JZ-HL

JZ-HL
1 / 19 PagesView full catalog

JZ-HL

Product catalog summary
General Information
Multileaf dampers of Type JZ-HL are designed for volume flow and pressure control in air conditioning systems, offering low-leakage shut-off for ducts and openings. They are available in standard and intermediate sizes, with maximum dimensions of 2000 × 1995 mm. The dampers feature aerofoil opposed action blades interconnected by external linkage, ensuring robust and low-maintenance operation.
Specifications
- Maximum dimensions: 2000 × 1995 mm
- Closed blade air leakage: EN 1751, classes 1 – 2
- Casing air leakage: EN 1751, class C
- Operating temperature: 0 – 100 °C
- Materials: Galvanised sheet steel for casing and blades, PP/PTV plastic for blade tip seals
- Optional powder-coated construction for increased corrosion resistance
Technical Data
The dampers are designed to handle a test pressure up to 2000 Pa, with different classes of air leakage depending on the size. They can operate within a temperature range of 0 to 100 °C. The torque required for closing ensures safe operation, countering aerodynamic forces.
Construction Features
- Rectangular casing with welded construction
- Flanges on both sides for duct connection
- External linkage with robust coupling rod and horizontal arms
- Blade shafts with a notch for position indication
- Compliance with ATEX guidelines for explosive atmospheres
Optional Equipment and Accessories
- Actuators: Open/Close, modulating, pneumatic, and explosion-proof actuators
- Installation subframe for easy installation
- Reinforced blades for steel or stainless steel variants
Standards and Guidelines
The dampers meet the general requirements of DIN 1946, part 4, regarding acceptable closed blade air leakage. They are maintenance-free, with construction and materials not subject to wear, although contamination should be removed to prevent corrosion.
Attachments and Order Code
The document provides detailed order codes for various configurations, including duct connection types, bearing materials, blade construction, and actuator options. The order example illustrates a configuration with brass bearings, reinforced blades, and a spring return actuator.
Specifications:
1. Actuators: The document details various types of actuators including double acting pneumatic actuators, single acting pneumatic actuators, and explosion-proof actuators. Each actuator type is specified with order codes, operating pressure, torque, and additional features like limit switches and solenoid valves.
2. Multileaf Dampers: Specifications include dimensions, weight, and construction details. Dampers are available in standard and intermediate sizes, with options for steel or stainless steel materials.
Procedures:
1. Installation: Guidelines for installing multileaf dampers are provided, emphasizing torsion-free installation and specific conditions for internal spaces. Installation can be done with or without subframes, and special instructions are given for large dimensions.
Standards and Norms:
1. Construction: Dampers with flange holes do not have corner holes, and flange holes are specified for certain casing sizes.
2. Drive Shafts: Different types of drive shafts are available, including standard, extended, and square shafts.
Recommendations:
1. Safety Functions: Actuators have safety functions such as power off to close/open and pressure off to close/open, ensuring operational safety.
2. Sound Levels: Sound power levels are provided for air-regenerated noise, based on specific measurement standards.
Key Data from Tables and Diagrams:
1. Torque and Pressure: Actuators are specified with torque values at 6 bar pressure, ranging from 30 Nm to 70 Nm.
2. Dimensions and Weight: Detailed tables provide dimensions and weight for multileaf dampers, with specific measurements for duct width and height.
Critical Information:
1. Operating Pressure: Actuators operate within a pressure range of 1.2 to 6 bar.
2. Material Options: Dampers are available in steel or stainless steel, with specific configurations for explosion-proof applications.
See more

Catalog excerpts

JZ-HL-1

Multileaf dampers Type JZ-HL For low-leakage shut-off in air conditioning systems Rectangular multileaf dampers for volume flow and pressure control as well as for ​ low-leakage shut-off of ducts and openings in walls and ceiling slabs ■■ Maximum dimensions 2000 × 1995 mm ■■ Closed blade air leakage to EN 1751, classes 1 – 2, depending on size ■■ Casing air leakage to EN 1751, class C ■■ Aerofoil opposed action blades ■■ Blades interconnected by external linkage ■■ Available in standard sizes and many intermediate sizes Optional equipment and accessories ■■ Actuators: Open/Close actuators, modulating actuators ■■ Explosion-proof construction with pneumatic actuator or spring return actuator ■■ Powder-coated construction

 Open the catalog to page 1
JZ-HL-2

Multileaf dampers General information Type JZ-HL Page General information Function Technical data Quick sizing Specification text Order code Attachments Dimensions and weight Product details Installation details Basic information and nomenclature Application – Multileaf dampers of Type JZ-HL are used as ​ an acting element in the volume flow and ​ pressure control in air conditioning systems – For low-leakage shut-off of ducts and openings ​ in walls and ceiling slabs – Powder-coated construction with increased ​ corrosion resistance if required – Steel and stainless steel variants with brass...

 Open the catalog to page 2
JZ-HL-3

Multileaf dampers General information the blade position (not for attachment ZS99) – With drive shaft as an attachment: For the ​ position of the drive shaft see 'Dimensions and ​ weight' – With actuator as an attachment: The actuator is ​ attached to the second blade from the top – Travel stop (angle section) ensures tight ​ closure of the top and bottom blades – Blade tip seals – Construction and materials comply with the EU ​ directive and guidelines for use in potentially ​ explosive atmospheres (ATEX) for variants with ​ brass or stainless steel bearings (-M, -E) Materials and surfaces –...

