Series DS-C Dry Type Sprinklers

Series DS-C Dry Type Sprinklers

Series DS-C Dry Type Sprinklers

Product catalog summary
Introduction
The TYCO Series DS-C Dry Type Sprinklers are designed for aesthetic environments such as nursing homes, restaurants, and schools. They feature a flat cover plate for concealment and allow for vertical adjustment and easy installation.
Specifications
- Sprinkler Identification Numbers (SINs): TY3535 (3 mm Bulb), TY3555 (5 mm Bulb)
- Approvals: UL and C-UL Listed, NYC Approved
- Maximum Working Pressure: 175 psi (12.1 bar)
- Inlet Thread Connections: 1 in. NPT, ISO 7-R1
- Discharge Coefficient: K=5.6 GPM/psi1/2
- Temperature Ratings: 155°F (68°C) with 139°F (59°C) Cover Plate, 200°F (93°C) with 165°F (74°C) Cover Plate
- Materials: Various metals including copper, stainless steel, and bronze
Operation
The sprinkler activates by heat, causing the cover plate to fall away and the glass bulb to shatter, releasing the plug and allowing water to flow.
Design Criteria
- Must be installed with Series RFII Concealed Cover Plates
- Not suitable for areas with higher air pressure above the ceiling
- Specific fittings required for installation
Installation
- Ensure proper fitting and sealing to prevent leaks and ensure functionality
- Use appropriate torque levels to avoid damage
- Follow specific steps for installation and cover plate assembly
Maintenance
Regular maintenance is required to ensure proper operation. The owner is responsible for maintaining the system in compliance with NFPA standards.
Warnings
- Improper installation can lead to system failure
- Follow all guidelines and standards to ensure safety and functionality
Procedures
Maintenance and care procedures emphasize obtaining permission before shutting down fire protection systems for maintenance. Ensure the absence of leaks and proper installation, including maintaining a nominal air gap between the cover plate and the ceiling.
Standards and Recommendations
The document references compliance with NFPA standards, specifically NFPA 25, for inspection, testing, and maintenance. It recommends using a qualified inspection service for these tasks.
Ordering Information
Details on ordering procedures include specifying the SIN, temperature rating, order length, and part number. Cover plates and sprinkler boots are also available for order, with specific part numbers provided.
Key Data from Tables and Figures
Table A provides minimum recommended lengths for exposed sprinkler barrels in wet pipe systems, considering temperature and wind velocity. Table B lists part numbers for the Series DS-C Standard Coverage Dry-Type Concealed Pendent Sprinkler. Figures illustrate sprinkler fitting configurations for heated and unheated areas, as well as the installation of the DSB-2 boot.
Warranty and Contact Information
The document includes a limited warranty and directs users to the Tyco Fire website for terms and conditions. Contact information for Johnson Controls is provided for further inquiries.
See more

