EA-PSI 10000 4U

EA-PSI 10000 4U
1 / 97 PagesView full catalog

EA-PSI 10000 4U

Product catalog summary
General Information
  • Document Usage: The manual should be kept near the equipment for reference and transferred with the equipment if relocated.
  • Copyright: Unauthorized reproduction or use of this manual is prohibited.
  • Validity: Applicable to specific EA-PSI models listed in the document.
  • Symbols and Warnings: Various symbols indicate potential hazards and important operational information.
Warranty and Liability
  • Warranty: EA Elektro-Automatik guarantees the functionality and performance of the equipment from delivery.
  • Limitation of Liability: The manufacturer is not liable for misuse, unauthorized modifications, or use of non-approved parts.
Disposal
  • Equipment must be returned to the manufacturer for disposal according to European regulations.
Product Key
  • Explanation of product labeling, including options like water cooling and construction details.
Intended Usage
  • The device is designed as a variable voltage/current source or sink, intended for installation in suitable equipment.
Safety
  • Safety Notices: High voltage risks and safety procedures are outlined, including the need for proper disconnection and grounding.
  • Operator Responsibility: Operators must ensure safety compliance and provide necessary training and equipment to users.
  • User Requirements: Only qualified and trained personnel should operate the equipment.
User Responsibility
The equipment is used in industrial operations and must comply with legal safety regulations. Users must be informed of job safety requirements, understand the operating manual, and use recommended safety equipment. They are responsible for ensuring the device is technically fit for use.
Alarm Signals
The equipment provides optical, acoustic, and electronic alarm signals for various conditions, causing the DC output to switch off. Critical signals include OverVoltage (OVP) and Power Fail (PF), which can damage the device or load. Non-critical signals include OverTemperature (OT), OverCurrent (OCP), OverPower (OPP), Master-Slave Protection (MSP), and Share Bus Fail (SF).
Functionality Test
Operators must decide when to test the device's functionality, which could be before each use or at defined intervals. The test involves disconnecting cables, measuring voltage and current at different settings, and ensuring the device operates correctly within specified ranges.
Technical Data
Operating Conditions: The device operates between 0 °C to 50 °C and must be acclimatized if condensation occurs. It should be used in dry rooms with sufficient air circulation and can operate up to 2000 m above sea level.
Cooling: The device uses forced air cooling, with fans regulating speed based on internal temperature. Water-cooled versions use water as the main cooling agent.
General Specifications: The device features a color TFT touch screen, rotary knobs, and various interfaces for communication. It supports parallel operation of up to 64 units.
Safety and EMC: Complies with multiple safety and EMC standards, including EN 61010-1 and EN 55011.
Mechanical Construction: The device has forced air cooling, with dimensions of 19" x 4U x 668 mm and a weight of 50 kg. Water-cooled versions weigh 56 kg.
Specific Technical Data
AC Input: Supports voltage ranges of 208 V and 380-480 V, with a power factor of approximately 0.99.
DC Output: Offers various voltage, current, and power ranges, with protective functions like OVP, OCP, and OPP.
Insulation: Provides reinforced or basic insulation depending on the model.
Panel Descriptions
The front panel includes a power switch, TFT control interface, rotary knobs, and USB host. The rear panel features connectors for master-slave bus, interfaces, remote sense, share bus, DC output, AC input, grounding, and USB/Ethernet interfaces.
Front Panel Description:
The front panel of the PSI 10000 4U Water Cooling Option includes a power switch, a TFT control interface for interactive operation, a rotary knob with push-button action for settings and control, a USB host for data logging, and an On/Off push-button with LED status display.
Rear Panel Description:
The rear panel features master-slave bus connectors for parallel connection, a slot for interfaces, remote sense connectors, share bus connectors, inlets and outlets for water-cooling, a DC output terminal, an AC input connector, a grounding connection screw, and interfaces for USB and Ethernet.
Control Elements:
The control panel includes a touchscreen display for selecting set values and displaying actual values and status, rotary knobs for adjusting voltage, current, power, or resistance, and a USB port for connecting standard USB sticks.
General Description:
The PSI 10000 4U series power supplies are designed for industrial tests requiring high power, offering 30 kW rated power. They include a function generator for set point curves, USB and Ethernet ports for remote control, and options for additional digital interfaces. The devices support parallel connection for constant current sharing and master-slave operation, allowing up to 64 units to be combined for a total power of up to 1920 kW. Water-cooled versions are available for reduced noise and environmental heating.
