1. Catalogs
  2. UniPi.technology
  3. Unipi Extension xS52
video corpo

Unipi Extension xS52

Unipi Extension xS52

Unipi Extension xS52

Product catalog summary
Product Overview
Unipi Extension xS52 is an extension module designed for communication via the RS485 serial interface using the Modbus RTU protocol. It is an economical solution for expanding projects with additional inputs and outputs, featuring a combination of analog inputs and digital/relay I/Os, suitable for complex projects involving analog component measurement.
Inputs & Outputs
  • 1 RS485 Modbus RTU
  • 4 digital/counter inputs
  • 5 relay outputs
  • 8 RTD analog inputs
Special Features
  • Direct Switch: Automatic response to input value changes
  • MasterWatchdog: Switches outputs to a safe mode if PLC communication is interrupted
  • Configurable user LEDs
  • Durable aluminum chassis (IP20)
  • Available in OEM variant
Analog Input Configuration
  • Resistance: 2 kΩ, Measuring range: 75–2000 Ω, Connection: Two-wire
  • Measuring current: < 0.3 mA, Resolution: 24 bits, Accuracy: ±0.3% of range
  • Compatible sensors: Pt100/Pt1000, Ni100/Ni1000/2k reostat
  • Resistance: 20 kΩ, Measuring range: 1–20 kΩ, Connection: Two-wire
  • Measuring current: < 0.03 mA, Resolution: 24 bits, Accuracy: ±1% of value
Installation and Operating Conditions
  • Power supply: SELV 24 V⎓ (±5%), Power consumption: Typ. 3 W, Max. 12 W
  • Dimensions: 72 × 90 × 56 mm, Weight: 320 g
  • Operating temperature: 0 ... +55 °C, Storage temperature: -25 ... +70 °C
  • Humidity: 10 ... 95%, without aggressive substances
  • Installation: On 35mm DIN rail, Connection: Pluggable terminal blocks
Compliance and Safety
  • Directive compliance: LVD 2014/35/EU, EMC 2014/30/EU, RoHS 2015/863/EU, WEEE 2012/19/EU
  • Galvanic isolation: 1.5 kVAC between RS-485 and other circuits
  • Ingress Protection: IP 20, Overvoltage category: II, Pollution degree: 2
Measurement Considerations
  • Temperature dependence of resistance measurement should be considered, especially at lower measuring ranges.
  • Graph indicates measurement error range relative to ambient temperature for a set of 16 channels.
See more

Catalog excerpts

Unipi Extension xS52-1

Product datasheet Unipi Extension xS52 is an extension module communicating via the RS485 serial interface with Modbus RTU protocol. The module is a simple and inexpensive method of extending your project by additional inputs & outputs. The xS52 features a set of analog inputs combined with a set of digital and relay I/Os. This makes it ideal for more complex projects involving the measurement of analogue components. INPUTS & OUTPUTS OTHER FEATURES ■ Special functions o Direct Switch - automatic response to input value change o MasterWatchdog - switches outputs to a safe mode if communication with the PLC is interrupted o Configurable user LEDs ■ Durable aluminium chassis (IP20)

 Open the catalog to page 1
Unipi Extension xS52-2

Digital inputs Input terminal_ Common ground LED indication Galvanic isolation (pulse) Measuring range Please note: The compensation of the lead resistance and the conversion to temperature according to the selected sensor is up to the user application. Measuring range Relay outputs Installation and operating conditions No. of inputs x group Output terminal Common terminal Load protection Short circuit pro' Overvoltage protection LED indication_ Galvanic isolation (pulse) 2.5 kVAC between RO and RO 4 kVAC between RO and all other circuits Operating conditions Power supply Rated voltage - SELV...

 Open the catalog to page 2
Unipi Extension xS52-3

Unipi Extension xS52 Temperature dependence of resistance measurement When measuring resistance, it is necessary to include the temperaturedependent measurement error of the device, especially at the lower limit of the measuring range. Directive compliance LVD: EMC: RoHS: WEEE: The graph represents the dependence of the measured value error range compared to the measured value at 20 °C for a set of 16 channels with 3 sigma coverage (99.7 % in-band measurement), various production batches.  Measurement mode: 2 kΩ  Measured resistance: 330 Ω Ambient temperature [°C] Measurement tolerance for...