4/14/EN/2 Fire dampers Type EN-FKS-K90 tested according to Euro standard DIN EN 1366-2 with General building approval Z-41.3-653 TROX GmbH Heinrich-Trox-Platz D-47504 Neukirchen-Vluyn Telephone +49 / 28 45 / 2 02-0 Telefax +49 / 28 45 / 2 02-2 65 e-mail trox@trox.de www.troxtechnik.com
Open the catalog to page 1Content • Notes • Description Content • Notes • Description_ 2 Applications • Standard sizes • Weights_ 5 Functional Description • Circuit Diagram _14 Fire dampers are designed for automatic isolation of fire compartments in ventilation and air conditioning systems (RLT-systems). They are suitable for installation in walls and ceilings made of concrete resp. masonry, in gypsum wall boards, in lightweight partitions and L90-walls. The damper installation is independent of the air flow direction. The thermal release with the fusible link can be removed from the outside for easy inspection....
Open the catalog to page 2Construction Type EN-FKS-K90 Application – see table on page 5 Fire resistance class – K90 according to DIN 4102 Release temperature 72 °C 95 °C alternatively Standard sizes Widths W = 200, 400, 600 and 800 mm Heights H = 100, 125, 160 and 200 mm Length L = 300 mm Permissible installation positions in case of installation in walls 0° – as shown 90° / 180° / 270° – see page 5 Type EN-FKS-K90 (standard construction) 30 185 B 30 30 H 30 ቨ ብ ቨ ቤ ቩ L = 300 ቢ ባ ቤ ብ ቦ ቧ ቨ ቩ ቪ ቢቪባ ቦ ቧ approx. 70 ca. 70 Casing Blade with perimeter ring seal Handle with locking device Release mechanism Fusible link...
Open the catalog to page 3with accessories Z43 resp. Z45 Fire resistance class Standard sizes Permissible installation positions in case of installation in walls Type EN-FKS-K90 with accessories Z43 resp. Z45 @ Blade with perimeter ring seal © Spring return actuator @ Thermo-electric release mechanism © Driving linkage (internal coupling) © Inspection cover (bottom resp. top inspection port) © Continous sealing strips (heat sensitive) ® Lip seal (cold seal), around the perimeter
Open the catalog to page 4Weights (approx. information in kg) with installation block For release mechanisms (starting with Z43) tabular value +5 kg. Any combination of B and H dimensions can be selected. Fire dampers may be connected only to ventilation ducting whose construction or layout - especially when heated in the event of a fire - does not exert any significant force on the fire damper or on the wall or ceiling, if necessary, flexible connectors made of barely flammable or normally flammable materials will have to be fitted between the fire damper and the ventilation ducting. 2) In conjunction with...
Open the catalog to page 5Installation Details Installation in solid walls and ceilings as well as in gypsum wall boards Installation - also with vertical rotation axis of the damper blade - in masonry walls in accordance with DIN 1053 with a minimum thickness of 115 mm, in concrete walls, in aerated concrete walls and lightweight concrete walls with a minimum thickness of 100 mm, in walls made of gypsum wall boards in accordance with DIN 18163 for gross densities 0.6 kg/dm3 with a minimum thickness of 100 mm and in ceilings made of concrete and aerated concrete with a minimum thickness of 100 mm. During...
Open the catalog to page 6Installation Details Ceiling installation Figure 1.4 Ceiling installation, above in ceilings, ceiling thickness D ≥ 100 mm, wet installation Figure 1.5 Ceiling installation, above in ceilings, ceiling thickness D ≥ 100 mm, dry installation with installation block Figure 1.6 Ceiling installation, below in ceilings, ceiling thickness D ≥ 100 mm, wet installation Figure 1.7 Ceiling installation, below in ceilings, ceiling thickness D ≥ 100 mm, dry installation with installation block ቢ Angle ባ Back stop plate, galvanised sheet steel Fig. 1.4 185 D ≥ 100 Fig. 1.6 with optional back stop plate ባ...
Open the catalog to page 7Installation Details Installation in lightweight partition walls with metal supports Installation - also with vertical rotation axis of the damper blade - in lightweight partitions with metal supports in accordance with the test certificate, the building authorities Completely fill gap "s" with Group II or III mortar, DIN 1053, with concrete, with approved fire protection mortar or plaster © Installation block, galvanised sheet steel ® Back stop plate, galvanised sheet steel (wall construction according to the particulars of the manufacturer) © Stiffing profile (according to the wall...
Open the catalog to page 8Installation Details ቢ ባ ቤ ብ Angle Installation block, galvanised sheet steel Back stop plate, galvanised sheet steel Fire rated partition wall (wall construction according to the particulars of the manufacturer) ቦ Perimeter strip (according to the wall construction) ቧ Chipboard screws, L ≥ 40 mm (supplied by others) ቨ Chipboard screws, L ≥ 60 mm (supplied by others) Installation in lightweight partition walls without metal supports and L90-walls Installation – also with vertical rotation axis of the damper blade – in at least 40 mm thick fire rated partition walls made of calcium silicate...
Open the catalog to page 9Connection of Ventilation Ducts According to the general building approval, fire dampers may only be connected to ventilation ducts that are unable to exert any significant force on the fire damper or on the wall or ceiling, on account of duct construction or layout, particularly when ducts heat up in event of fire. If this is not possible, flexible connectors must be located as shown in Fig. 4.1, Ref. No. 5 for installations shown in Figs. 1.2 to 1.7. A For installation as shown in Figs. 1.2 and 1.3 (if installation in walls made of gypsum wall boards), 2.1, 2.2, 3.1 and 3.2 ventilation...
Open the catalog to page 10Connection of Ventilation Ducts Ref. No. Application Fire resistance class* – on both sides with non-combustible ventilation ducts with resp. without openings for ventilation grille made of non-combustible materials k Ö H/B 4 L1 k min. 1.5d 1,5d L1 k min. 1.5d 1,5d K90 5 H/B – on both sides with flexible connectors and non-combustible ventilation ducts S S k k k V L1 k L1 k a 11
Open the catalog to page 11All TROX catalogs and technical brochures
-
Type KA-EU
21 Pages
-
Type FK-EU
52 Pages
-
Type XSA
21 Pages
-
Type MSA
21 Pages
-
Type DLQ
20 Pages
-
Type DCS
24 Pages
-
Type FD
22 Pages
-
Swirl Diffuser VDW
2 Pages
-
Air terminal devices
4 Pages
-
DID642
22 Pages
-
DID632
25 Pages
-
DID300B
24 Pages
-
DID312
22 Pages
-
DID614
17 Pages
-
Impulse diffusers Type ISH
15 Pages
-
Control_units
626 Pages
-
Type FD
35 Pages
-
Ceiling swirl diffusers Type FD
22 Pages
-
JZ-HL
19 Pages
-
JZ-LL
23 Pages
-
JZ-HL-AL
16 Pages
-
JZ-AL
15 Pages
-
JZ-LL-AL
16 Pages
-
Displacement Flow Diffusers
32 Pages
-
Air-water systems Design manual
60 Pages
-
Volume Flow Limiter
6 Pages
-
High Efficiency Terminal Filters
12 Pages
-
High efficiency air filter
9 Pages
-
Volume Flow Controller
12 Pages
-
Smoke Detector
7 Pages
-
Filter Media
16 Pages
-
Bag Filter Inserts
5 Pages
-
Volume Flow Controller
12 Pages
-
Jet nozzles
12 Pages