Block Diagram:
The block diagram shows the main components and their relationships, including digital, microprocessor-controlled components that can be updated via firmware.
Scope of Delivery:
The package includes the power supply device, remote sensing plugs, a USB cable, DC terminal covers, a sense terminal cover, a USB stick with documentation and software, an AC connector plug, and a set for AC cable strain relief.
Accessories and Options:
Available accessories include digital interface modules for various protocols and options like 19" racks and water cooling systems. The water cooling option replaces standard cooling blocks to reduce heat and noise.
Control Panel (HMI):
The HMI features a touchscreen display, rotary knobs, a pushbutton, and a USB port. The display shows actual and set values for voltage, current, power, and resistance, with status information and menu access. The rotary knobs can be assigned to different functions, and values can be adjusted via the touchscreen or knobs.
USB Ports:
The front USB port is for connecting USB sticks for data logging and sequence loading. The rear USB-B port is for device communication and firmware updates, supporting ModBus RTU protocol or SCPI language.
USB Port and Interface Module: The USB port does not have priority over the interface module or the analog interface and can only be used alternatively. Monitoring is always available. The interface module slot can accommodate various modules from the IF-AB series, allowing for different connectivity options such as CANopen, RS232, Profibus, Ethernet, and ModBus. Modules can be installed by the user, and a firmware update may be necessary for compatibility. The device must be switched off before adding or removing modules.
Analog Interface: This interface allows for remote control via analog or digital signals, with monitoring always available. The input and output voltage ranges can be switched between 0-5 V and 0-10 V.
Share BUS and Sense Connector: The Share BUS allows for parallel operation in a master-slave configuration. The Sense connector compensates for voltage drops and should only be wired to the master in a master-slave system.
Master-Slave Bus and Ethernet Port: The master-slave bus enables multiple devices to be connected via RS485. The Ethernet port allows for remote control and monitoring via a web interface or TCP/IP, supporting SCPI or ModBus RTU protocols.
Water Cooling: Water cooling is an optional feature that reduces noise and improves cooling efficiency but requires active water flow and poses a risk of damage from leaks or condensation. Installation details are provided in section 2.3.4.
Installation and Commissioning: Transport and storage guidelines emphasize avoiding hand transport due to weight and using original packaging. Installation requires ensuring the location can support the device's weight and proper ventilation. Water cooling installation requires specific conditions for water flow and temperature to prevent condensation.
Safety and Preparation: Safety procedures include ensuring the supply voltage matches the product label and selecting appropriate cables for AC and DC connections. Installation should minimize connection lengths and ensure proper touch protection for AC connections.
Water Cooling Requirements: Specific requirements for water flow, temperature, and pressure are outlined, with emphasis on preventing condensation by maintaining water intake temperature above the dew point.
Specifications and Procedures:
The document provides detailed specifications and procedures for connecting and operating a device, likely a power supply unit. It includes tables with temperature and humidity data, indicating performance metrics at various conditions.
Connection to AC Supply:
Only qualified personnel should connect the device to an AC supply. The device must be connected directly to a power grid, not through generators or UPS equipment. The cable cross-section must match the maximum input current, and external fusing is required. For water-cooled models, a 30 mA RCD is recommended for safety.
AC Supply Requirements:
The device operates on a three-phase supply without N, with a rated power input of 30 kW. It can run on 380/400/480 V or 208 V, with power derating to 18 kW at 208 V. Proper grounding is essential for safety.
DC Load Connection:
Heavy DC cables require strain relief to prevent damage. Proper cross-section and electric strength of DC cables are crucial. The device lacks false polarity protection, so correct polarity is essential to avoid damage.
Grounding:
The enclosure and DC output can be grounded for safety. Grounding the DC terminal voids basic protection, requiring additional safety measures.
Remote Sensing:
Effective during constant voltage operation, remote sensing should be disconnected in other modes to prevent oscillation. Proper cable layout and dielectric strength are necessary.
