Induction units for suspen ded ceilings Type DID632 DID632, hinged induced air grille Active chilled beam with two-way air discharge and horizontal heat exchanger, suitable for grid ceilings with grid size 600 or 625 Active chilled beam for heating and cooling, with 2-pipe or 4-pipe heat exchanger, for integration with various ceiling systems ■■ Preferably for room heights up to 4.0 m Eurovent certification ■■ High heating and cooling capacity with a low conditioned primary air volume flow rate and low sound power level ■■ Four nozzle variants to optimise induction based on demand ■■ Hinged, removable induced air grille in four designs Optional equipment and accessories ■■ Control system ■■ Additional casing for extract air ■■ Heat exchanger powder-coated black ■■ Powder coating in many different colours, e.g. RAL CLASSIC ■■ Adjustable air control blades for air direction control ■■ With an extended border also suitab
Open the catalog to page 1Induction units for suspended ceilings General information Technical data Quick sizing Specification text Order code Installation examples Installation details Basic information and nomenclature General information Function Application – Active chilled beams of Type DID632 for the integration into various ceiling systems, preferably for room heights up to 4.0 m – Particularly suitable for grid ceilings with grid size 600 or 625 – Adjustable air control blades (optional) allow or f the manual adjustment of the air discharge direction – 2-pipe or 4-pipe heat exchangers enable good comfort...
Open the catalog to page 2Induction units for suspended ceilings General information seal – Adjustable air control blades for air direction control Useful additions – Connecting hoses – Control equipment consisting of a control panel including a controller with integral room temperature sensor; valves and valve actuators; and lockshields – X-AIRCONTROL control system Construction features – Spigot is suitable for circular ducts to EN 1506 or EN 13180 – Four suspension points for on-site installation (by others) – Four nozzle variants to optimise induction based on demand – Optional additional casing with...
Open the catalog to page 3Induction units for suspended ceilings Functional description Active chilled beams provide centrally conditioned primary air (fresh air) to the room and use heat exchangers for additional cooling and/or heating. The primary air is discharged through nozzles (in 4 sizes) into the mixing chambers; as a result of this, secondary air is induced. Secondary air (room air) is induced via the induced air grille and passes through the horizontal heat exchanger, where it is heated or cooled. Primary and secondary air mix and are then supplied to the room horizontally through the supply...
Open the catalog to page 4Induction units for suspended ceilings ① Conditioned fresh air (primary air) ② Supply air
Open the catalog to page 5Induction units for suspended ceilings Technical data Nominal length Length Height Width Primary air spigot, diameter Primary air volume flow rate Cooling capacity Heating capacity Max. operating pressure, water side Max. operating temperature
Open the catalog to page 6Induction units for suspended ceilings The quick sizing table contains operating points for defined reference units. For other operating points you may use the Easy Product Finder design software. 02/2017 - DE/en TROX ®TECHNIK
Open the catalog to page 7Induction units for suspended ceilings
Open the catalog to page 8Induction units for suspended ceilings Quick sizing 02/2017 - DE/en TROX ®TECHNIK
Open the catalog to page 9Induction units for suspended ceilings
Open the catalog to page 10Induction units for suspended ceilings Specification text This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme. Active chilled beams of Type DID632, with two- way air discharge and high thermal output, providing high thermal comfort levels. For installation flush with the ceiling, preferably in rooms with a height up to 4.0 m. The units consist of a casing with suspension points, a spigot, non-combustible nozzles, and a horizontal heat exchanger. Nozzles in four sizes to optimise...
Open the catalog to page 11Induction units for suspended ceilings Order code Type DID632 Active chilled beam Induced air grille GL Longitudinal blades GQ Transverse blades LR Perforated metal, circular holes LQ Perforated metal, square holes Heat exchanger 2 2-pipe 4 4-pipe Nozzle variant Z Small plus M Medium G Large U Extra large Arrangement of casings and connections LL (also available as supply and extract air combination) LR ML MR RL RR (also available as supply and extract air combination) Note L = left side, R = right side, M = centre Additional casing with extract air spigot No entry: none AV Front...
Open the catalog to page 12Induction units for suspended ceilings Order code Order examples DID632–LR–2–M–LL/1193×1200×593 Perforated metal, circular holes 2-pipe Medium Left side, left side 1193 × 1200 mm 593 mm Induced air grille Heat exchanger Nozzle variant Arrangement of casings and connections Total length (diffuser face) × nominal length Width of front frame DID632–GQ–2–U–RR–AV–A1/1798×1200×598/P1/RAL9006/G3/LE/VS Induced air grille Heat exchanger Nozzle variant Arrangement of casings and connections Extract air spigot Water connections Total length (diffuser face) × nominal length Width of front frame Exposed surface...
Open the catalog to page 13Induction units for suspended ceilings
Open the catalog to page 14Induction units for suspended ceilings Set of air control blades If a high cooling capacity is required in a very small space with active chilled beams, optional air control blades allow for adjusting the air discharge pattern such that the acceptable air velocity in the occupied zone is not exceeded. The airflow of each active chilled beam is spread and discharged according to the room geometry. If the use of a room changes, the air discharge pattern can be optimised by adjusting the air control blades accordingly. – It is possible to adjust several air control blades (i.e....
Open the catalog to page 1521 Pages
52 Pages
21 Pages
21 Pages
20 Pages
24 Pages
22 Pages
2 Pages
4 Pages
22 Pages
24 Pages
22 Pages
17 Pages
15 Pages
626 Pages
35 Pages
22 Pages
19 Pages
23 Pages
16 Pages
15 Pages
16 Pages
32 Pages
60 Pages
6 Pages
12 Pages
9 Pages
12 Pages
16 Pages
7 Pages
16 Pages
5 Pages
12 Pages
12 Pages