Specifications:
The Trimod Besta Level Switch is designed with specific dimensions: D 200 mm, b 17 mm, k 160 mm, d2 18 mm, and d4 125 mm. It includes 8 units. The device does not have a ship register certificate.

Components:
The level switch consists of a switch module (Type A 304), a flange module (304), and a float module (98). The order number is A415736.

Operating Conditions:
- Operating Temperature: 0 to 70°C
- Ambient Temperature: 0 to 200°C
- Housing Material: Aluminium, sea water resistant
- Nominal Pressure: PN 8 bar, PP 13 bar
- Nominal Diameter: DN 80
- Switch Rating: 5A / 250VAC, 5A / 30VDC
- Enclosure Protection: IP65
- Flange Facing: PTFE
- Minimum Density: 0.750 kg/dm³
- Cable Entry: M20 x 1.5

Standards and Certifications:
The device complies with EN 1092-1 standards. It is important to avoid combinations of maximum values as per the temperature diagram 3081-009EN.

Contact Information:
Bachofen AG, Ackerstrasse 42, CH-8610 Uster, Switzerland. Phone: +41 44 944 11 11, Fax: +41 44 944 12 33, Email: [email protected], Website: www.trimodbesta.com
See more

Catalog excerpts

A 304 98-1

Trimod Besta Füllstandschalter Trimod Besta Level Switch Trimod Besta Contrôleur de niveau Safety Integrity Level: Ship register certificate: n/a Überwurfflansch Slip-on flange Bride folle Schmelze / Heat no: Bachofen-Nr. / Bachofen no: Dichteinheit / Fixflansch Sealing unit / Fixed flange Unité d'étanchéité / Bride fixe Schmelze / Heat no: Bachofen-Nr. / Bachofen no: *) The combinations of the maximum values are to be avoided! Limit value combinations acc. to temperature diagram 3081-009EN Schaltmodul A 304 98 Switch module (Art. no. A415736) Module de commande Betriebstemperatur Operating temp. Matériau boîtier Umgebungstemp. Ambient temp. Housing material Flanschmodul A Flange module Module de bride Nenndruck / -weite Aluminium Nom. Pressure / -Diameter Sea water resistant Pression- / Section Nominal Cable entry Schwimmermodul 304 Float module Module de flotteur *) PN 10 Operating diff. DN 80 Dichte min. Nenn- / Prüfdruck IP65 Flange Facing Type d'étanchéité Temp. d'ambiance Switch rating Order no. 98 Stk./ pcs./quant. Date/Visa Form B1 Nominal / Test press. Pression nominal / d'épreuve

 Open the catalog to page 1
A 304 98-2

Diagram show the limit values of the construction unit and/or the components, independently flange module / float module Micro switch type V15H10-TZ100 / -TZ100-A ■ Flat gasket type AFM 38 -100°C to 200°C Data sheet 338 Reinz

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.