Interface Module Installation:
Interface modules are user-installable and exchangeable. ESD protection is required during installation, and the device must be off.
Analog Interface and Share Bus:
The analog interface connects via a 15-pole connector, and the Share Bus balances voltage in parallel operations. Only compatible devices can connect to the Share Bus.
USB Port Connection:
The device can be controlled remotely via USB. Windows drivers are included, but Linux and MacOS drivers are not provided.
Initial Commissioning and Firmware Updates
For initial start-up, ensure connection cables are adequate, verify factory settings, and consult additional documentation for remote control. After firmware updates or long periods of non-use, similar checks are necessary before operation.
Operation and Safety
Only trained personnel should operate the device, especially when dealing with dangerous voltages. Use DC terminal covers for safety, and disconnect from mains when reconfiguring.
Operating Modes
The device operates in various modes: constant voltage (CV), constant current (CC), and constant power (CP). Each mode has specific characteristics and conditions under which it operates optimally.
  • Voltage Regulation: Maintains constant voltage unless limits are reached, then switches to CC or CP mode.
  • Current Regulation: Maintains constant current, switching to CC mode when limits are reached.
  • Power Regulation: Maintains constant power, adjusting current and voltage as needed.
Alarm Conditions
Alarms are indicated visually and acoustically, with specific alarms for power fail, overtemperature, overvoltage, overcurrent, and overpower conditions. Each alarm has specific triggers and responses to protect the device and connected applications.
Manual Operation
Switching on the device should be done using the rotary switch or an external cutout. The display provides device-related information upon startup.
Device Initialization and Configuration:
The device displays firmware versions and a language selection screen upon startup, followed by the main screen. Users can configure the DC output state after power-up in the settings menu, with options to keep it off or restore the last state. During startup, undefined statuses may appear on digital outputs, which should be ignored until the device is fully operational. Remote control can be blocked by activating 'Local' mode during manual operation.
Switching Off the Device:
To switch off, set the power switch to position 0, which stores the last DC output condition and set values, triggers a PF alarm, and powers off the device after a delay. The power switch physically disconnects the device from the AC grid.
Configuration via Menu:
The settings menu, accessible only when the DC output is off, allows configuration of various parameters using a numeric pad. Key settings include:
  • Presets: Set values for voltage (U), current (I), power (P), and resistance (R).
  • Protection: Adjust thresholds for over-voltage (OVP), over-current (OCP), and over-power (OPP) protection.
  • Limits: Define adjustment limits for parameters.
  • User Events: Set supervision thresholds for user-defined events.
  • Remote Control: Enable or disable remote control, affecting device operation.
  • Voltage Controller Speed: Adjust speed settings (slow, normal, fast) impacting voltage settling time.
  • SEMI F47: Activate/deactivate this feature related to a specific standard.
  • Analog Interface Range: Select voltage range for analog set values and reference voltage output.
  • REM-SB Level and Action: Configure input pin behavior for DC output control.
  • Pin Assignments: Customize alarm signaling for specific pins.
  • DC Output State: Configure DC output behavior after power-on, PF alarm, remote control exit, and OT alarm.
  • Master-Slave Mode: Enable and configure master-slave operation.
  • USB Logging: Configure logging settings, including interval and start/stop conditions.
  • Reset/Restart: Options to reset device to defaults or perform a warm start.
Sub Menus:
  • Profiles: Manage user profiles.
  • Overview: Display set values, alarm thresholds, and event settings.
  • About HW, SW: View device information like serial and article numbers.
  • Function Generator: Access function generator settings.
  • Communication: Configure digital communication settings for USB, Ethernet, and optional interface modules. Includes settings for DHCP, IP address, subnet mask, gateway, DNS, and port selection.
Specifications:
User-definable text for Profinet station name with a maximum length of 200 characters. CAN bus settings include baud rate (10 kbps to 1 Mbps, default 500 kbps), ID format (Standard 11 Bit or Extended 29 Bit), termination, data length, and base/broadcast IDs. RS232 settings include fixed serial settings with selectable baud rates.
Procedures:
Adjustment limits for set values (U, I, P, R) can be configured to prevent overvoltage. Operating modes (U/I, U/P, U/R) can be switched manually or via remote control. Set values can be adjusted using rotary knobs or direct input. The DC output can be switched on/off manually or remotely.