 Open the catalog to page 3
JZ-HL-4

Multileaf dampers Functional description Multileaf dampers with external linkage can have ​ parallel action blades or opposed action blades. An external linkage transfers the synchronous ​ rotational movement from the drive arm to the ​ individual blades. Even very large multileaf ​ dampers can be safely opened and closed with ​ this type of linkage. Opposed action blades close at different speeds ​ since the linkage includes a transverse link. This ​ facilitates the closing process and reduces the ​ closed blade air leakage. Schematic illustration of JZ-HL ① Casing ② Opposed blades ③ Blade tip...

 Open the catalog to page 4
JZ-HL-5

Multileaf dampers The torque for closing a multileaf damper must be such that the damper can be safely opened and closed. For closure, the torque must suffice to ensure complete shut-off by the blades. Opening is initiated without aerodynamic forces. When air flows through the damper, the aerodynamic forces of the airflow create a closing force (torque) on the blades; this happens independent of the direction of the airflow. This closing force must be countered, or overcome. The blade position, or blade angle a, for which there is the largest torque depends, among other factors, on the fan characteristics....

 Open the catalog to page 5
JZ-HL-6

Multileaf dampers Quick sizing Quick sizing tables provide a good overview of the ​ sound power levels and differential pressures that ​ can be expected. Approximate intermediate ​ values can be interpolated. Precise intermediate ​ values and spectral data can be calculated with ​ our Easy Product Finder design programme. The sound power levels LWA apply to multileaf ​ dampers with a cross-sectional area (B × H) of ​ 1 m². The differential pressures apply to multileaf ​ dampers installed in ducts (installation type A). JZ-LL, JZ-LL-A2, JZ-HL, differential pressure and sound power level v m/s...

 Open the catalog to page 6
JZ-HL-7

Multileaf dampers Specification text This specification text describes the general ​ properties of the product. Texts for variants can be ​ generated with our Easy Product Finder design ​ programme. Rectangular multileaf dampers for volume flow ​ and pressure control as well as for low-leakage ​ shut-off of ducts and openings in walls and ceiling ​ slabs. Ready-to-operate unit which consists of the ​ casing, aerofoil blades and the blade mechanism. Flanges on both sides, suitable for duct ​ connection. The blade position is indicated externally by a ​ notch in the blade shaft extension. Closed...

 Open the catalog to page 7
JZ-HL-8

Multileaf dampers Order code  Type JZ-HL Low-leakage multileaf damper, closed ​ blade air leakage to EN 1751, class 1 – 2  Installation subframe No entry: none ER With (only for construction G)  Duct connection No entry: corner holes on both sides G Flange holes on both sides (no corner ​ holes)  Attachments No entry: none Z04 – Z07 Quadrant stay Z12 – Z51 Actuators ZF01 – ZF15 Spring return actuators Z60 – Z77 Pneumatic actuators  Bearings No entry: plastic bearings M Brass bearings E Stainless steel bearings  Construction of blades Only for steel or stainless steel multileaf ​ dampers...

 Open the catalog to page 8
JZ-HL-9

Multileaf dampers Quadrant stays and limit switches Order code detail Z04 Z05 Z06 Z07 Open/Close actuators Order code detail Quadrant stay Quadrant stay Quadrant stay Quadrant stay Open/Close actuators, spring return Order code detail Supply voltage on/off Supply voltage on/off Supply voltage on/off Supply voltage on/off Supply voltage on/off Supply voltage on/off Supply voltage on/off Supply voltage on/off Damper blade position CLOSED Damper blade position OPEN Damper blade positions CLOSED nad OPEN Supply voltage Torque Auxiliary switch 100 – 240 V AC Supply voltage Supply voltage on/off Supply...

 Open the catalog to page 9
JZ-HL-10

Multileaf dampers Modulating actuators Order code detail Z20 Z21 Z51 Modulating actuators, spring return Order code detail ZF05 ZF10 ZF15 Supply voltage Auxiliary switch Supply voltage Auxiliary switch Double acting pneumatic actuators, including explosion-proof actuators Order ​ code ​ detail Mea­ ning Damper blade safety func­ tion Operating pres­ sure

 Open the catalog to page 10

All TROX catalogs and technical brochures

  1. Type KA-EU

    21  Pages

  2. Type FK-EU

    52  Pages

  3. Type XSA

    21  Pages

  4. Type MSA

    21  Pages

  5. Type DLQ

    20  Pages

  6. Type DCS

    24  Pages

  7. Type FD

    22  Pages

  8. DID642

    22  Pages

  9. DID632

    25  Pages

  10. DID300B

    24  Pages

  11. DID312

    22  Pages

  12. DID614

    17  Pages

  13. Control_units

    626  Pages

  14. Type FD

    35  Pages

  15. JZ-LL

    23  Pages

  16. JZ-HL-AL

    16  Pages

  17. JZ-AL

    15  Pages

  18. JZ-LL-AL

    16  Pages

  19. Filter Media

    16  Pages

  20. Jet nozzles

    12  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.