Safety Cautions
  • Ensure all safety precautions are read thoroughly before using the product.
  • Distribute the user manual to end users and maintenance managers, and keep it accessible.
Overview
  • The ACB OCR supports Russian and monitors faults that can damage the protection area, controlling ACB in such events. It also supports measurement, relay, and ACB virtual performance testing.
Product Specifications
  • Wiring Type: 3P3W, 3P4W
  • Rated Control Power: AC/DC 110 ~ 220V, 60Hz
  • Power Consumption: 3W or below
  • Frequency: 50/60Hz
  • Current Rating: 80A to 6300A
  • Measurement Range: Less than 40 times the rated current
  • Measurement Accuracy: ±3%
  • Communication: RS485 and RS232
  • Operating Temperature: -20℃ to 70℃
  • Storage Temperature: -40℃ to 80℃
  • Altitude: Up to 2000m
  • Standards: EMC specification – KS C 4620, Trip Unit specification – IEEE C37.17
Functions and Configurations
  • Measurement functions include magnitude and angle of 3-phase current and neutral current.
  • Relaying functions include long time delay, short time delay, instantaneous time, and ground fault trip.
  • Event recording functions include fault history and change history records.
  • Additional functions include load factor display, programmable digital output, and PC software support.
Relay Settings
  • Basic relay elements can be set using the front rotary switch, with additional elements set via display. Fine settings and neutral protection functions are supported.
Warranty Information
  • The warranty lasts one year for the original purchaser. VITZRO is not liable for damages caused by improper use or external factors.
Revision History
  • Version 1.0 released on 2018.08.10
Specifications and Settings
  • Rated Current (Iu): Set using a rotary switch, ranging from 0.5 to 1.0 times the primary rated current of the CT (In).
  • Long Time Delay (LTD): Detects overloads with settings for operating current (Ir) and delay time (Tr), inversely proportional to the fault current.
  • Short Time Delay (STD): Prevents over-current damage with settings for operating current (Isd) and delay time (Tsd), featuring both inverse and definite time characteristics.
  • Instantaneous Protection (INST): Provides immediate response to short circuit faults with settings for working current (Ii).
  • Ground Fault Protection (GFT): Protects against ground faults with settings for working current (Ig) and delay time (Tg).
  • Pre-Trip Alarm (PTA): Offers a preliminary warning with settings for working current (Ip) and delay time (Tp).
Event and Fault Logs
  • Fault Log: Records up to 300 fault occurrences, including details like fault current and time.
  • Event Log: Tracks changes in settings, recording the modified values and times.
System Configuration
  • Rated Frequency and CT Rating: Supports 50/60Hz frequency, adjustable via the system menu.
  • Communication Settings: Configurable ID and baud rate for communication, with options for 9600, 19200, and 38400 speeds.
  • Software Version: Displays the current software version, indicating major and minor updates.
  • System Time: Allows setting of the system time for logging purposes.
  • Password Protection: Enhances security by requiring a password for system access.
  • System Wiring: Configurable for three-phase three-wire or four-wire types, affecting fault operation.
  • Language Support: Offers English and Russian language options.
  • Digital Output (DO) Settings: Programmable outputs for relay elements, allowing flexible operation.
Maintenance and Warranty
  • Warranty: Provides a two-year warranty from the purchase date, covering manufacturing defects.
  • Repair and Inspection History: Encourages documentation of repairs for future reference.
Additional Features
  • Test Set: Allows setting of test conditions for self-tests, with adjustable test times and current ratings.
  • Log Data Clearing: Options to clear fault and event logs when necessary.
See more

Catalog excerpts

ACB OCR User Manual-1

User Guide ACB OC(G)R User Guide for ACB OCR that supports Russian Safety Cautions • Please make sure to read all safety precautions thoroughly before using this product • Please provide a copy of this user manual to end users and the maintenance manager. • Please keep this manual in an easily accessible place.

 Open the catalog to page 1
ACB OCR User Manual-3

ACB OC(G)R User Guide for ACB OCR that supports Russian

 Open the catalog to page 3
ACB OCR User Manual-4

Safety Precautions for the ACB OC(G)R ◈ Safety Precautions Thank you for purchasing the VITZRO EM ACB OC(G)R. These safety precautions provide important descriptions related to safety. Before starting any types of operations with the air circuit breaker, please read these safety precautions, the user manual, and other related documentation for appropriate use. Use this switch only after reading and understanding all of the safety information and precautions of this switch. In this user manual, the safety precautions are classified into three categories based on severity: [Danger], [Warning],...