Norms and Recommendations:
Timeout settings for TCP, USB/RS232, and Ethernet connections are configurable. Communication protocols (SCPI or ModBus) can be enabled/disabled. USB logging is available with restrictions and can be configured for different CSV formats.
Key Data from Tables/Graphs:
CAN settings include default values and ranges for baud rate, ID formats, and cyclic read/send times. RS232 baud rates are listed. Timeout settings for various interfaces are provided with default values and ranges.
Critical Information:
Adjustment limits are crucial for protecting applications. Operating modes and set value adjustments are essential for device functionality. USB logging provides mobility and ease of data recording without a PC.
Quick Menu: The device features a quick menu for easy access to frequently used settings, accessible by swiping up or tapping a bar. Features can be toggled on or off, with active features indicated by black on white buttons. Key features include USB logging, master-slave mode, resistance mode, and HMI settings like alarm and key sounds.
Graph Functionality: From HMI firmware version 2.02, a graph feature is available to visually display voltage, current, and power values. It does not record data but can be accessed anytime via the quick menu. Limited controls are available while the graph is displayed, but the DC output can be switched off for safety.
Remote Control: The device supports remote control via built-in interfaces (analog, USB, Ethernet) or optional modules. Only one interface can control the device at a time. Remote control can be locked or allowed through settings, and switching between manual and remote control is possible.
Digital Interface Options: Various optional interface modules are supported, including CANopen, RS232, Profibus, ProfiNet, EtherCAT, and ModBus TCP. Programming details are available in the "Programming Guide ModBus & SCPI." Interface monitoring ensures the device does not operate uncontrolled if communication fails.
Analog Interface: The analog interface allows remote control of current, voltage, power, and internal resistance. It requires concurrent setting of values and operates in 0-5 V or 0-10 V ranges. Alarms can be acknowledged via the analog interface, and specific alarms require a HIGH-LOW-HIGH signal to reset.
Specifications: The analog interface includes various pins for setting and monitoring values, with specific voltage ranges and accuracy levels. The interface is internally sampled by a digital microcontroller, affecting resolution.
Analog Output (AO): The analog output is derived from an operational amplifier circuit with low impedance. Specifications are detailed in the table above.
Application Examples:
a) Switching the DC Output with Pin REM-SB: The REM-SB pin is used to control the DC output remotely. It cannot function as a safety stop switch, and an external emergency stop system is recommended. The pin's behavior varies depending on whether remote control is active or not, with different configurations for locking or enabling the DC output.
b) Remote Control of Current and Power: Remote control requires activation, and set values for power and current are generated using reference voltage and potentiometers. The input voltage range affects resolution, and external sources must adhere to specified voltage ranges.
c) Reading Actual Values: Actual current and voltage values on the DC output can be monitored using a multimeter or PLC.
Alarms and Monitoring:
Device Alarms: Alarms such as overvoltage protection (OVP) and overheating protection are distinguished from user-defined events. Device alarms typically switch off the DC output and require acknowledgment. Configurable alarms include OVP, OCP, and OPP, with thresholds adjustable via the menu.
User Defined Events: These events, such as undervoltage detection (UVD) and overcurrent detection (OCD), can be configured independently and are active only when the DC output is on. They can trigger actions like alarms to protect sensitive applications.
Locking Mechanisms:
Locking the Control Panel (HMI): The HMI can be locked to prevent accidental changes, with options for full lock or allowing On/Off button access. Unlocking requires a PIN if set.
Locking Adjustment Limits and User Profiles: Adjustment limits can be locked with a PIN to prevent unauthorized changes. The same PIN is used for both HMI and limits lock.
Loading and Saving User Profiles: Profiles allow quick loading of settings and set values. Up to 5 user profiles can be saved, with a default read-only profile available.
User Profile Management
To save current settings as a user profile, ensure the DC output is off, access the main menu, select 'Profiles', choose a profile slot, and save the settings. Profiles can be edited and saved or discarded. Profiles can also be imported/exported via USB.
Function Generator Overview
