Overview: The document describes the Universal® Flow Monitors Vortex Shedding Flowmeter and Temperature Transmitter, specifically the CT 3/4-2 inch model. It is designed for measuring flow and temperature in water, water/glycol coolant, or low viscosity fluids.
Specifications:
  • Flow Range: 25-200 GPM (95-750 LPM)
  • Max Pressure: 300 PSI (20 Bar)
  • Temperature Range: 32-210°F (2-99°C)
  • Flow Rate Transmitter: 4-20 mA
  • Temperature Transmitter: 4-20 mA
  • Solid State Relay: Configurable as alarm or pulse out
  • LED Digital Display
  • CSA and CE Certified
Electrical Specifications:
  • Input Power: 10 - 30 VDC @ 80 mA
  • Output: 4-20mA for flow and temperature
  • Electrical Connection Options: Pin Connector, Pigtails, Junction Box
Material Specifications:
  • Flow Bodies: Brass or 316 Stainless Steel
  • Sensors: PVDF, with PEEK for high temperatures
  • Seals: Viton®
User-Configurable Options:
  • Selectable Alarm State (N.O. or N.C.)
  • Set Point or Pulse Output
  • Engineering Units (GPM, LPM)
  • Temperature Units (Fahrenheit or Celsius)
Instrument Specifications:
  • Flow: Visual readout with 3-digit LED, response time of 450 ms, accuracy of ±2% full scale
  • Temperature: Response time of 1.5 seconds, accuracy of ±3% of indicated temperature
  • Pressure: Operating pressure of 300 PSIG (20 Bar)
  • Enclosure Rating: IP 65, Type 1, 3, 4, 12, and 13
Installation and Ordering:
  • Pipe Connections: Female NPT, BSPP & BSPT
  • Back Pressure: 10 PSIG usually required
  • Model Codes: Various options for material, thread, and connector types
Pin Configuration:
  • 1: + 24 VDC power supply
  • 2: 4-20 mA flow signal out
  • 3: Supply ground
  • 4-5: Flow relay contacts
  • 6: 4-20 mA temp signal out
  • 7-8: Temp relay contacts
Additional Information: The document includes installation drawings and accessory cable options for pin connector meters.
See more

Catalog excerpts

CoolPoint vortex flow meter for water or corrosives Coolpoint Flow/Temperature Series-1

U N I V E R S A L Maximum ow ranges from Max pressure Temperature range ® F L O W M O N I T O R S CT 3/4-2 inch Flow and Temperature Transmitter 25-200 GPM (95-750 LPM) 300 PSI (20 Bar) 32-210°F (2-99°C) ™ CoolPoint UNIVERSAL Flow Monitors ® Vortex Shedding Flowmeter and Temperature Transmitter Flow/Temp CoolPoint™ with Rotatable Enclosure option Description User-Congurable Options This owmeter/temperature transmitter is made for water, water/glycol coolant or low viscosity uids. It has the following features: • Flow rate transmitter 4-20 mA • Temperature transmitter 4-20 mA • Solid state relay can be congured as alarm or pulse out • LED digital display • No moving parts to clog or wear • Certied CSA and CE Features that are selectable on 4-20 mA units include: • Selectable alarm state (N.O. or N.C.) • Set point or pulse output • Engineering units (GPM, LPM) • Fahrenheit or Celsius Instrument Specications • Electrical Specications • • • • Input Power: 10 - 30 VDC @ 80 mA Output: 4-20mA for ow with solid state relay congurable for set point or pulse out Output: 4-20mA for temperature Electrical Connection Pin Connector (standard) Pigtails (optional) Junction Box with terminal strip (optional) • Material Specications • Flow bodies of brass or 316 Stainless Steel with PVDF sensors and Viton® seals standard. PEEK sensors used for high temp for uids above 150° F. • • • Flow Visual readout: 3 digit LED, 0.3" digit height Response time: 450 ms. Deadband for alarm: 5% of full scale (maximum ow) Accuracy: ±2% full scale Repeatability: ±.25% of indicated Turndown (ratio of max to minimum ow rates):10:1 at all temperatures and 20:1 available optionally for standard temperatures. Temperature Response time: 1 1/2 seconds to 66% of change Deadband for alarm: ±2% full scale Accuracy: ±3% of indicated temperature Repeatability: ± .25% of indicated Output: 4 mA @32°F, 20mA @210°F linear Pressure 300 PSIG (20 Bar) operating pressure General Fluid temperature limits: 35-150° F (2-66° C) standard, 150-210° F (66-99° C) optional. Enclosure rating: IP 65, Type 1, 3, 4, 12 and 13 Pipe Connections: Female NPT, BSPP & BSPT Back pressure of 10 PSIG usually required. (See manual for elevated temperature.) Viton® is a registered trademark for DuPont Performance Elastomers.

 Open the catalog to page 1
CoolPoint vortex flow meter for water or corrosives Coolpoint Flow/Temperature Series-3

INSTALLATION DRAWING – BASIC METERS A B D E F C NPT Female Connection Size A B C D E F CT6 and CT8 4.50 2.25 4.04 4.92 3.75 4.19 [113mm] [57mm] [103mm] [125mm] [95mm] [113mm] CT12 and CT16 6.75 3.37 4.71 6.14 3.75 4.19 [171mm] [86mm] [120mm] [156mm] [95mm] [106mm] INSTALLATION DRAWING – METERS WITH OPTIONAL JUNCTION BOX A B D E F C NPT Female Connection 3.58 [91mm] .500-14 NPT Conduit Connection Size A B C D E F CT6 and CT8 4.50 2.25 6.52 4.92 3.75 7.79 [114mm] [57mm] [166mm] [125mm] [95mm] [198mm] CT12 and CT16 6.75 3.37 6.87 6.14 3.75 7.79 [171mm] [86mm] [175mm] [156mm] [95mm] [198mm] ACCESSORY...

 Open the catalog to page 3
CoolPoint vortex flow meter for water or corrosives Coolpoint Flow/Temperature Series-4

PIN CONNECTOR PINOUTS CT BROWN WHITE BLUE 1 2 PINK 7 6 8 3 4 RED 5 GRAY YELLOW GREEN 4-20 mA FLOW SIGNAL OUT +24 Vdc SUPPLY TEMP RELAY CONTACT 4-20 mA TEMP SIGNAL OUT TEMP RELAY CONTACT FLOW RELAY CONTACT FLOW RELAY CONTACT SUPPLY GROUND PIN CONFIGURATION: • 1: + 24 VDC power supply • 2: 4-20 mA ow signal out • 3: supply ground • 4: ow relay contact • 5: ow relay contact • 6: 4-20 mA temp signal out • 7: temp relay contact • 8: temp relay contact CT WITH W1 OPTION (GROUNDED) BROWN WHITE BLUE 1 2 6 8 3 4 PINK 7 RED 5 GRAY YELLOW GREEN 4-20 mA FLOW SIGNAL OUT +24 Vdc SUPPLY TEMP RELAY CONTACT 4-20...