The document outlines the technical specifications and features of the JZ-LL-AL multileaf dampers, which are designed for controlling volume flow and pressure in air conditioning systems. These dampers are recognized for their low-leakage shut-off capabilities.
Specifications
  • Maximum dimensions: 1200 × 1000 mm
  • Closed blade air leakage: EN 1751, class 4
  • Casing air leakage: EN 1751, class C
  • Operating temperature: 0 to 50 °C
  • Maximum static differential pressure: 2000 Pa
Construction Features
  • Constructed from extruded aluminium sections
  • Aerofoil opposed action blades
  • Closed cell side seals for enhanced hygiene
  • Encased gears for blade interconnection
  • Available in powder-coated or anodised finishes
Optional Equipment and Accessories
  • Various actuators (Open/Close, modulating, pneumatic)
  • Installation subframe for ease of installation
  • Quadrant stays and limit switches for blade position adjustment
Technical Data
Nominal sizes range from 200 × 100 mm to 1200 × 1000 mm. Sound power levels and differential pressures are provided for different configurations.
Maintenance
The dampers are maintenance-free due to their robust construction and materials, though regular cleaning is recommended to prevent contamination and corrosion.
Standards and Guidelines
The dampers comply with EN 1751 for air leakage and meet DIN 1946, part 4 requirements for closed blade air leakage.
Attachments and Actuators
Detailed order codes for various actuator types and configurations are provided, along with minimum torque requirements for actuator selection.
Dimensions and Weight
Standard sizes and configurations are detailed, including the number of blades and drive shaft positions. A table provides the weight of the dampers based on height and width dimensions.
Product Details
The dampers are available with standard or extended drive shafts, with specifications for each type. Drive shafts are available as a special accessory upon request.
Installation Details
Installation can be performed with horizontal or vertical blades, with or without an installation subframe. The installation must be torsion-free and is intended for internal spaces only. Specific instructions for wall and duct installations are provided.
Basic Information and Nomenclature
Key terms and measurements are defined, including duct width (B), duct height (H), number of flange screw holes (n), weight (M), and sound power level (LWA). The document also explains airflow velocity (v), volume flow rate (), and static differential pressure (Δpst).
See more

Catalog excerpts

JZ-LL-AL-1

Multileaf dampers Type JZ-LL-AL Opposed blades Multileaf dampers made of aluminium for extremely ​ low-leakage shut-off in air conditioning systems Rectangular multileaf dampers for volume flow and pressure control as well as for ​ extremely low-leakage shut-off of ducts and openings in walls and ceiling slabs ■■ Maximum dimensions 1200 × 1000 mm ■■ Closed blade air leakage to EN 1751, class 4 ■■ Casing air leakage to EN 1751, class C ■■ Aerofoil opposed action blades ■■ Closed cell side seals meet increased hygiene requirements Closed cell side seals ■■ Blades interconnected by gears ■■ Available in standard sizes and many intermediate sizes Optional equipment and accessories ■■ Actuators: Open/Close actuators, modulating actuators ■■ Powder-coated construction ■■ Anodised constructi

 Open the catalog to page 1
JZ-LL-AL-2

Multileaf dampers General information Type JZ-LL-AL Page General information Function Technical data Quick sizing Specification text Order code Attachments Dimensions and weight Product details Installation details Basic information and nomenclature Application – Multileaf dampers of Type JZ-LL-AL are used ​ as an acting element in the volume flow and ​ pressure control in air conditioning systems – For extremely low-leakage shut-off of ducts and​ openings in walls and ceiling slabs – Powder-coated construction with increased ​ corrosion resistance if required Special characteristics – Aerofoil...

 Open the catalog to page 2
JZ-LL-AL-3

Multileaf dampers General information Maintenance – Maintenance-free as construction and ​ materials are not subject to wear – Contamination should be removed as it may ​ JZ-LL-AL lead to corrosion and to increased closed ​ blade air leakage

 Open the catalog to page 3
JZ-LL-AL-4

Multileaf dampers JZ-LL-AL The internal gears transfer the synchronous ​ rotational movement from the drive arm to the ​ individual blades. Functional description Multileaf dampers with gears can only have ​ opposed action blades. Schematic illustration of JZ-LL-AL ① ② ① Casing ② Encased gears ③ Opposed blades ④ Side seal ⑤ Blade tip seal ⑥ Actuator ⑦ External linkage (from H = 600 mm) ⑧ Bearing plate with

 Open the catalog to page 4
JZ-LL-AL-5

Multileaf dampers The torque for closing a multileaf damper must be such that the damper can be safely opened and closed. For closure, the torque must suffice to ensure complete shut-off by the blades. Opening is initiated without aerodynamic forces. When air flows through the damper, the aerodynamic forces of the airflow create a closing force (torque) on the blades; this happens independent of the direction of the airflow. This closing force must be countered, or overcome. The blade position, or blade angle a, for which there is the largest torque depends, among other factors, on the fan characteristics....