The built-in function generator (FG) creates various signal forms for voltage or current. It includes standard functions like sine, triangle, rectangular, trapezoid, and arbitrary waveforms. Photovoltaic simulations use an XY generator with a table of values.
Function Generator Limitations
The FG is inaccessible in resistance mode. The power supply cannot fully replicate high-frequency signals due to its power stages. Amplitude resolution is approximately 52428 steps, and certain combinations of time and amplitude may not be possible.
Technical Complications
Continuous charging/discharging in switching mode power supplies can damage output capacitors. Minimum slope requirements have been removed in newer models.
Method of Operation
The FG operates with set values for voltage (U), current (I), and power (P). Functions apply to one set value while others remain constant. Master-slave systems require careful configuration of global set values.
Manual Operation
Functions are selected and configured via the touch screen when the DC output is off. Parameters and global limits must be set before running a function. Functions can be started/stopped via the touch screen or On/Off button.
Sine Wave Function
Configurable parameters include frequency, amplitude, and offset. The maximum power output is calculated by adding amplitude and offset values.
Triangular Function
Parameters include amplitude, offset, and rise/fall times. The cycle time is the sum of rise and fall times, determining frequency.
Rectangular Function
Configurable parameters include amplitude, offset, and pulse/pause times. The duty cycle is defined by the ratio of pulse to total period.
Trapezoidal Function
Parameters include amplitude, offset, and times for rise, top, fall, and base values. The function can be adjusted to form various wave shapes.
DIN 40839 Function
This function simulates automobile battery voltage during engine start, divided into five sequence points. It is optimal for use with an electronic load.
Arbitrary Function: The arbitrary function generator allows users to create complex function curves using up to 99 sequence points, which can be configured for either current (I) or voltage (U). Each sequence point can be repeated up to 999 times or infinitely. Parameters such as AC/DC start and end values, frequency, angle, and time can be configured for each sequence point. The function can overlay a linear progression (DC) with a sine curve (AC).
Loading and Saving Arbitrary Functions: Sequence points can be saved to or loaded from a USB stick in CSV format. The file must contain 99 rows with specific parameters and be stored in a folder named HMI_FILES. The file name must start with WAVE_U or WAVE_I.
Ramp Function: This function generates a rising or falling ramp between start and end values over a specified time. It includes a delay before the ramp starts and runs once, stopping at the end value. For repeating ramps, the Trapezoid function should be used.
IU Table Function: This function allows setting a DC output current based on the DC output voltage using a table with 4096 values. The table can be uploaded via USB or remote control. The function operates in CC mode with a load in CV mode. The table must be in CSV format with specific naming and formatting requirements.
Loading IU Tables: IU tables can be loaded from a USB stick formatted as FAT32. The file must begin with IU, be in CSV format, and contain exactly 4096 values. The values must not exceed the device's nominal value. Files not meeting these specifications will not be accepted.
Simple PV (Photovoltaics) Function
  • Preface: This function allows the power supply to simulate solar panels using an XY generator. It calculates an IU table from four typical values and allows adjustment of a fifth parameter, Irradiance, to simulate different light conditions.
  • Key Characteristics: Short-circuit current (ISC), open circuit voltage (UOC), and maximum power point (MPP) are crucial. UMPP is typically 20% below UOC, and IMPP is 5% below ISC.
  • Safety Notices: Not all solar inverters are compatible due to high capacities on DC outputs. Verify with the inverter's manufacturer.
  • Usage: Parameters Uoc, Isc, Umpp, and Impp are adjustable. The simulation's effectiveness can be verified using visualization tools like EA Power Control.
FC Table Function (Fuel Cell)
  • Preface: Simulates voltage and current characteristics of a fuel cell by setting parameters for four support points.
  • Usage: Parameters include Uoc, Isc, and supporting points P2 and P3. The device calculates the function as a table and loads it to the XY generator.
Extended PV Function According to EN 50530
  • Introduction: Used to simulate solar panels for testing solar inverters, offering manual and remote control.
  • Differences to Basic PV Function: Includes single and automatic test runs, more adjustable parameters, and data recording capabilities.
  • Technologies and Parameters: Involves selecting solar panel technology (cSI, Thin film, Manual) and adjusting parameters like fill factors and temperature coefficients.
