Impulse diffusers Type ISH
15Pages

{{requestButtons}}

Catalog excerpts

Impulse diffusers Type ISH - 1

Impulse diffusers Type ISH Cooling mode, horizon­ tal air discharge For industrial zones without air polluting processes Impulse diffusers with horizontal air discharge in cooling mode ■■ Nominal sizes 250, 355, 450, 560 mm ■■ Volume flow rate range 205 – 1585 l/s or 738 – 5706 m³/h ■■ Casing made of galvanised sheet steel ■■ For variable and constant volume flows ■■ Installation either free hanging or on walls or pillars ■■ Large throw distance due to high discharge momentum ■■ Discharge direction can be adjusted manually or with an actuator Heating mode, vertical ​ air discharge ■■ Chain pull for adjusting the discharge direction manually Optional equipment and accessories ■■ Exposed diffuser parts in RAL CLASSIC colours ■■ Electric and thermal actuators for adjusting the air discharge direction ■■ Bowden cable for adjusting the discharge direction manually ■■ Wall mount

Open the catalog to page 1
Impulse diffusers Type ISH - 2

Impulse diffusers General information Page General information Function Technical data Quick sizing Specification text Order code Accessories Dimensions and weight Installation details Basic information and nomenclature Application – Type ISH impulse diffusers are used primarily ​ for industrial zones without air polluting work ​ processes – Horizontal air discharge in cooling mode, ​ vertical air discharge in heating mode – Ventilation of large occupied zones due to high ​ discharge momentum – For variable and constant volume flows – For supply air to room air temperature ​ differences...

Open the catalog to page 2
Impulse diffusers Type ISH - 3

Impulse diffusers ISH Functional description Impulse diffusers discharge the air from air ​ conditioning systems with a high momentum such ​ that large throw distances are achieved. This ​ allows for the ventilation of large areas. Type ISH impulse diffusers are used primarily for ​ industrial zones without air polluting work ​ processes. They are installed above the occupied ​ zone. An adjustable air control disc allows for ​ adapting the air discharge direction to heating or ​ cooling mode. The supply air to room air ​ temperature difference may range from –8 to ​ +12 K. Cooling mode In...

Open the catalog to page 3
Impulse diffusers Type ISH - 4

Impulse diffusers

Open the catalog to page 4
Impulse diffusers Type ISH - 5

Impulse diffusers Technical data Nominal sizes Minimum volume flow rate Maximum volume flow rate, with LWA ≅ 55 dB(A) Supply air to room air temperature difference

Open the catalog to page 5
Impulse diffusers Type ISH - 6

Impulse diffusers Quick sizing tables provide a good overview of the volume flow rates and corresponding sound power levels and differential pressures. The maximum volume flow rates apply to a sound power level of approx. 55 dB (A).

Open the catalog to page 6
Impulse diffusers Type ISH - 7

Impulse diffusers Specification text This specification text describes the general ​ properties of the product. Texts for variants can be ​ generated with our Easy Product Finder design ​ programme. Impulse diffusers with a cylindrical casing, for ​ industrial zones without air polluting work ​ processes. With adjustable air control disc for air ​ patterns from horizontal (0°) to vertical (90°). ​ Large throw distances with horizontal air ​ discharge. For free hanging installation and also ​ for installation on walls or pillars. Ready-to-install component which consists of a ​ cylindrical...

Open the catalog to page 7
Impulse diffusers Type ISH - 8

Impulse diffusers HI Type ISH Impulse diffuser [2] Actuator No entry: chain pull for manual adjustment B Bowden cable for manual adjustment E6 24 V AC/DC, modulating 0 - 10 V DC T Thermal actuator [4] Fixing No entry: none W00 With wall mount K00 With chain fixing (only for variants with chain pull) WK0 With wall mount and chain fixing (only for variants with chain pull) [5] Exposed surface No entry: galvanised P0 Powder-coated RAL 9010, pure white P1 Powder-coated, specify RAL CLASSIC colour Gloss level RAL 9010 50 % RAL 9006 30 % All other RAL colours 70 % 24 V AC/DC,...

Open the catalog to page 8
Impulse diffusers Type ISH - 9

Impulse diffusers ISH Wall mount (accessory) a ① Diffuser ② Centre of diffuser ③ Wall mount, inner part ④ Wall mount, outer part ⑤ Wall bracket

Open the catalog to page 9
Impulse diffusers Type ISH - 10

Impulse diffusers Chain pull for manual adjustment Bowden cable for manual adjustment

Open the catalog to page 10
Impulse diffusers Type ISH - 11

Impulse diffusers Dimensions and weight ISH-E* Electric actuator 02/2017 - DE/en TROX ®TECHNIK

Open the catalog to page 11
Impulse diffusers Type ISH - 12

Impulse diffusers Installation details Installation and commissioning – Installation preferably at heights between ​ 3.5 m and 10 m – Freely suspended installation – Vertical duct connection – The spigot has to be screw-fixed to the duct ​ and the entire system has to be securely fixed ​ and suspended (by others) – Fixing to walls or pillars with optional wall ​ mount – Attach the chain fixing and the hand lever of ​ he t Bowden cable to the wall or pillar, if necessary ​ These are only schematic diagrams to illustrate ​ installation details. Free hanging installation above workstations –...

Open the catalog to page 12
Impulse diffusers Type ISH - 13

Impulse diffusers Installation details Free hanging installation Wall fixing ① Wall mount

Open the catalog to page 13
Impulse diffusers Type ISH - 14

Impulse diffusers Installation details Wall fixing, detail ① Screws to be fixed once the diffuser has been ​ placed

Open the catalog to page 14
Impulse diffusers Type ISH - 15

Impulse diffusers Basic information and nomenclature Hauptabmessungen B₁ [mm] Breite des Frontdurchlasses B₄ [mm] Breite eines rechteckigen Anschlussstutzens ØD [mm] Außendurchmesser des Anschlussstutzens ØD₁ [mm] Gehäusedurchmesser Definitionen LWA [dB(A)] Schallleistungspegel des Strömungsgeräusches, ​ A-bewertet ISH H₁ [mm] Höhe des Frontdurchlasses T₁ [mm] Gehäusetiefe T₄ [mm] Tiefe eines rechteckigen Anschlussstutzens m [kg] Gewicht (Masse) Nahzone mindestens 0,5 m Im Abstand Lnz beträgt die Luftgeschwindigkeit ​ maximal 0,2 m/s, gemessen 0,1 m über dem ​ Boden  [m³/h] und [l/s]...

Open the catalog to page 15

All TROX catalogs and technical brochures

  1. Type KA-EU

    21 Pages

  2. Type FK-EU

    52 Pages

  3. Type XSA

    21 Pages

  4. Type MSA

    21 Pages

  5. Type DLQ

    20 Pages

  6. Type DCS

    24 Pages

  7. Type FD

    22 Pages

  8. DID642

    22 Pages

  9. DID632

    25 Pages

  10. DID300B

    24 Pages

  11. DID312

    22 Pages

  12. DID614

    17 Pages

  13. Control_units

    626 Pages

  14. Type FD

    35 Pages

  15. JZ-HL

    19 Pages

  16. JZ-LL

    23 Pages

  17. JZ-HL-AL

    16 Pages

  18. JZ-AL

    15 Pages

  19. JZ-LL-AL

    16 Pages

  20. Filter Media

    16 Pages

  21. Jet nozzles