IPS

IPS

Product catalog summary
Features
The IPS outdoor post insulator is a gray composite insulator designed for outdoor use. It features a fiberglass core that provides good mechanical characteristics, while the external surface is made of weatherproof silicone rubber. This insulator is suitable for use in highly polluted environments, classified as D Level according to IEC 60815, due to its increased creepage distance. It is primarily used as a support for outdoor Medium Voltage applications.
Standards
The insulator complies with several standards, including IEC 62231, IEC 61952, IEC 60507, and Enel GSTP001 (formerly DS 3170).
Routine Tests
The routine tests conducted on the insulator include:
  • Visual and dimension check
  • Bending stress test
  • Power frequency withstand test
  • Dry lightning impulse voltage test
  • Wet lightning impulse voltage test
  • STL (Short Time Load) test
  • Voltage withstand test with salt fog (224 kg/m3)
Technical Specifications
The insulator is available in two models with the following specifications:
  • IPS 24: Max. Operating voltage: 24 kV, Lightning impulse voltage withstand: 150 kV, Power frequency voltage withstand (wet): 70 kV, STL: 25 kN, SCL: 5 kN, Creepage distance: 700 mm
  • IPS 36: Max. Operating voltage: 36 kV, Lightning impulse voltage withstand: 170 kV, Power frequency voltage withstand (wet): 70 kV, STL: 10 kN, SCL: 2 kN, Creepage distance: 1400 mm
See more

Catalog excerpts

IPS-1

outdoor post insulator FEATURES Gray composite outdoor post insulator. It has a berglass core with good mechanical characteris cs while the external surface is made of weatherproof silicone rubber. It can be used in highly polluted environments (D Level – IEC 60815) thanks to increased creepage distance. Used as support for outdoor Medium Voltage STANDARDS IEC 62231, IEC 61952, IEC 60507, Enel GSTP001 (former DS 3170) ROUTINE TESTS • Visual and dimension check • Bending stress • Power frequency withstand and wet) • Dry ligh ng impulse voltage • STL • Voltage withstand test with salt fog (224 kg/m3 ) Light ing impulse voltage withstand Power frequency voltage withstand Creepage distance

 Open the catalog to page 1

All Veneta Isolatori catalogs and technical brochures

  1. IPA

    1  Page

  2. PSE-PSL

    1  Page

  3. TBS 250A

    1  Page

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.