The document provides technical specifications for the Unitronics Uni-COM™ UAC-01EC2 Module, which supports EtherCAT and allows UniStream™ controllers to function as EtherCAT masters. It is compatible with the UniStream™ PLC (USC-B5/B10) family.
Communication Specifications
  • EtherCAT: 1 port, 100 Base-TX (RJ45), 500VAC isolation for 1 minute, supports shielded CAT5e cable up to 100m.
  • Data Exchange: CoE based, supports line, daisy chain, and star topologies with a maximum 100m transmission distance between nodes.
  • Capabilities: Supports up to 8 Unitronics SERVO drives, EtherCAT terminal system modular I/O, CoE protocol, PDO and SDO messages, 1 ms scan time.
USB Host
  • Intended for firmware updates only, 1 Type A port, USB 2.0 (480Mbps), no isolation, overcurrent protection included.
IO/COM Bus
  • Bus current consumption: 650 mA.
Indicator LEDs
  • LNK: Green indicates Ethernet connection.
  • ECAT: Green indicates EtherCAT running; various blink patterns indicate communication or runtime errors.
  • Status: Red and green indicators show power, PLC connection status, and errors.
  • Orange: Indicates firmware upgrade status.
Environmental Specifications
  • Ingress Protection: IP 20, NEMA 1.
  • Operational Temperature: -20°C to 55°C.
  • Storage Temperature: -30°C to 70°C.
  • Relative Humidity: 5% to 95% non-condensing.
  • Shock and Vibration: Compliant with IEC standards.
Physical Specifications
  • Weight: 0.14 Kg.
  • Dimensions: As shown in the document images.
Disclaimer
The document includes a disclaimer regarding the accuracy of the information and potential changes to product specifications without notice.
See more

Catalog excerpts

Uni-COM™ Modules-1

Technical Specifications This guide provides specifications for Unitronics' Uni-COM™ UAC-01EC2 Module. The UAC-01EC2 module support EtherCAT. Via this module, UniStream™ controllers can act as EtherCAT masters. The UAC-01EC2 EtherCAT master module can be used with UniStream™ PLC (USC-B5/B10) family of Programmable Logic Controllers. Installation Guides are available in the Unitronics Technical Library at www.unitronicsplc.com.

 Open the catalog to page 1
Uni-COM™ Modules-2

Technical Specifications Ethernet Connected OFF: During startup. ON: EtherCAT running, topology ok and all slaves communicating Slow Blink: EtherCAT communication failure or topology error Rapid Blink: Runtime error ON: Power on but no PLC connected Slow Blink: During OS startup Rapid Blink: PLC communication failure ON: Power and PLC connected and running Slow Blink: During boot Rapid Blink: During OS startup ON: During firmware upgrade process. Slow Blink: Firmware finished successfully Rapid Blink: During firmware upgrade failure EtherCAT Link ECAT EtherCAT Communication Status Environmental...

 Open the catalog to page 2
Uni-COM™ Modules-3

Side View Front View The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market. All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of merchantability, fitness for...

 Open the catalog to page 3

All Unitronics (1989)(R"G) LTD catalogs and technical brochures

  1. M91-2-R1

    3  Pages

  2. EtherCAT

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.