Catalog excerpts

Series DS-C Dry Type Sprinklers-1

Worldwide www.tyco-fire.com Contacts Series DS-C Dry Type Sprinklers 5.6K Concealed Pendent Standard and Quick Response, Standard Coverage General Description TYCO Series DS-C Dry Type Sprinklers, 5.6K Concealed Pendent, Standard (5 mm Bulb) and Quick Response (3 mm Bulb) and Standard Coverage, are decorative sprinklers featuring a flat cover plate designed to conceal the sprinkler. This type of sprinkler is typically used to provide a sprinkler drop from an unheated attic into an area where aesthetics is a concern, such as nursing homes, restaurants, and schools. Each unit includes a Cover Plate Assembly that conceals the sprinkler operating components above the ceiling. The separable two-piece design of the Cover Plate and Support Cup Assemblies allows installation of the sprinklers and pressure testing of the fire protection system prior to installation of a suspended ceiling or application of the finish coating to a fixed ceiling. They also permit removal of suspended ceiling panels for access to building service equipment without having to first shut down the fire protection system and remove sprinklers. Also, the separable two-piece design of the Sprinkler provides for 1/2 in. (12,7 mm) of vertical adjustment. Series DS-C Sprinklers are shipped with a Disposable Protective Cap. The Protective Cap is temporarily removed for installation, and then it can be replaced to help protect the sprinkler while the IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. ceiling is installed or finished. The tip of the Protective Cap can also be used to mark the center of the ceiling hole into plaster board and ceiling tiles by gently pushing the ceiling product against the Protective Cap. When the ceiling installation is complete the Protective Cap is removed and the Cover Plate Assembly installed. NOTICE Series DS-C Dry Type Concealed Pendent Sprinklers described herein must be installed and maintained in compliance with this document and the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. Contact the installing contractor or product manufacturer with any questions. Series DS-C Dry Type Concealed Pendent Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. Sprinkler Identification Numbers (SINs) TY3535 - 3 mm Bulb TY3555 - 5 mm Bulb Technical Data Discharge Coefficient Temperature Ratings 155°F (68°C) Sprinkler with 139°F (59°C) Cover Plate 200°F (93°C) Sprinkler with 165°F (74°C) Cover Plate See Ordering Procedure section Physical Characteristics Inlet ���������������������������������������������������������� Copper Plug ��������������������������������������������������������� Copper Yoke. . . . . . . . . . . . . . . . . . . . . . . . Stainless Steel Casing. . . . . . . . . . . . . . Galvanized Carbon Steel Insert ���������������������������������������������������������Bronze Bulb Seat �������������������������������������� Stainless Steel Bulb ������������������������������������������������������������� Glass Deflector ���������������������������������������������������Bronze Frame �������������������������������������������������������Bronze Guide Tube ���������

 Open the catalog to page 1
Series DS-C Dry Type Sprinklers-2

Operation When TYCO Series DS-C Dry Type Concealed Pendent Sprinklers is in service, water is prevented from entering the assembly by the Plug with Gasketed Spring Plate Seal (see Figure 1) in the Inlet of the Sprinkler. PLUG WITH GASKETED SPRING PLATE SEAL When exposed to heat from a fire, the Cover Plate, which is normally soldered to the Retainer at three points, falls away to expose the Sprinkler Assembly. At this point the Deflector supported by the Guide Pins drops down to its operational position. The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature...

 Open the catalog to page 2
Series DS-C Dry Type Sprinklers-3

SPRINKLER FITTING (REFER TO DESIGN CRITERIA SECTION) FACE OF SPRINKLER FITTING ORDER LENGTHS: 5" (127,0 mm) to 48" (1219,2 mm) IN 1/4" (6,4 mm) INCREMENTS SPRINKLER SUPPORT CUP ASSEMBLY FACE OF CEILING, RETAINING RING MOUNTING SURFACE DEFLECTOR IN DROPPED POSITION COVER PLATE RETAINER ASSEMBLY FIGURE 2 SERIES DS-C STANDARD COVERAGE DRY-TYPE CONCEALED PENDENT SPRINKLER INSTALLATION DIMENSIONS 2-1/2" DIA. (63,5 mm) CLEARANCE HOLE FIGURE 3 DISPOSABLE PROTECTIVE CAP ALIGN ARROWS WITH FRAME ARMS ACCEPTS 1/2" SOCKET DRIVE FIGURE 4 RFII SPRINKLER WRENCH

 Open the catalog to page 3
Series DS-C Dry Type Sprinklers-4

Design Criteria TYCO Series DS-C 3 mm bulb-type Dry Type Concealed Pendent Sprinklers (TY3535) are UL and C-UL Listed as quick response, standard spray sprinklers for use in accordance with the current NFPA standard. Series DS-C 5 mm bulb-type Dry Type Concealed Pendent Sprinklers (TY3555) are UL and C-UL Listed as standard response, standard spray sprinklers for use in accordance with the current NFPA standard. Series DS-C Dry Type Sprinklers are only listed when installed with Series RFII Concealed Cover Plates having a factory-applied painted or metallic finish. Series DS-C Dry Type Sprinklers...

 Open the catalog to page 4
Series DS-C Dry Type Sprinklers-5

Installation TYCO Series DS-C Dry Concealed Pendent Sprinklers must be installed in accordance with this section. Series DS-C Dry Type Concealed Pendent Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. See the Design Criteria section for other important requirements regarding piping design and sealing of the clearance space around the Sprinkler Casing. Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter...

 Open the catalog to page 5
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.