120 Series

120 Series
1 / 28 PagesView full catalog

120 Series

Product catalog summary
Overview
The document provides comprehensive details on the 120 Series of explosion-proof switches, including pressure, vacuum, differential pressure, and temperature switches. These switches are designed to meet global safety standards, certified for SIL2 functional safety systems with SIL3 capability, and compliant with NACE MR0175 standards. They offer multiple outputs and easy installation features.
Specifications
The 120 Series switches operate across a wide range of temperatures and pressures. They feature a die-cast aluminum enclosure with epoxy powder coating, certified to enclosure type 4X and IP66 standards. The switches offer SPDT, DPDT, or dual SPDT outputs, with optional hermetically sealed micro-switches. Sensor materials include optional Hastelloy® and Monel® for corrosive media.
Certifications and Approvals
The switches have numerous certifications, including cULus, ATEX, IECEx, and others for countries like Russia, Ukraine, China, India, Korea, Brazil, and Taiwan. They comply with directives such as the ATEX Directive, Pressure Equipment Directive, and Low Voltage Directive.
Agency Approvals
Specific agency approvals are listed for regions including the United States, Canada, Europe, Russia, Ukraine, China, and others, ensuring compliance with local safety and performance standards.
Model Specifications
Detailed specifications for various models within the 120 Series are provided, including adjustable set point ranges, deadband, over range pressure, and proof pressure. Information on diaphragm and pressure connection materials is included, with options for different applications and environments.
Key Features
  • RoHS compliant and SIL2 certified, with SIL3 capability.
  • Easy installation and wiring with dual electrical conduit openings and accessible terminal blocks.
  • Wide variety of pressure, vacuum, differential pressure, and temperature ranges.
  • Certified for use in hazardous locations with worldwide approvals.
  • Optional features for enhanced performance in corrosive environments.
Optional Materials
Options for sensor materials include aluminum and stainless steel pressure connections, with diaphragms made from Viton®, Kapton®, Teflon®, Hastelloy®, and Monel®. These materials comply with NACE MR0175 standards for corrosive media.
Compliance and Safety
The document outlines compliance options such as flameproof and intrinsic safety certifications for various regions, including INMETRO, KOSHA, ATEX, and EAC. It also mentions SIL2 certification and NACE MR0175 compliance for specific models.
Installation and Maintenance Recommendations
Recommendations include ensuring pressure and temperature limits are not exceeded, using backup units for critical applications, and selecting adjustable ranges to prevent unsafe conditions. Proper installation is emphasized to avoid damage from shock, vibration, and moisture.
Warranty
A limited warranty covers defects in material and workmanship for 24 months from the date of manufacture, with exclusions for tampering, misuse, and unauthorized disassembly.
Additional Products
Alternative products such as the One Series Safety Transmitter and Vanguard Gas Detector are briefly mentioned, highlighting features like safety diagnostics, wireless communication, and explosion-proof designs.
Warranty Disclaimer
The seller provides a limited warranty for repair and replacement of the product. All other warranties, including implied warranties of merchantability or fitness for a particular purpose, are disclaimed.
Limitation of Liability
The seller's liability to the buyer for any loss or claim, including breach of warranty, contract, negligence, or strict liability, is limited to the repair and replacement warranty. The seller is not liable for special, indirect, consequential, or other damages, including loss of profits or production.
Specifications
Product specifications are subject to change without notice.
Contact Information
For a list of international and domestic sales offices, visit www.ueonline.com. For the latest information, visit the website.
See more

Catalog excerpts

120 Series-1

EXPLOSION-PROOF PRESSURE, VACUUM, DIFFERENTIAL PRESSURE AND TEMPERATURE SWITCHES • Meet global requirements with worldwide certifications and approvals • Certified for use in SIL2 functional safety systems. SIL3 capable • NACE MR0175 compliant models • Increase flexibility with multiple outputs • Easy installation via dual electrical conduit openings • Simplify wiring through easy-to-access terminal block • Match process requirements with an assortment of available sensors • Improve measurement accuracy with ultra-low pressure ranges RoHS compliant

 Open the catalog to page 1
120 Series-2

As safety requirements become more stringent, the determining factor in specifying an industrial pressure, differential pressure and/ or temperature switch rests upon that switch protecting equipment, processes and personnel. Meeting hazardous location requirements through worldwide approvals and certifications, UE’s 120 Series is the choice where potentially explosive or highly corrosive atmospheres exist. • Standard product approvals The 120 Series offers a variety of pressure, vacuum, differential pressure and temperature ranges, as well as process connections, wetted materials and sensor...

 Open the catalog to page 2
120 Series-3

specifications STORAGE TEMPERATURE AMBIENT TEMPERATURE LIMITS Temperature models: Type B, C and F: ±1% of full scale range Type E: ±2% of full scale range Set point repeats after 2.5 G, 5-500 Hz Die cast aluminum, epoxy powder coated; gasketed; cover lock; internal set point lock standard on types J, C, F; gasketed stainless steel tamper-resistant dial cover on types B, H, E; aluminum nameplate ENCLOSURE CLASSIFICATION Certified to enclosure type 4X. Class I, Division 1 product meets enclosure type 7; Class II, Division 1 product meets enclosure type 9. Certified to IP66 requirements SWITCH OUTPUT...