  • Simulation Modes: Includes U/I and E/T controllable simulations, and DAY U/I and DAY E/T automatic simulations.
  • Day Trend: Processes a curve of up to 100,000 points for long-term tests, with optional interpolation for intermediate points.
Intermediate Steps and Data Recording:
The document outlines the process of determining intermediate steps based on dwell time, with each step having a dwell time between 500 and 999 ms. These steps respect the slope between current and next day trend curve points, including value alterations. Data recording during simulation is possible, storing data every 100 ms with a maximum of 576,000 data sets, resulting in a maximum record time of 16 hours. Data can be saved to a USB stick or read via a digital interface.
Configuration and Simulation:
The configuration process involves selecting panel technology, adjusting parameters, and setting input modes. The simulation mode selection includes loading day trend data and enabling interpolation. The recording feature can be enabled to collect additional data. The simulation can be controlled manually or remotely, with specific stop criteria outlined, such as device alarms or user events.
Master-Slave Operation:
Devices can be connected in parallel in a master-slave configuration to increase total current and power. The Share bus balances units dynamically, and the master-slave bus connects up to 64 units. Wiring guidelines and restrictions are provided, including the need for termination at the bus ends. Mixed systems with different power classes or series are supported, with recommendations for selecting the master unit.
Remote Control and Other Applications:
The function generator can be remotely controlled, with specific commands differing from manual operation. Parallel operation in master-slave mode is detailed, including wiring and setup of the digital master-slave bus. Mixed systems with different power classes or series are supported, with guidelines for selecting the master unit to achieve optimal power output.
Configuring the Master-Slave Operation
  • Slave Configuration: Begin by configuring all slave units with the DC output off. Access the Settings menu, select 'Slave' mode, and activate bus termination if needed. Repeat for all slave units.
  • Master Configuration: Configure the master unit similarly, selecting 'Master' mode, which enables BIAS resistor termination.
  • Initialization: The master initializes the system, displaying results. If initialization fails, repeat the process. The system re-initializes each time the master is powered.
Operating the Master-Slave System
  • After configuration, the master displays the total system values. Slaves cannot be controlled manually but can be monitored.
  • The master controls the system and shares set values with slaves. It is remotely controllable.
  • Alarms on slaves are indicated on the master, requiring acknowledgment to continue operation.
  • Loss of connection to a slave results in a shutdown of all outputs, requiring re-initialization.
Alarms and Problem Situations
  • Loss of connection triggers an MSP alarm, switching off outputs. Re-initialization or deactivation of master-slave mode clears the alarm.
  • Slaves disconnected from AC supply need re-initialization upon return.
  • Multiple masters prevent system initialization.
  • Alarms are displayed on both master and slave units, with the master showing the most recent one.
Series Connection
  • Series connection is possible with restrictions: ensure no potential against ground exceeds specified limits, and remote sensing is not used.
  • Series connection is not supported in Master-Slave mode.
SEMI F47 Specification
  • Devices must continue operation during a power sag of up to -50% for 1.7 seconds.
  • SEMI F47 is disabled if the device boots with low AC voltage and requires decreased max power.
  • Activation adjusts power settings and can be stored for future boots.
Service and Maintenance
  • No regular maintenance is needed, but fan cleaning may be required.
  • Battery replacement should be done by qualified personnel.
  • For faults, contact the supplier and follow return procedures.
Firmware Updates
  • Updates should address existing bugs or add desired features. They carry risks and should be installed cautiously.
  • Review firmware changes thoroughly before updating.
Specifications and Safety Measures:
The document emphasizes the importance of connecting external sources, such as batteries, to the device with caution. It recommends attaching warning signs to ensure users are aware of polarity issues. Additionally, it suggests incorporating fuses in line with DC cables to prevent potential damage to the device.
Contact and Support:
For repairs, the device should be returned to the manufacturer unless otherwise arranged. No RMA number is required, but adequate packaging and a detailed fault description are necessary. Contact options for technical support include telephone and email, with specific contact details provided for EA Elektro-Automatik GmbH in Germany and EA Elektro-Automatik Inc. in San Diego, USA.
See more

