1. Catalogs
  2. UNIVERSAL FLOW MONITORS
  3. CoolPointMed with IS (3/4 - 2 inch)

CoolPointMed with IS (3/4 - 2 inch)

CoolPointMed with IS (3/4 - 2 inch)

CoolPointMed with IS (3/4 - 2 inch)

Product catalog summary
Overview: The document describes the Universal® Flow Monitors Vortex Shedding Flowmeter, specifically the CP 3/4-2 inch model, designed for measuring flow rates of water and low viscosity fluids. It features a maximum flow range of 25-200 GPM (95-750 LPM), a maximum pressure of 300 PSI (20 Bar), and a temperature range of 32-210°F (2-99°C).
Description: The flowmeter is suitable for water and water/glycol coolant applications. It has no moving parts, reducing the risk of clogging or wear. It is CSA and CE certified and offers a 4-20 mA output. Two versions are available: a three-wire version with a solid-state relay for alarms or pulse output and a two-wire version (option E14) without display or alarms, suitable for intrinsically safe operations.
Electrical Specifications: The flowmeter requires an input power of 10-30 VDC at 80 mA (standard) or 25 mA (two-wire option). It provides a 4-20 mA output for flow measurement and 100 pulses per gallon from the solid-state relay for the three-wire version, except for the 2-inch CP16 model, which provides 25 pulses per gallon.
Material Specifications: The flow bodies are made of brass or 316 stainless steel with PVDF sensors and Viton® seals. PEEK sensors are used for high-temperature applications above 150°F.
User-Configurable Options: The three-wire standard 4-20 mA units offer selectable alarm states, set points, pulse outputs, and engineering units (GPM, LPM).
Instrument Specifications: The flowmeter features a 3-digit LED display with a 0.3" digit height, a 5% deadband for alarms, ±2% accuracy of full scale, and ±0.25% repeatability. It has a turndown ratio of 10:1, extendable to 20:1 for standard temperatures. The operating pressure is 300 PSIG, with a response time of 450 ms. The enclosure is rated IP 65, Type 1, 3, 4, 12, and 13.
Installation and Configuration: The document provides detailed installation drawings and configuration instructions for both basic meters and meters with optional junction boxes. It includes pin connector pinouts and accessory cable options.
Ordering Information: Model codes are provided for selecting the appropriate flowmeter configuration based on flow maximum, pipe size, material, thread options, and special options like rotatable heads and high-temperature capabilities.
See more

Catalog excerpts

CoolPointMed with IS (3/4 - 2 inch)-1

Maximum flow ranges from Max pressure Temperature range UNIVERSAL Flow Monitors ® Vortex Shedding Flowmeter CoolPoint™ with Rotatable Enclosure option User-Configurable Options Features that are selectable on the 3 wire standard 4-20 mA units include: • Selectable alarm state (N.O. or N.C.) • Set point or pulse output • Engineering units (GPM, LPM) This flowmeter is made for water, water/glycol coolant of low viscosity fluids. There are no moving parts to clog or wear. They are certified CSA and CE. They have a 4-20 mA output. There are two versions. The three wire version (power supplied separate from the 4-20) has a solid state relay that can be configured as an alarm or as a pulse out. It has a bright LED digital display of flow rate. The two wire version (option E14) has no display, pulse out or alarm point. It can be operated in an intrinsically safe mode only when used in conjunction with an approved intrinsic safety barrier meeting required entity parameters. Instrument Specifications • Flow Visual readout: 3 digit LED, 0.3" digit height. Deadband for Alarm: 5% of full scale (maximum flow) 3 wire units only. Accuracy: ±2% of full scale (maximum flow). Repeatability: ±.25% of indicated flow. Turndown (ratio of max to minimum flow rates): 10:1 at all temperatures and 20:1 available optionally for standard temperatures. • Pressure 300 PSIG (20 Bar) operating pressure • Response time 450 ms. • General Fluid temperature limits: 35-150° F (2-66° C) standard, 150-210° F (66-99° C) optional 3 wire units only. Enclosure rating: IP 65, Type 1, 3, 4, 12 and 13 • Pipe Connections: Female NPT, BSPP & BSPT • Back pressure of 10 PSIG required Electrical Specifications • Input Power: 10 - 30 VDC @ 80 mA standard, 25 mA for the 2 wire option • Output: 4-20mA for flow • 100 pulses per gallon from the solid state relay for 3 wire (standard) option – all units except the 2 inch CP16 which is 25 pulses per gallon • Electrical Connection Pin Connector (standard) Pigtails (optional) Junction Box with terminal strip (optional) Material Specifications Flow bodies of brass or 316 Stainless Steel with PVDF sensors and Viton® seals standard. PEEK sensors used for high temp for fluids above 150° F. Viton® is a registered trademark for DuPont Performance Elastomers. CP-CNMed091412

 Open the catalog to page 1
CoolPointMed with IS (3/4 - 2 inch)-2

Select the appropriate symbols to build a model code: Special options W1=20:1 extended turndown*** E20=High temp (150-210° F)**** Available with CN units only: E14 = 2wire 4-20 mA looppowered transmitter. No alarms, display or high temp available with this option. NOTE: E14 option can be operated in an intrinsically safe mode only when used in conjunction with an approved instrinsic safety barrier meeting required entity parameters. 8140R-ASSY = Optional approved barrier * Indicates default selection. If no selection is made, this option is assumed. *** Requires grounded wiring, standard temp...

 Open the catalog to page 2
CoolPointMed with IS (3/4 - 2 inch)-3

Installation Drawing – Basic Meters A Installation Drawing – Meters with Optional Junction Box A

 Open the catalog to page 3
CoolPointMed with IS (3/4 - 2 inch)-4

ACCESSORy CablES Available for Pin Connector Meters Series Description Length in Part Meters Number CP/CN 5 pin 1 6241-1M female 3 6241-3M 10 6241-10M Barrier used for 2 wire option where Intrinsic Safety is required. Part number: 8140-ASSY CP 3 wire standard units WHITE +24 Vdc SUPPLY FLOW RELAY CONTACT BLACK BLUE To turn flow relay contact from a switch to a pulse out by externally connecting a 2K - 10K Ohm pull up resistor from power supply to one flow relay contact and connecting the other flow relay contact to supply ground. FLOW RELAY CONTACT SUPPLY GROUND configuration: • 1: + 24 VDC power...

 Open the catalog to page 4

Archived catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.