VAMP 57
1 /16Pages

VAMP 57

VAMP 57
1 /16Pages

Catalog excerpts

VAMP 57-1

VAMP 57 Multipurpose feeder and motor protection relay The VAMP 57 feeder manager has been developed to cover basic protection needs for OEMs, utilities and industrial applications. Thanks to its cost-effective and flexible design, the VAMP 57 provides an excellent alternative for various protection applications. User-friendliness has always been a feature of VAMP products, and the VAMP 57 is no exception. The rapid setting and download/upload is achieved with the unique VAMPSET setting software which dramatically improves usability

 Open the catalog to page 1
VAMP 57-2

VAMP RANGE // VAMP 57 PROTECTION RELAY www.schneider-electric.com/vamp-protection 2 VAMP RANGE // VAMP 57 PROTECTION RELAY www.schneider-electric.com/vamp-protection 2 VAMP 57 at a glance- Robust hardware • User selectable Ethernet, RS485 or RS232 based communication interface • Designed for demanding industrial conditions Common technology for cost efficiency • Powerful CPU supporting IEC 61850 • Thanks to four setting groups adaptation to various protection schemes is convenient User-friendly and high functionality • Common firmware platform with other VAMP range protection devices •...

 Open the catalog to page 2
VAMP 57-4

VAMP RANGE // VAMP 57 PROTECTION RELAY User friendly HMI interface Ease of use A great deal of effort has gone into the design of the operational aspects of the new products. Unicode support allows the menu text and settings to be translated by user into various international languages including for example Russian and Chinese. The informative human machine interface shows all of the required information for the user with support of customised legend texts. The VAMP 57 protection relay concept has been extended with a number of features that make installation and testing of the relays even more...

 Open the catalog to page 4
VAMP 57-5

VAMP RANGE // VAMP 57 PROTECTION RELAY www.schneider-electric.com/vamp-protection 5 VAMP is an expert in communication with vast experience in interfacing different system integrators, SCADA, RTUs, PLCs and gateways using a large number of supported protocols. Flexible adaptation of the communication protocols together with powerful and easy to use software tools are the key to successful integration. IEC 61850 The IEC 61850 protocol can be used to read or write static data or to receive events sent spontaneously from the relay. In addition, the interface allows peer-to-peer communication between...

 Open the catalog to page 5
VAMP 57-6

VAMP RANGE // VAMP 57 PROTECTION RELAY www.schneider-electric.com/vamp-protection 6 VAMPSET is a user-friendly, free-of-charge relay management software for setting parameters and configuring VAMP relays. Via the VAMPSET software, relay parameters, configurations and recorded data can be exchanged between PC and VAMP relays. Supporting the COMTRADE format, VAMPSET also incorporates tools for analysing relay events, waveforms and trends from data recorded by the relays, e.g. during a network fault situation. Relay's setting views are organised to several folders in the VAMPSET setting tool...

 Open the catalog to page 6
VAMP 57-7

VAMP RANGE // VAMP 57 PROTECTION RELAY The VAMP 57 offers a complete set of measurement functions to replace the conventional metering functions of switchgear and controlgear installations. The measurement functions cover phase, line and residual currents, current imbalance, system frequency and harmonics from phase currents. Condition monitoring continuously monitors trip circuits, breaker wear and current transformers.

 Open the catalog to page 7
VAMP 57-8

VAMP RANGE // VAMP 57 PROTECTION RELAY

 Open the catalog to page 8
VAMP 57-9

VAMP RANGE // VAMP 57 PROTECTION RELAY Programmable stages There are now eight stages available to use with various applications. Each stage can monitor any analogue (measured or calculated) signal and issue start and trip signals. Programmable stages extend the protection functionality of the manager series to a new level. For example, if four stages of frequency are not enough, with programmable stages, the maximum of 12 can be reached. Other examples are using the stages to issue an alarm when there are a lot of harmonics (THD) or indicating reverse power condition. Programmable logic: The...

 Open the catalog to page 9
VAMP 57-10

VAMP RANGE // VAMP 57 PROTECTION RELAY Voltage scaling mode Inputs / Outputs The VAMP 57 hosts various optional modules in order to upgrade the relay functionality from basic to more advanced applications.

 Open the catalog to page 10
VAMP 57-11

VAMP RANGE // VAMP 57 PROTECTION RELAY Dimensional drawings Panel mounting VAMP 57 PANEL MOUNTING VAMP 57

 Open the catalog to page 11
VAMP 57-12

VAMP RANGE // VAMP 57 PROTECTION RELAY Phase currents & voltage input, X1 3 Earth-fault current input , X1 A Nominal Supply Voltage [V] , X2 A Power A 48 - 230 V (range: 40 - 265 V ac / dc) Conformal coating Note: For exact DI, DO and AI amount see table on page 10 Accessories Order code USB programming cable (Vampset) V57 Panel Seal Cover V57 (RS232) - Remote / Extension / IRIG-B (3xD9) V57 (RS232) - VPA 3CG Profibus adapter cable Fiber optic module (plastic - plastic) Fiber optic module (glass - glass) Profibus DP fieldbus optio

 Open the catalog to page 12
VAMP 57-13

VAMP RANGE // VAMP 57 PROTECTION RELAY Main technical data Auxiliary voltage Voltage range Measuring circuit Rated phase current IN Current measuring range Rated neutral current I0N Current measuring range Thermal withstand Voltage measuring range Continuous voltage withstand Digital inputs Digital inputs (external voltage max 265 V) Nominal operation voltage DI1 – DI16 1: 24 - 230 V ac / dc (max. 265 V ac / dc) 2: 110 - 230 V ac / dc (max. 265 V ac / dc) 3: 220 - 230 V ac / dc (max. 265 V ac / dc) Typical switching treshold 1: 12 V ac / dc 2: 75 V ac / dc 3: 155 V ac / dc Outputs Rated volta

 Open the catalog to page 13
VAMP 57-14

VAMP RANGE // VAMP 57 PROTECTION RELAY Test value 5 kV, 1.2/50 ms, 0.5 J, communication 1 kV 2 kV, 50 Hz, communication 0,5 kV Electrical safety tests Impulse voltage withstand Dielectric test Insulation resistance Protective bonding resistance Power supply burden Standard & Test class / level IEC/EN 60255-27 & EN 60255-5, Class III IEC/EN 60255-27 & EN 60255-5, Class III IEC/EN 60255-27 & EN 60255-5 IEC/EN 60255-27 IEC/EN 60255-1 Disturbance tests

 Open the catalog to page 14

All Vamp catalogs and technical brochures

  1. VAMP 321

    12  Pages

  2. vamp 265

    2  Pages

  3. VAMP 11V

    16  Pages

  4. VAMP 1 1 F

    16  Pages

  5. VAMP 50 series

    20  Pages

  6. VAMP 259

    12  Pages

  7. VAMP 125

    1  Page

  8. VAMP 11V

    16  Pages

  9. VAMP 59

    12  Pages

  10. VAMP 55

    190  Pages

  11. VAMP 120

    8  Pages

  12. VAMP 40

    24  Pages

  13. VAMP 50

    20  Pages

  14. VAMP 230

    16  Pages

  15. VAMP 210

    2  Pages

  16. VAMP 135

    8  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.