1. Catalogs
  2. TSI
  3. AirAssure Indoor Air Quality Monitor - Spec Sheet

AirAssure Indoor Air Quality Monitor - Spec Sheet

AirAssure Indoor Air Quality Monitor - Spec Sheet

AirAssure Indoor Air Quality Monitor - Spec Sheet

Product catalog summary
Overview
The AirAssure™ Indoor Air Quality (IAQ) Monitors are IoT-enabled devices designed to maintain building health and sustainability by measuring gas and particulate pollutants along with essential IAQ parameters. These monitors can be installed in less than ten minutes and allow for real-time tracking of indoor air quality through TSI Link™ Solutions cloud-based software.
Features and Benefits
  • Quick installation within ten minutes.
  • User-friendly dashboard for real-time analysis and reporting.
  • Remote management of multiple devices.
  • Options to share data publicly or keep it private.
  • Custom alerts for exceeded levels.
Ideal Applications
  • Schools & Universities
  • Office Buildings
  • Hospitals & Medical Facilities
  • Industrial Buildings
  • Government & Civic Buildings
  • Hotels & Convention Centers
  • Retail Stores & Shopping Malls
  • Restaurants
  • Power Generation & Petrochemical Plants
  • Any indoor congregation area
Specifications
  • Carbon Monoxide (CO): Range 0-1000 ppm, Accuracy ±15% or ±15 ppb, Resolution 100 ppb.
  • Nitrogen Dioxide (NO2): Range 0-20 ppm, Accuracy ±15% or ±15 ppb, Resolution 1 ppb.
  • Sulfur Dioxide (SO2): Range 0-10 ppm, Accuracy ±15% or ±15 ppb, Resolution 1 ppb.
  • Ozone (O3): Range 0-20 ppm, Accuracy ±15% or ±15 ppb, Resolution 1 ppb.
  • Total Volatile Organic Compounds (tVOC): Range 0-1000 ppm, Resolution 1 ppb.
  • Carbon Dioxide (CO2): Range 400-10,000 ppm, Accuracy ±3% + 30 ppm, Resolution 1 ppm.
  • Formaldehyde (H2CO): Range 0-1000 ppb, Accuracy ±20% + 20 ppb, Resolution 1 ppb.
  • Particulate Matter (PM): Range 0-1000 μg/m³, Accuracy ±10 μg/m³ or ±10%, Resolution 1 μg/m³.
  • Relative Humidity (RH): Range 0-100% RH, Accuracy ±3% RH, Resolution 1% RH.
  • Temperature (T): Range 0-60 °C, Accuracy ±0.5 °C, Resolution 0.1 °C.
  • Barometric Pressure (BP): Range 7.7-37.2 in HG, Accuracy ±0.12 in Hg, Resolution 0.01 in Hg.
Power Requirements
  • 24VAC Back Panel: 24VAC, 50/60 Hz.
  • USB-C AC/DA Adapter: Input 100-240VAC, 50-60Hz, Output 5VDC.
  • Power Consumption: < 5 W.
Hardware and Parts
  • Model Numbers: 8144-2, 8144-4, 8144-6 with various sensor configurations.
  • Includes universal USB power supply, 24 VAC terminal connector, 32GB Micro-SD card, and mounting kit.
  • Replacement parts available for sensors and power supply.
Software Integration
The AirAssure™ IAQ Monitor integrates with TSI Link™ Solution for device management from remote locations. More details are available at tsi.com/tsilink.
See more

Catalog excerpts

AirAssure Indoor Air Quality Monitor - Spec Sheet-1

AIRASSURE™ INDOOR AIR QUALITY MONITOR Maintain building health and sustainability with IoT-enabled AirAssure™ Indoor Air Quality (IAQ) Monitors. Designed to install in less than ten minutes, each device measures gas and particulate pollutants along with essential IAQ parameters to help you optimize and achieve indoor air quality. Deploy one monitor or more and track real-time indoor air quality conditions in your space using TSI Link™ Solutions cloud-based software. With remote access to data and device operation controls, you'll have what is needed to make impactful decisions- anytime, anywhere. + asy to install – get up and running in less than 10 minutes E + ser-friendly dashboard for real-time analysis and reporting U + anage multiple devices remotely from the comfort of your M + Hospitals & Medical Facilities + hare data publicly, or keep it private S + overnment & Civic Buildings G + et up custom alerts when certain levels are exceeded S + otels & Convention Centers H + etail Stores & Shopping Malls R + Restaurants + ower Generation & Petrochemical Plants P + nywhere People Congregate Indoors A UNDERSTANDING, ACCELE

 Open the catalog to page 1
AirAssure Indoor Air Quality Monitor - Spec Sheet-2

SPECIFICATIONS AIRASSURE™ INDOOR AIR QUALITY MONITOR Carbon Monoxide (CO) Range 0 - 1000 ppm Accuracy ±15 ppb, ±15% of reading or whichever is greater Resolution 100 ppb Dimensions in 6.75 in x 3.5 in x 1.3 (17.1 cm x 8.9 cm x 3.3 cm) Weight 0.5lb (0.23 kg) Relative Humidity (RH) Range 0 - 100% RH Accuracy ± 3% RH ±10% of reading (100 - 1000 μg/m³) Resolution 1% RH Temperature (T) Range 0-60 °C Accuracy +/- 0.5 °C Resolution 0.1 °C Nitrogen Dioxide (NO2) Range 0 - 20 ppm Accuracy ±15 ppb, ±15% of reading or whichever is greater Resolution 1 ppb Barometric Pressure (BP) Range 7.7 - 37.2 in HG...

 Open the catalog to page 2

All TSI catalogs and technical brochures

  1. 5000 SERIES

    4  Pages

  2. DP-Calc 5825

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.