ELECTRICAL CIRCULAR DUCT HEATERS

ELECTRICAL CIRCULAR DUCT HEATERS
1 / 16 PagesView full catalog

ELECTRICAL CIRCULAR DUCT HEATERS

Product catalog summary
Overview
Electrical circular duct heaters EKA are designed for heating fresh air in ventilation systems. Constructed with Aluzinc coated steel and stainless steel heating elements, they include protection thermostats and screw terminals for easy connection. These heaters are intended for indoor installation and clean air heating only, with specific installation orientations and environmental conditions.
Safety Requirements
Improper use can lead to serious injury due to fire, explosion, burns, or electrical shock. The heater should only be used with the specified electrical voltage and frequency. It is crucial to ensure the heater is unplugged before servicing to avoid high voltage contact.
Transporting and Storing
Heaters must be stored in dry conditions with humidity not exceeding 70% and temperatures between 5-40°C. They should not be stored for more than one year to prevent damage.
Installation and Electrical Connection
Installation must be performed by a competent electrician, adhering to local standards and regulations. The heater must be earthed, and an automatic circuit breaker should be installed. The power supply cable should match the heater's power requirements.
Technical Data
The document provides detailed specifications for various EKA models, including dimensions, power supply requirements, and heating capacities. The heaters operate with a minimum airflow and have specific power and voltage configurations.
Overheating Protection
Each heater is equipped with two thermostats for overheating protection. The first thermostat automatically resets at 50°C, while the second requires manual reset at 100°C. Additional thermostats are included in models with ESKM controllers.
Operation Descriptions
Different models (EKA NV, NI, NIS, ESKM) offer various control methods, including integrated potentiometers, external wired controls, and remote signals. The heaters operate using a PID regulator for precise temperature control.
Quality and Disposal
All heaters are tested before shipment to ensure quality. Disposal of the heaters should be conducted according to local environmental regulations to prevent harm.
Compliance
The heaters comply with several international standards, ensuring they meet essential safety and environmental requirements.
Specifications
Heaters are designed with integrated temperature control, PTC (air velocity), PS (air pressure), and temperature sensors. Setpoint temperature ranges vary by model, with options from 0°C to 50°C. Heaters can be controlled via potentiometer or wired remote control panel, depending on the model.
Operating Procedures
Upon power supply activation, the controller enters a 30-second preparation mode. Heating is initiated based on air velocity and pressure detection, indicated by LED signals. Different models operate with varying control modes, including supply air temperature sensor and room air temperature sensor integration.
Installation Recommendations
Pre-heater casing and air duct should be insulated with rock wool (10cm, R~2.4m²K/W). Pressure hose placement depends on the heater's position relative to the motor.
Troubleshooting
Common issues include no heating, full output not by setpoint, and automatic circuit breaker switching off. Solutions involve checking sensor resistances, ensuring correct pressure settings, and verifying electrical connections. Contact [email protected] for PCB or triac faults.
Warranty
A 2-year warranty is provided from the date of the manufacturer's invoice. Warranty claims require notification within 5 days of fault detection and product return at the customer's expense. The manufacturer is not liable for damages during transportation or installation.
Important Notes
Power supply must be switched off before performing any fault elimination work. Non-standard options are available; contact [email protected] for more information.
See more

Catalog excerpts

ELECTRICAL CIRCULAR DUCT HEATERS-1

ELECTRICAL CIRCULAR DUCT HEATERS Technical data Moun ng Maintenance

 Open the catalog to page 1
ELECTRICAL CIRCULAR DUCT HEATERS-2

Thank you for your purchase of this product. This manual describes how to use and install the supplied product. Be sure that you have read and understood its contents before using the heater. The electrical heater's model and serial number are located on the label of the product. WARNING! SAFETY REQUIREMENTS Improper use of this heater can result in serious bodily injury due to hazards of fire and explosion, burn and electrical shock. Use only with electrical voltage and frequency specified on model label. Do not perform any service with heater plugged in. Serious injury or death may occur if personnel...

 Open the catalog to page 2
ELECTRICAL CIRCULAR DUCT HEATERS-3

Table of contents Descrip on Installa on and electrical connec on Technical data Model marking Heaters EKA with integrated controller Descrip on of opera ng EKA NV … (PTC…PS) Descrip on of opera ng EKA NI … (PTC…PS)* Descrip on of opera ng EKA NIS … (PTC…PS)*

 Open the catalog to page 3
ELECTRICAL CIRCULAR DUCT HEATERS-4

Descrip on Electrical duct heaters EKA are designed to heat fresh air in ven la on systems. Casing (EKA protec on class IP 44, except EKA Type NV which protec on class IP 30) is made from Aluzinc coated steel which is high temperature proof and with rubber seals for duct connec on. Tube of hea ng element is made from stainless steel AISI 304. There are 2 protec on thermostats and screw terminals for easy connec on installed in the heaters. Heaters can be installed horizontally with the electrical connec on box facing upwards or sideways and ver cally (only if the air flow direc on upwards). Heaters...

 Open the catalog to page 4
ELECTRICAL CIRCULAR DUCT HEATERS-5

Installa on and electrical connec on Electrical duct heaters EKA can be installed horizontally in any posi on except electrical connec on box downward and ver cally (only if the air flow direc on upwards) (see Fig. 2). IMPORTANT: The installa on to the mains power supply may only be wired by a competent electrician. The power supply cable must be selected in the ra o with power of the heater. When installing these heaters, the standards and regula ons in force in your country must be followed strictly adhered to. Within the installa on an electrical isola on automa c circuit breaker (not included)...

