DID632
25Pages

{{requestButtons}}

Catalog excerpts

DID632 - 1

Induction units for suspen­ ded ceilings Type DID632 DID632, hinged induced ​ air grille Active chilled beam with two-way air discharge and ​ horizontal heat exchanger, suitable for grid ceilings ​ with grid size 600 or 625 Active chilled beam for heating and cooling, with 2-pipe or 4-pipe heat exchanger, for ​ integration with various ceiling systems ■■ Preferably for room heights up to 4.0 m Eurovent certification ■■ High heating and cooling capacity with a low conditioned primary air volume ​ flow rate and low sound power level ■■ Four nozzle variants to optimise induction based on demand ■■ Hinged, removable induced air grille in four designs Optional equipment and accessories ■■ Control system ■■ Additional casing for extract air ■■ Heat exchanger powder-coated black ■■ Powder coating in many different colours, e.g. RAL CLASSIC ■■ Adjustable air control blades for air direction control ■■ With an extended border also suitab

Open the catalog to page 1
DID632 - 2

Induction units for suspended ceilings General information Technical data Quick sizing Specification text Order code Installation examples Installation details Basic information and nomenclature General information Function Application – Active chilled beams of Type DID632 for the ​ integration into various ceiling systems, ​ preferably for room heights up to 4.0 m – Particularly suitable for grid ceilings with grid ​ size 600 or 625 – Adjustable air control blades (optional) allow ​or f the manual adjustment of the air discharge ​ direction – 2-pipe or 4-pipe heat exchangers enable good ​...

Open the catalog to page 2
DID632 - 3

Induction units for suspended ceilings General information seal – Adjustable air control blades for air direction ​ control Useful additions – Connecting hoses – Control equipment consisting of a control panel ​ including a controller with integral room ​ temperature sensor; valves and valve ​ actuators; and lockshields – X-AIRCONTROL control system Construction features – Spigot is suitable for circular ducts to EN 1506 ​ or EN 13180 – Four suspension points for on-site installation ​ (by others) – Four nozzle variants to optimise induction ​ based on demand – Optional additional casing...

Open the catalog to page 3
DID632 - 4

Induction units for suspended ceilings Functional description Active chilled beams provide centrally conditioned ​ primary air (fresh air) to the room and use heat ​ exchangers for additional cooling and/or heating. The primary air is discharged through nozzles (in ​ 4 sizes) into the mixing chambers; as a result of ​ this, secondary air is induced. Secondary air ​ (room air) is induced via the induced air grille and ​ passes through the horizontal heat exchanger, ​ where it is heated or cooled. Primary and secondary air mix and are then ​ supplied to the room horizontally through the ​...

Open the catalog to page 4
DID632 - 5

Induction units for suspended ceilings ① Conditioned fresh air (primary air) ② Supply air

Open the catalog to page 5
DID632 - 6

Induction units for suspended ceilings Technical data Nominal length Length Height Width Primary air spigot, diameter Primary air volume flow rate Cooling capacity Heating capacity Max. operating pressure, water side Max. operating temperature

Open the catalog to page 6
DID632 - 7

Induction units for suspended ceilings The quick sizing table contains operating points for defined reference units. For other operating points you may use the Easy Product Finder design software. 02/2017 - DE/en TROX ®TECHNIK

Open the catalog to page 7
DID632 - 8

Induction units for suspended ceilings

Open the catalog to page 8
DID632 - 9

Induction units for suspended ceilings Quick sizing 02/2017 - DE/en TROX ®TECHNIK

Open the catalog to page 9
DID632 - 10

Induction units for suspended ceilings

Open the catalog to page 10
DID632 - 11

Induction units for suspended ceilings Specification text This specification text describes the general ​ properties of the product. Texts for variants can be ​ generated with our Easy Product Finder design ​ programme. Active chilled beams of Type DID632, with two-​ way air discharge and high thermal output, ​ providing high thermal comfort levels. For installation flush with the ceiling, preferably in ​ rooms with a height up to 4.0 m. The units consist of a casing with suspension ​ points, a spigot, non-combustible nozzles, and a ​ horizontal heat exchanger. Nozzles in four sizes to...

Open the catalog to page 11
DID632 - 12

Induction units for suspended ceilings Order code  Type DID632 Active chilled beam  Induced air grille GL Longitudinal blades GQ Transverse blades LR Perforated metal, circular holes LQ Perforated metal, square holes  Heat exchanger 2 2-pipe 4 4-pipe  Nozzle variant Z Small plus M Medium G Large U Extra large  Arrangement of casings and connections LL (also available as supply and extract air ​ combination) LR ML MR RL RR (also available as supply and extract air ​ combination) Note L = left side, R = right side, M = centre  Additional casing with extract air spigot No entry: none AV...

Open the catalog to page 12
DID632 - 13

Induction units for suspended ceilings Order code Order examples DID632–LR–2–M–LL/1193×1200×593 Perforated metal, circular holes 2-pipe Medium Left side, left side 1193 × 1200 mm 593 mm Induced air grille Heat exchanger Nozzle variant Arrangement of casings and connections Total length (diffuser face) × nominal length Width of front frame DID632–GQ–2–U–RR–AV–A1/1798×1200×598/P1/RAL9006/G3/LE/VS Induced air grille Heat exchanger Nozzle variant Arrangement of casings and connections Extract air spigot Water connections Total length (diffuser face) × nominal length Width of front frame Exposed...

Open the catalog to page 13
DID632 - 14

Induction units for suspended ceilings

Open the catalog to page 14
DID632 - 15

Induction units for suspended ceilings Set of air control blades If a high cooling capacity is required in a very ​ small space with active chilled beams, optional air ​ control blades allow for adjusting the air discharge ​ pattern such that the acceptable air velocity in the ​ occupied zone is not exceeded. The airflow of ​ each active chilled beam is spread and ​ discharged according to the room geometry. If the ​ use of a room changes, the air discharge pattern ​ can be optimised by adjusting the air control ​ blades accordingly. – It is possible to adjust several air control blades ​...

Open the catalog to page 15

All TROX catalogs and technical brochures

  1. Type KA-EU

    21 Pages

  2. Type FK-EU

    52 Pages

  3. Type XSA

    21 Pages

  4. Type MSA

    21 Pages

  5. Type DLQ

    20 Pages

  6. Type DCS

    24 Pages

  7. Type FD

    22 Pages

  8. DID642

    22 Pages

  9. DID300B

    24 Pages

  10. DID312

    22 Pages

  11. DID614

    17 Pages

  12. Control_units

    626 Pages

  13. Type FD

    35 Pages

  14. JZ-HL

    19 Pages

  15. JZ-LL

    23 Pages

  16. JZ-HL-AL

    16 Pages

  17. JZ-AL

    15 Pages

  18. JZ-LL-AL

    16 Pages

  19. Filter Media

    16 Pages

  20. Jet nozzles

    12 Pages