DID300B
1 /24Pages

DID300B

DID300B
1 /24Pages

Catalog excerpts

DID300B-1

Induction units for suspen­ ded ceilings Side entry primary air spi­ got DID300B without indu­ ced air grille DID300B, water connec­ tions (2-pipe system ​ shown) Active chilled beam with two-way air discharge, ​ 300 mm nominal width, with horizontal heat exchanger Active chilled beam for heating and cooling, with 2-pipe or 4-pipe heat exchanger, for ​ integration with various ceiling systems ■■ Preferably for room heights up to 4.00 m ■■ High heating and cooling capacity with a low conditioned primary air volume ​ flow rate and low sound power level Eurovent certification ■■ High comfort levels due to low airflow velocity in the occupied zone ■■ Three nozzle variants to optimise induction based on demand ■■ Side entry or top entry primary air spigot ■■ Removable induced air grille Optional equipment and accessories ■■ Control system ■■ Additional casing for extract air ■■ Heat exchanger powder-coated black ■■ Powder coating in many different colours, e.g. RAL CLASSIC

 Open the catalog to page 1
DID300B-2

Induction units for suspended ceilings Type Page Basic information and nomenclature 300B - 23 Application - Active chilled beams of Type DID300 B for the integration into various ceiling systems, preferably for room heights up to 4.00 m - Shallow construction of only 210 mm, hence suitable for low ceiling void spaces, e.g. in refurbishment projects - 2-pipe or 4-pipe heat exchangers enable good comfort levels with a low conditioned primary air volume flow rate - Energy-efficient solution since water is used for heating and cooling Special characteristics - Side entry or top entry...

 Open the catalog to page 2
DID300B-3

Induction units for suspended ceilings General information Maintenance – No moving parts, hence low maintenance – The heat exchanger can be vacuumed with an ​ industrial vacuum cleaner if necessary DID300B – VDI 6022, Part 1, applies (Hygiene ​ requirements for ventilation and air-​ conditioning systems and units)

 Open the catalog to page 3
DID300B-4

Induction units for suspended ceilings Functional description Active chilled beams provide centrally conditioned ​ primary air (fresh air) to the room and use heat ​ exchangers for additional cooling and/or heating. The primary air is discharged through nozzles into ​ the mixing chambers; as a result of this, ​ secondary air (room air) is induced via the ​ induced air grille and passes through the ​ horizontal heat exchanger. Primary and secondary air mix and are then ​ supplied to the room horizontally through the ​ supply air slots. ⑧ ① Primary air spigot ② Casing top ③ Nozzles ④ Water connections...

 Open the catalog to page 4
DID300B-5

Induction units for suspended ceilings ① Conditioned fresh air (primary air) ② Supply air

 Open the catalog to page 5
DID300B-6

Induction units for suspended ceilings Technical data Nominal length Length Height Width Primary air spigot, diameter Primary air volume flow rate Cooling capacity Heating capacity Max. operating pressure, water side Max. operating temperature

 Open the catalog to page 6
DID300B-7

Induction units for suspended ceilings The quick sizing table contains operating points for defined reference units. For other operating points you may use the Easy Product Finder design software. 02/2017 - DE/en TROX ®TECHNIK

 Open the catalog to page 7
DID300B-8

Induction units for suspended ceilings Quick sizing

 Open the catalog to page 8
DID300B-9

Induction units for suspended ceilings Specification text This specification text describes the general ​ properties of the product. Texts for variants can be ​ generated with our Easy Product Finder design ​ programme. Active chilled beams of Type DID300B, with two-​ way air discharge, high thermal output, and of ​ shallow construction. For installation flush with the ceiling, preferably in ​ rooms with a height up to 4.00 m. The units consist of a casing with suspension ​ points, a spigot, non-combustible nozzles, and a ​ horizontal heat exchanger. Three nozzle variants to optimise induction...

 Open the catalog to page 9
DID300B-10

Induction units for suspended ceilings Order code Active chilled beam  Heat exchanger 2 2-pipe 4 4-pipe  Nozzle variant K Small M Medium G Large  Arrangement of casings and connections Top entry primary air spigot (V) Supply air V-S V-M V-L V-R Supply and extract air combination (A) V-L-AR V-R-AL Side entry primary air spigot (H) Supply air H-SV H-SH H-LV H-LH H-MV H-MH H-RV H-RH Supply and extract air combination (A) H-LV-ARV H-RV-ALV H-LH-ARH H-RH-ALH H-LV-ARH H-RV-ALH H-LH-ARV H-RH-ALV  Total length (diffuser face) × nominal size [mm] L × LN Supply air 893 – 1500 × 900 1193 – 1800 × 1200...

 Open the catalog to page 10
DID300B-11

Induction units for suspended ceilings Order code Order examples DID300B-2-M-V-M/1000×900 Heat exchanger Nozzle variant Arrangement of casings and connections Total length (diffuser face) × nominal length 2-pipe Medium Top entry primary air spigot (V) 1000 × 900 mm DID300B-4-M-H-LV-ARV/1396×1200/P1-RAL9016/G3/VS Heat exchanger Nozzle variant Arrangement of casings and connections Total length (diffuser face) × nominal length Exposed surface Surface of heat exchanger Valves and actuators 4-pipe Medium Supply and extract air combination (A) 1396 × 1200 mm RAL 9016 Black (RAL 9005) With

 Open the catalog to page 11
DID300B-12

Induction units for suspended ceilings Construction with side entry primary air spigot L₁ Construction with top entry primary air spigot L₁ ① Suspension holes

 Open the catalog to page 12
DID300B-13

Induction units for suspended ceilings Non-active section as extension: 8 kg/m Top entry primary air spigot -1 kg/piece 02/2017 - DE/en TROX ®TECHNIK

 Open the catalog to page 13
DID300B-14

Induction units for suspended ceilings Casing arrangement Mit horizontalem Pri-marluftstutzen H-SV Primary air spigot at the front Casing arrangement: standard (centre) H-SH Primary air spigot at the rear Casing arrangement: standard (centre) H-MV Primary air spigot at the front Casing arrangement: centre H-MH Primary air spigot at the rear Casing arrangement: centre

 Open the catalog to page 14
DID300B-15

Induction units for suspended ceilings DID300B Casing arrangement Mit vertikalem Primar-luftstutzen Top entry primary air spigot Casing arrangement: standard Top entry primary air spigot Casing arrangement: left side V-M Top entry primary air spigot Casing arrangement: centre V-R Top entry primary air spigot Casing arrangement: right side

 Open the catalog to page 15

All TROX catalogs and technical brochures

  1. Type KA-EU

    21  Pages

  2. Type FK-EU

    52  Pages

  3. Type XSA

    21  Pages

  4. Type MSA

    21  Pages

  5. Type DLQ

    20  Pages

  6. Type DCS

    24  Pages

  7. Type FD

    22  Pages

  8. DID642

    22  Pages

  9. DID632

    25  Pages

  10. DID312

    22  Pages

  11. DID614

    17  Pages

  12. Control_units

    626  Pages

  13. Type FD

    35  Pages

  14. JZ-HL

    19  Pages

  15. JZ-LL

    23  Pages

  16. JZ-HL-AL

    16  Pages

  17. JZ-AL

    15  Pages

  18. JZ-LL-AL

    16  Pages

  19. Filter Media

    16  Pages

  20. Jet nozzles

    12  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.