Type FK-EU
52Pages

{{requestButtons}}

Catalog excerpts

Type FK-EU - 1

Fire dampers Type FK-EU FK-EU with fusible link for 72 °C or 95 °C CE compliant according to European regulations With TROXNETCOM as an option For diverse applications Rectangular fire damper for the isolation of duct penetrations between fire compartments, for a variety of installation situations, available in many different sizes and constructions ■ Nominal sizes 200 × 200 – 1500 × 800 mm, in increments of 1 mm ■ Low differential pressure and sound power level ■ Explosion-proof construction (ATEX) as an option ■ Air transfer damper as an option ■ Optional stainless steel casing or powder-coated casing for increased corrosion protection ■ Integration into the central BMS with TROXNETCOM ATEX certification Optional equipment and accessories ■ Electric actuator 24 V/230 V ET ■ Universal installation options ■ Release temperature 72/95 °C ■ Duct smoke detector RM-O-3-D

Open the catalog to page 1
Type FK-EU - 2

Fire dampers Type Page Installation kit - installation in solid walls 1.1 - 16 Installation kit - installation with flexible ceiling joint 1.1 - 18 Installation kit - for installation on the face of solid walls 1.1 - 19 Installation kit - for installation adjacent to solid walls 1.1 - 20 Installation kit - for installation remote from solid walls 1.1 - 21 Installation kit - for installation in lightweight partition 1.1 - 23 walls/fire walls Cover grille 1.1 - 25 Spring return actuator 1.1 - 34 Duct smoke detectors...

Open the catalog to page 2
Type FK-EU - 3

Fire dampers General information FK-EU with fusible link FK-EU with spring return actuator FK-EU with spring return actuator (explosion-proof) FK-EU as air transfer damper Product examples

Open the catalog to page 3
Type FK-EU - 4

Fire dampers General information Fire damper Type FK-EU For detailed information on attachments see Chapter K4 – 1.2. Application – TROX fire dampers of Type FK-EU, with CE marking and declaration of performance, for the isolation of duct penetrations between fire compartments in the event of a fire – To prevent the propagation of fire and smoke through ductwork to adjacent designated fire compartments Classification – Class of performance to EN 13501-3, up to EI 180 (ve, ho, i ↔ o) S Variants – With fusible link – With fusible link for use in potentially explosive atmospheres – With spring...

Open the catalog to page 4
Type FK-EU - 5

Fire dampers Construction features - Rectangular or square construction, rigid casing, both flanges with fixing holes - Suitable for the connection of ducts, spigots, flexible connectors or a cover grille - The release mechanism is accessible and can be tested from the outside - Two inspection access panels - Remote control with spring return actuator Materials and surfaces Casing: - Galvanised sheet steel - Galvanised sheet steel, powder-coated RAL 7001 - Stainless steel 1.4301 Damper blade: - Special insulation material - Special insulation material with coating Other components: - Damper...

Open the catalog to page 5
Type FK-EU - 6

Fire dampers General information Functional description In the event of a fire, fire dampers shut automatically to prevent the propagation of fire Construction with fusible link and smoke through ductwork to adjacent designated fire compartments. In the event of a fire, the damper is triggered at 72 °C or at 95 °C (use in warm air ventilation systems) by a fusible link. The release mechanism is accessible and can be tested from the outside. Schematic illustration of FK-EU with fusible link ① Casing ② Damper blade ③ Travel stop for OPEN position ④ Travel stop for CLOSED position ⑤ Inspection...

Open the catalog to page 6
Type FK-EU - 7

Fire dampers General information Function Construction with spring return actuator Functional description The spring return actuator enables the motorised opening and closing of the damper blade; it can be activated by the central BMS. In the event of a fire, the damper is triggered thermoelectrically at 72 °C or 95 °C (use in warm air ventilation systems). As long as power is supplied to the actuator, the damper blade remains open. If the supply voltage fails, the damper closes (power off to close). Motorised fire dampers can be used to shut off ducts. The torque of each actuator is...

Open the catalog to page 7
Type FK-EU - 8

Fire dampers Function 1 Construction with spring return actuator, explosion-proof Functional description The fire damper is used as a shut-off device to prevent fire and smoke from spreading through ducting in areas with potentially explosive atmospheres. The fire damper is suitable for supply air and extract air systems in potentially explosive atmospheres. For the operation of the fire damper, the operating and installation manual and the technical data in the additional operating manual must be observed. Use in areas with potentially explosive atmospheres (ATEX) According to declaration...

Open the catalog to page 8
Type FK-EU - 9

Fire dampers General information Function Air transfer damper Functional description Air transfer dampers are designed to shut off openings for air transfer in fire resistant internal walls and ceiling slabs. To prevent smoke from spreading in buildings, it is extremely important that the smoke is detected at an early stage. Duct smoke detector Type RM-O-3-D is required to control and trigger the air transfer damper. The smoke detector operates on the principle of light scattering and detects the smoke regardless of its temperature so that the fire dampers can be closed before the release...

Open the catalog to page 9
Type FK-EU - 10

Fire dampers FK-EU Design information – Approved only for use in ventilation and air conditioning sytems – A class of performance up to EI 120 (ve, ho, i ↔ o) S can only be achieved with ducts connected on both ends, or with a duct on one end and a cover grille on the other end. – If the fire damper is installed in a solid wall, solid ceiling slab, lightweight partition wall or shaft wall with a lower fire resistance class than that of the fire damper, the fire resistance class of the wall or ceiling slab applies also to the FK-EU (details upon request) – Ducting must be installed in such a...

Open the catalog to page 10
Type FK-EU - 11

Fire dampers Correct use on the face of, adjacent to and remote from solid walls Installation location Construction and building material Mortar-based installation Performance class On the face of solid walls Solid walls, 100 gross density ≥ 500 kg/m³ Solid walls, 100 gross density ≥ 500 kg/m³ Solid walls, 100 gross density ≥ 500 kg/m³ Adjacent to solid walls Remote from solid walls

Open the catalog to page 11

All TROX catalogs and technical brochures

  1. Type KA-EU

    21 Pages

  2. Type XSA

    21 Pages

  3. Type MSA

    21 Pages

  4. Type DLQ

    20 Pages

  5. Type DCS

    24 Pages

  6. Type FD

    22 Pages

  7. DID642

    22 Pages

  8. DID632

    25 Pages

  9. DID300B

    24 Pages

  10. DID312

    22 Pages

  11. DID614

    17 Pages

  12. Control_units

    626 Pages

  13. Type FD

    35 Pages

  14. JZ-HL

    19 Pages

  15. JZ-LL

    23 Pages

  16. JZ-HL-AL

    16 Pages

  17. JZ-AL

    15 Pages

  18. JZ-LL-AL

    16 Pages

  19. Filter Media

    16 Pages

  20. Jet nozzles

    12 Pages