Catalog excerpts

EA-PSI 10000 4U-1

Programmable DC Power Supplies © EA Elektro-Automatik in 2022, this information is subject to change without notice

 Open the catalog to page 1
EA-PSI 10000 4U-2

Installing the water cooling 31 Connection of remote sense 37 Installation of an interface module 38 Connecting the analog interface 39 Connecting the USB port (rear side) 39 Commission after a firmware update or a long period of non-use 39 Voltage regulation / Constant voltage 40 Current regulation / constant current / current limiting 41 Power regulation / constant power / power limiting 41 Internal resistance regulation 41 Changing the operating mode 52 Manual adjustment of set values 53 Recording to USB stick (logging) 54 Remote control via a digital interface 57 Remote control via the analog...

 Open the catalog to page 2
EA-PSI 10000 4U-3

3.6.2 Device alarm and event handling 63 3.7 Locking the control panel (HMI) 66 3.8 Locking the adjustment limits and user profiles 66 3.9 Loading and saving user profiles 67 3.10.5 Sine wave function 71 3.10.12 IU table function (XY table) 78 3.10.13 Simple PV (photovoltaics) function 80 3.10.14 FC table function (fuel cell) 81 3.10.15 Extended PV function according to EN 50530 83 3.10.16 Remote control of the function generator 88 3.11.1 Parallel operation in master-slave (MS) 89 4.2 Fault finding / diagnosis / repair 94 4.2.2 Trouble-shooting device problems 95 Attention! The part of this...

 Open the catalog to page 3
EA-PSI 10000 4U-4

This document is to be kept in the vicinity of the equipment for future reference and explanation of the operation of the device. This document is to be delivered and kept with the equipment in case of change of location and/or user. The most recent issue of this document can be found online, on our website. Reprinting, copying, also partially, usage for other purposes as foreseen of this manual are forbidden and breach may lead to legal process. This manual is valid for the following equipment including derived variants: EA Elektro-Automatik guarantees the functional competence of the applied...

 Open the catalog to page 4
EA-PSI 10000 4U-5

A piece of equipment which is intended for disposal must, according to European laws and regulations (ElektroG, WEEE) be returned to the manufacturer for scrapping, unless the person operating the piece of equipment or another, delegated person is conducting the disposal. Our equipment falls under these regulations and is accordingly marked with the following symbol: The device contains a Lithium battery cell. Disposal of that battery follows the above stated rule or specific local regulations. Decoding of the product description on the label, using an example: EA-PSI 10 080 - 1000 4U zzz Field...

