J6 Series
8Pages

{{requestButtons}}

Catalog excerpts

J6 Series - 1

Pressure and Vacuum switches features • Gasketed, Die Cast Aluminum Enclosure with Epoxy Coating • SPDT Switch Output • Adjustable Deadband Option • Sealed, Isolated Metal Bellows Sensors • Adjustable Pressure Ranges: 30 ”Hg Vac to 6000 psi (-1 to 414 bar) UNITED ELECTRIC CONTROLS

Open the catalog to page 1
J6 Series - 2

The J6 is a reliable, sensitive pressure switch, originally designed for instrument air applications in process plants. Its compact design and combination of set-point sensitivity and narrow or optional adjustable deadband, offers cost-saving solutions for a variety of applications. The J6 is ideally suited for a wide range of industrial processes such as alarm/shutdown and low/high service pressures. OEMs also utilize the J6 in machinery and equipment for threshold protection. • Optional ATEX or GOST intrinsic safety compliance • Designed to meet Enclosure Type 4X • SPDT switch output •...

Open the catalog to page 2
J6 Series - 3

specifications Ambient TEMPERATURE limits -40° to 160°F (-40 to 71°C); set point typically shifts less than 1% of range for a 50°F (28°C) ambient temperature change Models S126B-S164B, 126-364, 680: ± 1% of adjustable range; models 610-614: ± 1.5% of adjustable range Set point repeats after 15 G, 10 millisecond duration Set point repeats after 2.5 G, 5-500 Hz Die cast aluminum, epoxy powder coated, gasketed; captive cover screws Enclosure classification Designed to meet Enclosure Type 4X requirements Switch output One SPDT; switch may be wired “normally open” or “normally closed" Electrical...

Open the catalog to page 3
J6 Series - 4

pressure model chart Model Adjustable Set Point Range Low end of range on fall; High end of range on rise psi bar (unless noted) (unless noted) (unless noted) (unless noted) (unless noted) (unless noted) (unless noted) Over Range Pressure* Welded 316L stainless steel bellows and 1/2” NPT (female) pressure connection S126B Welded 316L stainless steel bellows and 1/4” NPT (female) pressure connection (Model 680 not recommended for rapid or high cycling pressure changes) 354 303 stainless steel piston with Buna N O-ring and 303 stainless steel 1/4” NPT (female) pressure connection (not...

Open the catalog to page 4
J6 Series - 5

Model Adjustable Set Point Range Low end of range on fall; Over Range Pressure* Proof Pressure** High end of range on rise psi bar (unless noted) (unless noted) (unless noted) (unless noted) (unless noted) (unless noted) (unless noted) Brass bellows with nickel-plated brass 1/4” NPT (female) pressure connection†; Models 126 and 134 have zinc-plated steel spring exposed to media 126 Phosphor bronze bellows with nickel-plated brass 1/4” NPT (female) pressure connection; Model 218 has 300 series stainless steel spring exposed to media 218 †Several of these models were previously offered with...

Open the catalog to page 5
J6 Series - 6

how to order Building a part number Select a Type Refer to the “Type” section below. Refer to the “Model Charts”. Refer to the “Options” section. Determine type number based on switch output, enclosure, adjustment and reference. Determine model based on adjustable range, deadband and proof pressure. Determine option number based on switch output, optional materials or other product enhancements. Fill in the type portion of your part number with the corresponding number. Fill in the model portion of your part number with the corresponding number. Fill in the option portion of your part...

Open the catalog to page 6
J6 Series - 7

dimensional drawings Dimensional drawings for all models may be found at www.ueonline.com Internal Set Point Adjustment All dimensions stated in inches (millimeters) Pressure Sensors Models 218-230

Open the catalog to page 7
J6 Series - 8

RECOMMENDED PRACTICES AND WARNINGS United Electric Controls Company recommends careful consideration of the following factors when specifying and installing UE pressure and temperature units. Before installing a unit, the Installation and Maintenance instructions provided with unit must be read and understood. • To avoid damaging unit, proof pressure and maximum temperature limits stated in literature and on nameplates must never be exceeded, even by surges in the system. Operation of the unit up to maximum pressure or temperature is acceptable on a limited basis (e.g., start-up, testing)...

Open the catalog to page 8

All United Electric Controls catalogs and technical brochures

  1. 55 Series

    8 Pages

  2. 24 Series

    8 Pages

  3. J21K Series

    8 Pages

  4. 800 series

    8 Pages

  5. 400 series

    16 Pages

  6. 117 Series

    12 Pages

  7. Sensor Box

    8 Pages

  8. 120 Series

    28 Pages

  9. 100 Series

    15 Pages

  10. 10 Series

    8 Pages

  11. One Series

    16 Pages

  12. 12 Series

    16 Pages

  13. UE Catalog

    16 Pages

  14. AST Catalog

    12 Pages

  15. PSI Catalog

    8 Pages

  16. 54 Series

    12 Pages

  17. J40 Series

    8 Pages

Archived catalogs

  1. UE Catalog

    16 Pages