 Open the catalog to page 3
120 Series-4

120 S e ri e s agency approvals UE declarations and third-party issued certifications are available for download at www.ueonline.com/certs UNITED STATES AND CANADA Class I, Division 1 and 2, Groups B, C & D Class II, Division 1 and 2, Groups E, F & G Class III Class I, Zone 1, Group IIB + H2 T6 Tamb: -50°C to 71°C Enclosure Type 4X per UL 50 (USA), IP66 per EN 60529 (Canada) UL Listed (USA), cUL Listed (Canada) Pressure: 1203; CSA C22.2 No. 25 & 30 - File # E40857 Temperature: 1203; CSA C22.2 No. 25 & 30 - File # E43374 Canadian registration number (CRN) for Canadian provinces can be found at...

 Open the catalog to page 4
120 Series-5

agency approvals cont. INTERNATIONAL CERTIFICATION* (INCLUDES AUSTRALIA) IECEx Certified Ex d IIC T6 Gb Ex tb IIIC T85°C Db IP66 Tamb. = -40°C to +75°C IEC 60079-0, 60079-1, 60079-31 Certificate # IECEx UL 03.0001X Ex ia IIC T6 Ga IEC 60079-0, 60079-11 Certificate # IECEx UL 14.0075X * See http://www.iecex.com/countries.htm for a list of participating members. INDIA Ex d IIC T6 Gb PESO: CCEs Identification# P314108/1 EN 60079-0, 60079-1, 60079-31 Ex ia IIC T6 Ga (OPTIONAL – code M405) PESO: CCEs Identification# P305465/1 EN 60079-0, 60079-11 KOREA KOSHA, Article 34 of Industrial Safety and Health...

 Open the catalog to page 5
120 Series-6

pressure model chart • Type J120, single switch with internal adjustment, dual conduits Adjustable Set Point Range Low end of range on fall; High end of range on rise “wc mbar Over Range Pressure* Proof Pressure** Buna N diaphragm and O-Ring with epoxy coated aluminum, 1/2” NPT (female) pressure connection, large 0.72" orifice for clean-out purposes (other wetted materials available see pg. 18) 520 521 522 523 524 525 Welded 316L stainless steel diaphragm and 1/2” NPT (female) pressure connection, large 0.72" orifice for clean-out purposes 530 531 532 533 534 535 mbar (unless noted) 1.5” sanitary...

 Open the catalog to page 6
120 Series-7

pressure model chart • Type J120, single switch with internal adjustment, dual conduits (cont.) Adjustable Set Point Range Over Range Pressure* Proof Pressure** Low end of range on fall; High end of range on rise psi bar psi bar (unless noted) (unless noted) (unless noted) (unless noted) 316L stainless steel diaphragm (optional Hastelloy® C 276 or Monel® 400); Viton® GLT O-Ring (optional Kalrez®, Ethylene Propylene or Aflas®); 316 stainless steel 1/2” NPT (female) pressure connection (optional Hastelloy® C 276 or Monel® 400), 0.72” orifice for clean-out purposes. Models 188 and 189 have a 316L...

 Open the catalog to page 7
120 Series-8

pressure model chart • Type J120, single switch with internal adjustment, dual conduits (cont.) Model Adjustable Set Point Range Low end of range on fall; Lower 75% range span High end of range on rise Over Range Pressure* Proof Pressure** Welded 316 stainless steel diaphragm and 1/2” NPT (female) pressure connection, large 0.72” orifice for clean-out purposes. NACE MR0175 compliant with M401 option (except model 194) 190 191 192 193 194 Welded 316 stainless steel diaphragm and 1/2” NPT (female) pressure connection, 0.06” orifice to dampen pulsations. NACE MR0175 compliant with M401 option (except...

 Open the catalog to page 8
120 Series-9

pressure model chart • Type J120, single switch with internal adjustment, dual conduits (cont.) Model Adjustable Set Point Range Over Range Pressure* Low end of range on fall; High end of range on rise psi bar psi bar psi (unless noted) (unless noted) (unless noted) (unless noted) Proof Pressure** (unless noted) 303 stainless steel piston with Buna N O-Ring and 303 stainless steel 1/4” NPT (female) pressure connection (not recommended for gas service since drying of the O-Ring seal can allow bleeding of medium into the atmosphere) 612 616 316 stainless steel bellows and 1/4” NPT (female) pressure...

 Open the catalog to page 9
120 Series-10

pressure model chart • Type J120, single switch with internal adjustment, dual conduits with adjustable deadband micro-switch† Adjustable Set Point Range Adjustable Deadband Low end of range on fall; High end of range on rise psi bar (unless noted) (unless noted) (unless noted) Over Range Proof Pressure* Pressure** (unless noted) (unless noted) Viton® diaphragm and O-ring with 1/4" NPT (female) 316 stainless steel pressure connection 15622 Buna N diaphragm and O-Ring with nickel-plated brass 1/4" NPT (female) pressure connection 15834 15835 15836 15837 15838 15839 • H121, single switch with external...

 Open the catalog to page 10

All United Electric Controls catalogs and technical brochures

  1. 55 Series

    8  Pages

  2. J6 Series

    8  Pages

  3. 24 Series

    8  Pages

  4. J21K Series

    8  Pages

  5. 800 series

    8  Pages

  6. 400 series

    16  Pages

  7. 117 Series

    12  Pages

  8. Sensor Box

    8  Pages

  9. 100 Series

    15  Pages

  10. 10 Series

    8  Pages

  11. One Series

    16  Pages

  12. 12 Series

    16  Pages

  13. AST Catalog

    12  Pages

  14. PSI Catalog

    8  Pages

  15. 54 Series

    12  Pages

  16. J40 Series

    8  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.