 Open the catalog to page 5
ELECTRICAL CIRCULAR DUCT HEATERS-6

Fig. 4. Moun ng example EKA NIS/ESKM… *- External control signal (0…10VDC) is used in EKA NIS type heater. **- External PWM control signal ON/OFF: ON (6…24VDC) is used in EKA ESKM type heater. Fig. 5. Moun ng example EKA NV/NI…2NTC… *- Temperature set point knob and TR NTC10 are used in EKA NV 2NTC heater version. **- TR5K NTC10 is used in EKA NI 2NTC heater version. Fig. 6. Moun ng example EKA NV/NI… (Preheater) **- TR5K used only in EKA NI pre-heater version. *- Temperature set point knob used only in EKA NV pre-heater version.

 Open the catalog to page 6
ELECTRICAL CIRCULAR DUCT HEATERS-7

Fig. 7. Moun ng example EKA NIS/ESKM… (Preheater) *- External control signal 0…10VDC (from AHU if possible) is used in EKA NIS type pre-heater. **- External PWM control signal ON/OFF: ON 6…24VDC (from AHU if possible) is used in EKA ESKM type preheater. Type 1 – Standard EKA heater dimensions; Type 2 – EKA heater with external pressure relay dimensions; Type 3 – EKA heater with external cooling radiator dimensions; Type 4 – EKA heater with external cooling radiator and pressure relay di

 Open the catalog to page 7
ELECTRICAL CIRCULAR DUCT HEATERS-9

This declara on is in conformity with the requirements of the standards: LST EN 60335-2-30:2010+AC:2010+A11:2012+AC:2015 (EN60335-2-30:2009+ AC:2010+ A11:2012+ +AC:2014); LST EN61000-4-2:2009 (EN61000-4-2:2009); LST EN 61000-4-3:2006+A1:2008+A2:2010 (EN 61000-4-3:2006+A1:2008+A2:2010); LST EN 61000-4-4:2013 (EN 61000-4-4:2012); LST EN 61000-4-5:2014 (EN 61000-4-5:2014); LST EN 61000-4-11:2004 (EN 61000-4-11:2004); LST EN 61000-6-2:2005 (EN 61000-6-2:2005); LST EN 61000-3-2:2014 (EN 61000-3-2:2014); LST EN 61000-6-3:2007 + A1:2011 (EN 61000-6-3:2007 + A1:2011); LST EN 61000-3-3:2014 (EN 61000-3-3:2013)....

 Open the catalog to page 9
ELECTRICAL CIRCULAR DUCT HEATERS-10

without integrated control with integrated controller NV – Poten ometer for temperature control is on the lid of the heater NI – External wired remote setpoint knob (TR5K) for temperature control NIS – External wired remote (0…10) VDC signal for temperature control (analog input) ESKM – External wired remote PWM (ON/OFF: ON (6…24) VDC) signal for temperature control 1B – Duct diameter (mm) 100 – 100 mm 160 – 160 mm 125 – 125 mm 200 – 200 mm 150 – 150 mm 315 – 315 mm 2 – Hea ng power (kW) 0.3 – 0,3 kW ... 24.0 – 24,0 kW (NV, NI, NIS) >15 kW with mounted addi onal step 0.3 – 0,3 kW ... 15.0 – 15,0...

 Open the catalog to page 10
ELECTRICAL CIRCULAR DUCT HEATERS-11

Overhea ng protec on Two overheat protec on thermostats are installed in the electrical circular heater EKA. The first one with automa c reset, turns off the hea ng when the temperature reaches 50 °C and turns on when the temperature drops below 50 °C. The second with manual reset, turns off the hea ng when the temperature reaches 100 °C. In this case need to figure the cause of the overhea ng of the heater. Eliminate overhea ng cause, press „RESET“ bu on on heaters cover. Addi onal overhea ng thermostat (with automa c reset) is installed in the EKA heater with ESKM to protect the ESKM controller....

 Open the catalog to page 11
ELECTRICAL CIRCULAR DUCT HEATERS-12

Descrip on of opera ng EKA NIS … Electrical duct heaters EKA NIS … are designed for the heaters power (0…100) % control by analog signal input (0…10) VDC. When the heater power supply is switched on, LED 6 on the controller (EKR-K…) PCB (see Fig. 1 on page 4) flashes every second. If controller turns on the hea ng depending on analog signal, LED 5 lights (see Fig. 1 on page 4). Descrip on of opera ng EKA NV … (PTC…PS) Electrical duct heaters EKA NV … (PTC…PS) are designed with integrated temperature control, PTC (air velocity), PS (air pressure) and temperature sensors, setpoint poten ometer knob...

 Open the catalog to page 12
ELECTRICAL CIRCULAR DUCT HEATERS-13

Descrip on of opera ng EKA NIS … (PTC…PS) * Electrical duct heaters EKA NIS … (PTC…PS) are designed for the heaters power (0…100) % control by analog signal input (0…10) VDC, with integrated PTC (air velocity) and PS (air pressure) sensors. When the heater power supply is switched on, controller (EKR-K…) is in prepara on mode for 30 seconds, LED 1 flashes once every 5 seconds. If air velocity is detected by PTC sensor (rapid LED 1 flashes when Min. 1,5 m/s is detected) and air pressure is greater than min 20kPA a er prepara on mode ends, LED 1 will start to flash once every second and controller...

 Open the catalog to page 13