Prylada Core (IoT Sensor Hub ADH-02) User Manual Version 1.0 17/05/2021 __________________________________________________________________ User Manual Version 1.0 1 prylada core (ADH-02 rev1.0) Document Number: tymiqum0000120
Open the catalog to page 1
Revision History Version Initial version Yury Tsybulka __________________________________________________________________ User Manual Version 1.0 2 prylada core (ADH-02 rev1.0) Document Number: tymiqum0000120
Open the catalog to page 2
Table of Contents 1. Overview 1.1. Cautions & Warnings 1.2. Electrostatic Discharge Caution 2. Key Features 2.1. Wireless connectivity 2.1.1. LTE 2.2. Interfaces 2.2.1. 4-channel isolated software programmable 2.2.2. 3 Digital inputs 2.2.3. Digital outputs 2.2.4. 1 bistable relay 2.2.9. 3V 300mA power output 2.3. Power supply 2.4. Dimensions 2.5. Applications 3. Connectors description 3.1. Top view 3.2. Bottom view 5. Getting starting 5.1. Powering-up ADH-02 5.2. Antennas connection 5.3. SIM card installation 5.4. Analog IOs 5.5. Digital Inputs 5.6. Digital Outputs 5.8. Relay 5.9. External...
Open the catalog to page 3
1. Overview ADH-02 is a data acquisition module with IoT gateway functionality. It can be used as a standalone data harvester as well as a proxy, linking a cloud with IoT mesh. ADH-2 has onboard a range of industrial interfaces that can be extended thanks to modular device architecture. It can be powered via dual-source prioritized power supply input that enables battery back-up functionality. The board requires external LTE and GNSS antennas connected with u.FI connectors. 1.1. Cautions & Warnings TYMIQ provides all the documentation, design resources, web application and other resources...
Open the catalog to page 4
2. Key Features 2.1. Wireless connectivity 2.1.1. LTE ● ● ● ● nRF9160 based Assisted GPS Certified LTE bands: B1, B2, B3, B4, B5, B8, B12, B13, B14, B17, B18, B19, B20, B25, B26, B28 and B66 External antennas for LTE and GPS are required connected via u.FI connectors 2.2. Interfaces 2.2.1. 4-channel isolated software programmable ● ● ● ● ● ● Analog inputs 4-20 mA, 0-10V Analog outputs 4-20 mA, 0-10V Digital input (dry contact) RTD measurement 16-bit Σ-∆ ADC and 13-bit DAC HART – compatible 1 high-side 5-34V switch 1 low-side switch Voltage rating 220V Current rating 2A...
Open the catalog to page 5
Logistics and asset tracking Sensors networks Smart energy Smart building automation Smart agriculture Predictive maintenance Factory automation Retail and monitor devices Medical devices Wearables __________________________________________________________________ User Manual Version 1.0 6 prylada core (ADH-02 rev1.0) Document N
Open the catalog to page 6
3. Connectors description 3.1. Top view __________________________________________________________________ User Manual Version 1.0 7 prylada core (ADH-02 rev1.0) Document Number: tymiqum0000120
Open the catalog to page 7
__________________________________________________________________ User Manual Version 1.0 8 prylada core (ADH-02 rev1.0) Document Number: tymiqum0000120
Open the catalog to page 8
5. Getting starting 5.1. Powering-up ADH-02 ADH-02 can be powered by connecting power source(s) to one of two or to both “EXT POWER” and “BATT POWER” connectors. Both power inputs are +-40V tolerant and have under- and overvoltage protection enabling device operation in 5-25V range. Both inputs have reverse polarity protection. The difference between “EXT POWER” and “BATT POWER” is in priority only - “EXT POWER” is of higher priority comparing to “BATT POWER”, and therefore even if battery, being connected to “BATT POWER”, provides higher voltage than power source connected to “EXT POWER”,...
Open the catalog to page 9
5.2. Antennas connection ADH-02 is designed to work with external LTE and GPS antennas. External antennas can be connected directly to u.Fl connector or via u.Fl to SMA adapter. While connecting antennas, users should follow antenna connection rules described in a datasheet provided by antenna manufacture in order not to lower device RF performance. 5.3. SIM card installation ADH-02 supports micro-SIM cards which are to be inserted as shown in the picture above. SIM card socket is of Push-Push Eject type. __________________________________________________________________ User Manual Version...
Open the catalog to page 10
5.4. Analog IOs ADH-02 contains a powerful on-the-fly reprogrammable 4-inputs-outputs subsystem. Each channel can be individually programmed to act as: ● ● ● ● ● ● 4-20 mA digital input 4-20 mA digital output 0-10V analog input 0-10V analog output Digital input RTD measurement __________________________________________________________________ User Manual Version 1.0 11 prylada core (ADH-02 rev1.0) Document Number: tymiq
Open the catalog to page 11
5.5. Digital Inputs ADH-02 is equipped with three 20V digital inputs sharing one ground pin. 5.6. Digital Outputs ADH-02 contains 1 high-side and 1 low-side low-side switches. Pictures below depicts: ● low-side switch connection - the switch commutates LOAD connection to ground. __________________________________________________________________ User Manual Version 1.0 12 prylada core (ADH-02 rev1.0) Document Number: tymiqum0000120
Open the catalog to page 12
High-side switch connection – the switch commutates LOAD to power source 5.8. Relay ADH-02 is equipped with bistable relay letting user to leave some device being powered even if ADH-02 is off __________________________________________________________________ User Manual Version 1.0 13 prylada core (ADH-02 rev1.0) Document Number: tymiqum000012
Open the catalog to page 13
5.9. External sensors power supply In case sensors, connected to ADH-02, require to be powered from ADH-02 there is 3.3V output with 300mA current limit. It gets active as soon as the isolated power domain is on. __________________________________________________________________ User Manual Version 1.0 14 prylada core (ADH-02 rev1.0) Document Number: tymiqum0000120
Open the catalog to page 14
6. Using the System 6.1 Connectors ADH-02 is equipped with miniature 2.5 pitch AVX connectors of 9276 series compliant with wires up to 1 mm diameter. Like any connector of this type, it imposes certain requirements on how the wires should be prepared, and how they should be removed. ● Wire strip length must be 4-5 mm ● Wire can be removed with use of special tool only provided by manufacturer or its equivalent provided by TYMIQ 6.2. Running ADH-02 The following steps are to be performed to make ADH-02 running: 1. Mount ADH-02 in housing if necessary 2. Attach power supply according to the...
Open the catalog to page 15All TYMIQ GmbH catalogs and technical brochures
-