power Frequency ※ The single-phase voltage of the commercial and emergency power can be measured. Manual Switchover Item Commercial Power Emergency Power 2 Emergency Power Commercial Power Press the emergency on button more than 1.5 seconds (activated only when emergency power is normal) Press the commercial on button more than 1.5...

Open the catalog to page 4
ATS controller (VITAC200) - 5

Electronic Automatic Transfer Switch Controller Communication Functions / Dimension / Installation 180(W)×120(H)×56.6(D) Measurement: Checks the voltage and frequency of the commercial and emergency power. Status monitoring tab: Checks the status of the commercial/emergency power and switch on/off. Settings tab: Checks and changes the current value of major parameters. Communication Functions Electronic Automatic Transfer Switch Controller ※ VITAC 200 penetrates into the panel when installed. M4×L12 bolts are used (based on 3t panel thickness).

Open the catalog to page 5
ATS controller (VITAC200) - 6

Electronic Automatic Transfer Switch Controller Connection Wiring Method Connection Wiring Method ATS - W & WP Type Connection Wiring Diagram Connection Wiring Method ATS-WN Type Connection Wiring Diagram ATS-W & WP Type CLOSE Operating Signal Status Signal Comm. Port UTIL EMG InterON ON Lock Com Operating Signal ATS-WN Type Comm. Port Micro-usb Operating Signal Status Signal Alarm Output UTIL EMG InterON ON Lock Com Operating Signal Electronic Automatic Transfer Switch Controller

Open the catalog to page 6

All VitzroEM Co. catalogs and technical brochures

  1. MCCB

    24 Pages

  2. Power Fuse

    21 Pages

  3. VIDER-M5

    11 Pages

  4. VIDER-M4

    11 Pages