Samba™PLC+HMI™
1 /5Pages

Samba™PLC+HMI™

Samba™PLC+HMI™
1 /5Pages

Catalog excerpts

Samba™PLC+HMI™-1

Technical Specifications Item SM35-J-R20 PLC with Flat panel, Color touch display 3.5’’ SM43-J-R20 PLC with Flat panel, Color touch display 4.3’’ SM70-J-R20 PLC with Flat panel, Color touch display 7’’ Power SupplyItem SM35-J-R20 SM43-J-R20 SM70-J-R20 Input voltage Permissible range Max. current consumption npn inputs pnp inputs Notes: 20.4VDC to 28.8VDC with less than 10% ripple See Note 1 1. To calculate the actual power consumption, subtract the current for each unused element from the maximum current consumption value according to the values below: Digital Inputs Number of inputs Input type Galvanic isolation Nominal input voltage Input voltage pnp (source) Input current Input impedance Response time Input cable length Normal digital input High Speed Input 12. See Note 2 See Note 2 None 24VDC 10ms typical, when used as normal digital inputs Up to 100 meters Up to 50 meters, shielded, see Frequency table below

 Open the catalog to page 1
Samba™PLC+HMI™-2

High speed inputs Specifications below apply when wired as HSC/shaft-encoder. Frequency (max)_See Note 3 Input type Input range Input impedance Maximum input rating Galvanic isolation Conversion method Resolution (except 4-20mA) Resolution (at 4-20mA) Conversion time Precision Status indication Successive approximation 10-bit (1024 units) One configured input is updated per scan. See Note 4 0.9% Yes - if an analog input deviates above the permissible range, its value will be 1024. 4. For example, if 2 inputs are configured as analog, it takes 2 scans to update all analog values.

 Open the catalog to page 2
Samba™PLC+HMI™-3

Digital Outputs Number of outputs Output type Isolation Type of relay Output current (resistive load) Rated voltage Minimum load Life expectancy Response time Contact protection 8 relay (in 2 groups). See Note 5 SPST-NO (Form A) Tyco PCN-124D3MHZ or compatible 3A maximum per output 8A maximum total per common 250VAC / 30VDC 1mA, 5VDC 100k operations at maximum load 10ms (typical) External precautions required (see Increasing Contact Life Span in the product’s Installation Guide) 5. Outputs 0, 1,2 and 3 share a common signal. Outputs 4, 5, 6, and 7 share a common signal. Illumination backlight...

 Open the catalog to page 3
Samba™PLC+HMI™-4

Communication Ports Galvanic isolation Baud rate Input voltage Cable length USB device (SM43,SM70 only) Port type Specification Cable ±20VDC absolute maximum 15m maximum (50’) USB 2.0 complaint; full speed USB 2.0 complaint; up to 3m Port 2 (optional) See Note 6 CANbus (optional) See Note 6 6. The user may order and install one or both of the following modules: - A serial RS232/RS485 isolated/non-isolated interface module, or an Ethernet Interface module in port 2. modules documentation is available on the Unitronics website. Battery back-up Battery replacement Real-time clock functions (date...

 Open the catalog to page 4
Samba™PLC+HMI™-5

Environment Operational temperature Storage temperature Relative Humidity (RH) Operating Altitude Shock Vibration The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or temporarily withdraw any of the forgoing from the market. All information in this document is provided "as is" without warranty of any kind, either expressed or...

 Open the catalog to page 5

All Unitronics (1989)(R"G) LTD catalogs and technical brochures

  1. M91-2-R1

    3  Pages

  2. EtherCAT

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.