TrojanUVFit?
8Pages

{{requestButtons}}

Catalog excerpts

TrojanUVFit? - 1

WASTEWATER DISINFECTION FILTERED IN-PIPE TREATMENT

Open the catalog to page 1
TrojanUVFit? - 2

Proven Trojan products. A new application. Validated, chemical-free disinfection from the industry leader Around the globe, wastewater treatment plants of all sizes are responding to the water quality and quantity demands of the communities they serve. As more municipalities adopt wastewater reuse policies and practices, wastewater treatment plants are required to treat effluent to higher levels –essentially eliminating all pathogens prior to reuse or discharge. Depending on site and design conditions, wastewater treatment plants producing filtered effluent sometimes prefer a disinfection...

Open the catalog to page 2
TrojanUVFit? - 3

Fully Validated Performance. System sizing is based on actual dose delivery verified through bioassay validation. Real-world, field performance data eliminates sizing assumptions and risks associated with theoretical dose calculations. Compact Design. The small reactor footprint simplifies indoor retrofit installations and reduces construction costs. Reliable, Proven Components. UV lamps, quartz sleeves, electronic ballasts, sensors and sleeve wiping system have been tested, proven reliable and are operating in hundreds of installations. Design Flexibility. Reactors can be installed in...

Open the catalog to page 3
TrojanUVFit? - 4

Designed for efficient, reliable performance Sleeve Wiping System Automatic sleeve wiping system operates on-line without interrupting disinfection. The wiping sequence occurs automatically at preset intervals without operator involvement. System Control Center The microprocessor or PLC-based controller continuously monitors and controls UV system functions. SCADA communication via ModBus for remote monitoring, control and dose pacing is available. Programmable digital and analog I/O capabilities can generate unique alarms for individual applications and send signals to operate valves and...

Open the catalog to page 4
TrojanUVFit? - 5

Power Distribution Center (PDC) The PDC panel distributes power to the reactor, UV intensity sensor and sleeve wiping system. The panel also houses high-efficiency, variable-output (60 –100% power) or constant-output ballasts with proven performance in hundreds of installations around the world. End Cap The end cap protects and isolates connections for components such as lamps, sleeves and wiping system. Power is automatically disconnected if end cap is removed thereby ensuring a safe working environment for operators. UV Reactor Electropolished 316L stainless steel chamber available in...

Open the catalog to page 5
TrojanUVFit? - 6

Regulatory-Endorsed Bioassay Validation Field testing ensures accurate dose delivery Benefits: • Validated in accordance with industry protocols established by National Water Research Institute (NWRI) • Performance data is generated from actual field testing over a wide range of flow rates and water quality (UV transmission) • Bioassay testing offers peace of mind and improved public and environmental safety due to verified dose delivery – not theoretical calculations Compact Reactor for Installation Flexibility Efficient, cost-saving design enables retrofit or new construction Benefits: •...

Open the catalog to page 6
TrojanUVFit? - 7

Built for Reliable Performance and Easy Maintenance Designed for trouble-free operation and minimal service Benefits: • Routine procedures, including lamp changeouts are simple and require minimal time – reducing maintenance costs • Access to internal components (lamps, sleeves, cleaning system) through service entrance at one end. • Service entrance and connections isolated and protected by end cap • Intensity sensor continuously monitors UV output to ensure dose delivery The TrojanUVFit™ lamps are easily replaced in minutes without the need for tools. Robust Sleeve Wiping System Automatic...

Open the catalog to page 7
TrojanUVFit? - 8

System Specifications Model Lamp Type High-efficiency, High-output, Low-Pressure Amalgam Sleeve Wiping Automatic Wiping System Electronic, constant output (100% power) or Electronic, variable output (60 to 100% power) Reactor Chamber Materials of Construction Standard Flange Size (ANSI/DIN), inches (mm) Outlet Flange Orientation Multiple orientations available 3, 6, 9, or 12 o’clock position Approx. Reactor Length, inches (mm) Power Distribution Center Electrical Supply Dimensions, inches Dimensions, mm 208V, 1 phase, 2 wire + GND, 50/60 Hz 240V, 1 phase, 2 wire + GND, 50/60 Hz (other...

Open the catalog to page 8

All Trojan Technologies Inc catalogs and technical brochures

  1. TrojanUVSwift

    10 Pages