Application
The QALCOSONIC F2 is an ultrasonic flow sensor designed as a sub-assembly of a heat meter for measuring the volume of heat-conveying liquids in heating and cooling systems. It converts this measurement into an electrical pulse signal and is used with approved heating/cooling energy calculators. It is suitable for commercial energy measurement in district heating plants, factories, and residential buildings.

Special Features
- Accuracy class 2
- Nominal flow options: DN15/20/25/40/65/80/100
- Dynamic range: Qp/Qi = R 100/250
- Ambient class B
- Protection class: IP 65/67
- Nominal pressure: PN16/25 bar
- Liquid temperature range: 5°C to 130°C
- Power supply: Battery or External 24V AC/DC
- Battery lifetime: Over 12 years
- Flexible mounting positions
- No straight sections required up to DN50
- No air measurement

Technical Data
- Flow rate limits: 0.6 to 60 m³/h
- Medium temperature: +5°C to +130°C
- Protection class: IP65/67
- Ambient temperature: +5°C to +55°C
- Installation: Indoor, outdoor, in pits or installation boxes
- Nominal pressure: PN16/25 bar
- Cable lengths: 1.2m to 200m
- Battery lifetime: 12 years
- Calculator mounting: Standard DIN-rail

Approvals
- MID
- EN 14154

Power Supply
- Options include AA battery (3.6 V, 2.4 Ah) with a lifespan of at least 12 years, or external power supply (12-42 V DC or 12-36 V AC) with backup battery.

Dimensions and Mounting
- Calculator dimensions: 117 mm x 44 mm x 89.5 mm
- Flow sensor mechanical dimensions vary by DN size, with lengths ranging from 110 mm to 360 mm and weights from 0.7 kg to 15 kg.

Contact Information
- Axioma Metering UAB, Lithuania
- Email: [email protected]
- Website: axiomametering.com
See more

Catalog excerpts

QALCOSONIC F2-1

ULTRASONIC FLOW SENSOR APPLICATION Ultrasonic flow sensor QALCOSONIC F2 is designed as sub-assembly of heat meter for measuring heat-conveying liquid volume in heating/cooling systems and conversion it into electrical pulse signal. It is used in conjunction with the type approved heating/cooling energy calculator. As a component of heat energy meter the QALCOSONIC F2 flow sensor could be used for commercial account of energy quantity in district heating plants, in factories, in single or multifamily houses. • Dynamic range up to Qp/Qi = R 100/250 • Temperature of conveying liquid: 5° C ...130° C • Power supply options: Battery/External 24V AC/DC • Battery lifetime > 12 years • Mounting in any installation position • Can be mounted in both flow and return pipe. • No straight sections required up to DN50 • Pulse value is freely ordered1 Ultrasonic technology • High accuracy

 Open the catalog to page 1
QALCOSONIC F2-2

POWER SUPPLY: Power supply (one of following depending on meter configuration): • AA battery 3,6 V 2,4 Ah (Li-SOCl2) battery, operation time at least 12 years, • 12..42 V DC or 12...36 V 50/60Hz AC external power supply, used current 10 mA and back up battery AA 3,6 V (Li-SOCl2), operation time at least 12 years. TECHNICAL DATA

 Open the catalog to page 2
QALCOSONIC F2-3

DIMENSIONS AND MOUNTING OF CALCULATOR

 Open the catalog to page 3
QALCOSONIC F2-4

MECHANICAL DIMENSIONS OF FLOW SENSOR AXIOMA METERING UAB / Veterinary str. 52 / Biruliskiy k., Kauno r. LT-54469 / Lithuania / [email protected] / axiomametering.com

 Open the catalog to page 4

All UAB Axioma Metering catalogs and technical brochures

  1. QALCOSONIC E2

    6  Pages

  2. QALCOSONIC E1

    4  Pages

  3. QALCOSONIC F1

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.