 Open the catalog to page 5
EA-PSI 10000 4U-6

The equipment is intended to be used only as a variable voltage and current source or only as a variable current sink. Furthermore it's only intended to be used installed and operated in suitable equipment (19” rack or similar), together with a rigid, non-retractable AC supply connection. Typical application for a voltage source is DC power supply to any relevant user, including when used as battery charger to test charge various battery types, and for current sinks the replacement of an ohmic resistor by an adjustable electronic DC load in order to load relevant voltage and current sources of...

 Open the catalog to page 6
EA-PSI 10000 4U-7

• Electrical equipment operation means that some parts accessible on the outside of the device can be under high voltage. Therefore all parts under voltage must be covered during operation! This basically applies to all models, except for the 60 V model according to SELV. • The DC terminal is isolated from the AC input and not connected to ground internally. Hence there can be dangerous potential between the DC poles and PE, for instance caused by a connected external source application. Due to charged capacitors this could even be true if the DC output or the device are already switched off....

 Open the catalog to page 7
EA-PSI 10000 4U-8

Operator is any natural or legal person who uses the equipment or delegates the usage to a third party, and is responsible during its usage for the safety of the user, other personnel or third parties. The equipment is in industrial operation. Therefore the operators are governed by the legal safety regulations. Alongside the warning and safety notices in this manual the relevant safety, accident prevention and environmental regulations must also be applied. In particular the operator has to be acquainted with the relevant job safety requirements identify other possible dangers arising from the...

 Open the catalog to page 8
EA-PSI 10000 4U-9

The equipment offers various possibilities for signaling alarm conditions, however, not for danger situations. The signals may be optical (on the display as text), acoustic (piezo buzzer) or electronic (status output of the analog interface or digitally readable status bits). All alarms will cause the device to switch off the DC output. For details about the different alarms refer to section "3.3. Alarm conditions". The meaning of the signals is as follows: The operator of the device must decide when to check the device for correct functionality, by whom and how often. The when could either be...

 Open the catalog to page 9
EA-PSI 10000 4U-10

Technical data Approved operating conditions Ambiance The allowed ambient temperature range for operation is 0 °C (32 °F) to 50 °C (122 °F). During storage or transport, the allowed range extends to -20 °C (-4 °F) to 70 °C (158 °F). In case water condensation occurred due to transport, the device must be acclimatized prior to operation for at least 2 hours, ideally in a place with good air circulation. The device is intended to be operation in dry rooms. It must not be exposed or operated to extreme dust, high air humidity, danger of explosion and aggressive chemicals polluting the air. The operating...

 Open the catalog to page 10
EA-PSI 10000 4U-11

Voltage, Phases Power factor Leakage current Inrush current / Phase current Overvoltage category Temperature coefficient CV Compensation (Remote Sense) Load regulation CC Line regulation CC Stability CC Temperature coefficient CC Load regulation CP Load regulation CR Protective functions Range 1: 208 V, ±10%, 3ph AC (with DC output power derating to 18 kW) <0.05% FS (0 - 100% load, constant output voltage and constant temperature) <0.01% FS (208 V - 480 V AC +10% supply voltage, constant load and constant temperature) <0.02% FS (during 8 h of operation, after 30 minutes warm-up, at constant output...

 Open the catalog to page 11

All TPS Elektronik GmbH catalogs and technical brochures

  1. TO Series

    9  Pages

  2. EA-PS 100004U

    75  Pages

  3. EA-PS 10000 2U

    68  Pages

  4. TPS-MPT36S

    2  Pages

  5. ESD Trolley

    2  Pages

  6. EA-ELR 10000 4U

    96  Pages

  7. EA-ELR 10000 3U

    95  Pages

  8. EA-PSI 10000 2U

    92  Pages

  9. EA-PSB 10000 2U

    105  Pages

  10. EA-ELR 10000 2U

    91  Pages

  11. EA-PS 9000 1U

    4  Pages

  12. EA-PS 2000 B

    4  Pages

  13. EA-PS 3000C

    4  Pages

  14. HYT-1500360E

    6  Pages

  15. FSP550-50FS

    49  Pages

  16. FSP220-50FGBBI

    10  Pages

  17. FSP300-50UCB

    14  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.