 Open the catalog to page 4
ACB OCR User Manual-5

The following is the warranty for the original Vitzro product purchaser. ■ arranty Conditions W • warranty of the Vitzro product lasts one year, during which period you can get support for the product itself. The ■ VITZRO shall not be liable for any warranty of the product damage caused by the following. If the product has been used without considering the installation information (rated power, CT, DI, DO, communication), power supply, PT/CT, and digital I/O rating that are specified in the product user guide. • If the product is damaged due to external artificial factors or the product installation...

 Open the catalog to page 5
ACB OCR User Manual-6

1. Overview 1-1. Product Overview The Russian supported ACB OCR equipment monitors fault that can damage the protection area and controls ACB in the event of any such fault. This ACB OCR can support measurement, relay, and ACB Virtual performance testing, and controls ACB by being attached in front of ACB. 1-2. Product Specification The product specification is as follows 1-2-1) ating Specification R Item Wiring Type Rated Control Power Power Consumption Rating Current Measurement Range Measurement Accuracy M easuring less than 40 times of the rated current R ated current ± 3% F or continuous...

 Open the catalog to page 6
ACB OCR User Manual-7

1-2-2) unctions and Configurations F 1) Measurement functions - Magnitude and Angle of the 3-phase current and neutral current - 3-phase current Vector Diagram - Symmetrical component of the current (Current Sequence) 2) Relaying functions - Long Time Delay - Short Time Delay - Instantaneous Time - Ground Fault Trip - Pre-Trip Alarm 3) Event recording functions - Fault history records:300 - Change history records:300 4) Additional functions - Load factor display - Setting Digital Output (Programmable DO) - Setting password - Improved Self-Test - Relay element fine setting - MCR function - PC...

 Open the catalog to page 7
ACB OCR User Manual-8

Relay operation status display Graphic LCD RESET button ENTER button TEST button Cursor movement & setting value change button Back button Relay setting rotary switch Multi-functional external input port Engineering communication port If ACB is Opened as OCR detects Fault, MTD and OCR should be reset to maintain the normal state of ACB and OCR.

 Open the catalog to page 8
ACB OCR User Manual-9

6) LED The LED at the top front of ACB OCR indicates the relay operation alarm or abnormal operation alarm. Each LED is described below. - PTA LED : It is lit when the PTA function is working - LTD LED : It blinks during Long Time Delay (LTD) Pickup, and it is lit when LTD Pickup is detected. - STD/INST LED : It is lit when Short Time Delay (STD) or Instantaneous Time (INST) is detected. - GFT LED : It is lit when grounding is detected. - Alarm LED : It is lit when there is a system problem during self-diagnosis, etc. 7) unction Button F The function buttons in front of ACB OCR are used to select...

 Open the catalog to page 9
ACB OCR User Manual-10

8) Bottom Configuration The terminal block of ACB, ACB and the terminal to which ACB OCR is wired are at the bottom of ACB OCR. The configuration is as shown below. Digital Input - Unused terminal Digital Input - Unused terminal Voltage measurement - Unused terminal - Unused terminal Phase A current input - Phase A CT input terminal Phase B current input - Phase B CT input terminal Phase C current input - Phase C CT input terminal Neutral current input - Neutral CT input terminal - RS485 higher-level communication terminal

 Open the catalog to page 10
ACB OCR User Manual-11

2. Function 2-1. Menu This ACB OCR is composed of the following menus. • MEASUREMENT You can check the measurement current and phase, and vector diagram. You can also check I0, I1, and I2. • SYSTEM You can set various factors such as the rated current, rated frequency, System wiring, communication, System time, password, language, Digital Output, and self-test condition. You can also clear the log information and check the version information. • RELAY You can set the operating current of protection factors (long time delay, short time delay, instantaneous) and operation delay time in details....

 Open the catalog to page 11
ACB OCR User Manual-12

Select MAIN MENU → SYSTEM → MEASUREMENT to check. The measurement details you can check include the current, phase, vector diagram, and current sequence value. ▶ Menu navigation to open the current measurement screen ▶ Menu navigation to open the sequence measurement scree

 Open the catalog to page 12
ACB OCR User Manual-13

2-4. Relay Russian supported ACB OCR supports Long Time Delay (LTD), Short Time Delay (STD), Instantaneous (INST), Ground Fault Trip (GFT) element, as well as various additional relay elements. Basic relay elements (LTD/STD/INST/GFT) can be set using the front rotary switch. Additional elements can be set using the display. The fine setting of the basic relay elements and neutral protection function are supported. Select MENU → RELAY → FINE SET to set in details. The current setting value of each relay element can be checked by selecting MENU → RELAY → RELAY SET. ▶ Rotary Switch ※Use the ◀/▶...

 Open the catalog to page 13
ACB OCR User Manual-14

※Use the ◀/▶ key to change the settings confirmation page. ※Press the ENTER key to check the settings ※#. If the Rotary Switch is used, you will automatically switch to the SET CHECK

 Open the catalog to page 14
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.