 Open the catalog to page 5
JZ-LL-AL-6

Multileaf dampers Quick sizing Quick sizing tables provide a good overview of the sound power levels and differential pressures that can be expected. Approximate intermediate values can be interpolated. Precise intermediate values and spectral data can be calculated with our Easy Product Finder design programme. The sound power levels LWA apply to multileaf dampers with a cross-sectional area (B x H) of 1 m2. The differential pressures apply to multileaf dampers installed in ducts (installation type A). JZ-LL-AL, differential pressure and sound power level Installation type A Installation type...

 Open the catalog to page 6
JZ-LL-AL-7

Multileaf dampers Specification text This specification text describes the general ​ properties of the product. Texts for variants can be ​ generated with our Easy Product Finder design ​ programme. Rectangular multileaf dampers for volume flow ​ and pressure control as well as for low-leakage ​ shut-off of ducts and openings in walls and ceiling ​ slabs. Ready-to-operate unit which consists of the ​ casing, aerofoil blades and the blade mechanism. Flanges on both sides, suitable for duct ​ connection. The blade position is indicated externally by a ​ notch in the blade shaft extension. Closed...

 Open the catalog to page 7
JZ-LL-AL-8

Multileaf dampers Order code  Type JZ-LL-AL Low-leakage multileaf damper ​ made of aluminium, closed blade air ​ leakage to EN 1751, class 4  Nominal size [mm] B × H  Installation subframe No entry: none ER With installation subframe  Attachments Z04 Quadrant stay Z05 – Z07 Quadrant stay and limit switches Z12 – Z51 Actuators ZF01 – ZF15 Spring return actuators Z60 – Z77 Pneumatic actuators  Damper blade safety function Only for spring return actuators or ​ pneumatic actuators NO Pressure off/power off to OPEN NC Pressure off/power off to CLOSE  Surface No entry: standard construction P1...

 Open the catalog to page 8
JZ-LL-AL-9

Multileaf dampers Quadrant stays and limit switches Order code detail Quadrant stay Quadrant stay Quadrant stay Quadrant stay Open/Close actuators Order code detail Limit switch Function Damper blade position CLOSED Damper blade position OPEN Damper blade positions CLOSED nad OPEN Supply voltage Auxiliary switch Minimum torque of multileaf damper has to be considered when selecting the actuator. Open/Close actuators, fast-running Order code detail ZS21 ZS22 Open/Close actuators, spring return Order code detail Supply voltage Supply voltage on/off Supply voltage on/off Supply voltage on/off Supply...

 Open the catalog to page 9
JZ-LL-AL-10

Multileaf dampers Modulating actuators, spring return Order code detail ZF05 ZF10 ZF15 Damper blade safety ​ function – Power off to close/open Power off to close/open – Power off to close/open Power off to close/open – Power off to close/open Power off to close/open – Power off to close/open Power off to close/open Supply voltage Auxiliary switch Minimum torque, depending on nominal size of multileaf damper and the operating pressure have to be ​ considered when selecting the actuator. Single acting pneumatic actuators Order ​ Mea­ code detail ning Z72 Damper blade safety function Power off...

 Open the catalog to page 10
JZ-LL-AL-11

Multileaf dampers JZ-LL-AL, standard sizes JZ-LL-AL, standard sizes H mm Position of drive shaft JZ-LL-AL, intermediate sizes

 Open the catalog to page 11
JZ-LL-AL-12

Multileaf dampers JZ-LL-AL, intermediate sizes H mm Position of drive shaft

 Open the catalog to page 12
JZ-LL-AL-13

Multileaf dampers Product details – Drive shafts (special accessory) upon request Aluminium multileaf dampers, corner holes B + 76

 Open the catalog to page 13

All TROX catalogs and technical brochures

  1. Type KA-EU

    21  Pages

  2. Type FK-EU

    52  Pages

  3. Type XSA

    21  Pages

  4. Type MSA

    21  Pages

  5. Type DLQ

    20  Pages

  6. Type DCS

    24  Pages

  7. Type FD

    22  Pages

  8. DID642

    22  Pages

  9. DID632

    25  Pages

  10. DID300B

    24  Pages

  11. DID312

    22  Pages

  12. DID614

    17  Pages

  13. Control_units

    626  Pages

  14. Type FD

    35  Pages

  15. JZ-HL

    19  Pages

  16. JZ-LL

    23  Pages

  17. JZ-HL-AL

    16  Pages

  18. JZ-AL

    15  Pages

  19. Filter Media

    16  Pages

  20. Jet nozzles

    12  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.