  3. Series DS-2 Dry-Type Sprinklers 11.2K Pendent Standard and Quick Response, Standard Coverage

Series DS-2 Dry-Type Sprinklers 11.2K Pendent Standard and Quick Response, Standard Coverage

Series DS-2 Dry-Type Sprinklers 11.2K Pendent Standard and Quick Response, Standard Coverage

Series DS-2 Dry-Type Sprinklers 11.2K Pendent Standard and Quick Response, Standard Coverage

Product catalog summary
Introduction
The document outlines the technical specifications and installation guidelines for TYCO Series DS-2 Dry-Type Sprinklers, available in Standard and Quick Response models. These sprinklers are designed for environments with freezing temperatures, such as unheated areas or freezers.

Specifications
  • Sprinkler Identification Numbers (SINs): TY5255 for Standard Response, TY5235 for Quick Response.
  • Approvals: UL and C-UL Listed, NYC Approved under MEA 173-02-E.
  • Maximum Working Pressure: 175 psi (12.1 bar).
  • Inlet Thread Connections: 1 Inch NPT, ISO 7-R 1.
  • Temperature Ratings: Various ratings available, refer to Table A for details.
  • Finishes: Natural Brass, Chrome Plated, Signal White.
  • Materials: Copper, Stainless Steel, Bronze, Glass, Carbon Steel.

Operation
The sprinklers operate using a glass bulb filled with fluid that expands when heated. Upon reaching the rated temperature, the bulb shatters, activating the sprinkler to discharge water.

Design Criteria
Installation must comply with NFPA 13 standards, suitable for dry and wet pipe systems. Specific fittings and configurations are required to prevent freezing.

Installation Guidelines
  • Install in fittings meeting design criteria.
  • Seal clearance spaces to prevent condensation and ice build-up.
  • Use torque levels of 20 to 30 lb-ft to avoid leakage or damage.
  • Do not install if the bulb is cracked or has lost liquid.
  • Follow sealing and drainage instructions to prevent freezing.

Exposure Length and Drainage
Table B provides guidelines for minimum exposed barrel lengths to prevent freezing in wet pipe systems. Proper drainage and sealing are critical.

Figures and Tables
Includes figures and tables illustrating installation configurations, temperature ratings, and discharge coefficients, essential for correct installation and operation.
Installation and Maintenance Procedures
1. Use the W-Type 17 Sprinkler Wrench for installation and removal. Ensure non-hardening sealant is used and torque guidelines are followed.
2. After ceiling installation, slide the escutcheon into place without lifting the ceiling panel. For Deep Escutcheon, rotate the inner piece to secure it.

Care and Maintenance
- Maintain according to specified guidelines.
- Obtain permission before shutting down systems for maintenance.
- Absence of an escutcheon may delay operation.
- Inspect for leakage from the Vent Hole.
- Replace sprinklers showing leakage, corrosion, or damage.
- Do not alter sprinklers post-manufacture; replace if exposed to corrosive elements.
- Owners must comply with NFPA standards and local codes.

Ordering Information
- Specify details such as SIN, order length, inlet connections, temperature rating, and finish when ordering.
- Use the W-Type 17 Sprinkler Wrench and Model DSB-2 Dry Sprinkler Boot for installation.

Specifications
- Finishes include chrome plated, natural brass, and signal white.
- Temperature ratings range from 135°F to 286°F.
- Order lengths vary from 5.50 inches to 48.00 inches.
- Part numbers are based on response type, escutcheon type, and order length.
See more

Catalog excerpts

Series DS-2 Dry-Type Sprinklers 11.2K Pendent Standard and Quick Response, Standard Coverage-1

Worldwide www.tyco-fire.com Contacts Series DS-2 Dry-Type Sprinklers 11.2K Pendent Standard and Quick Response, Standard Coverage General Description Series DS-2 Dry-Type Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. TYCO Series DS-2 Dry-Type Sprinklers, 11.2K Pendent, Standard (5 mm bulb) and Quick Response (3 mm bulb), and Standard Coverage are decorative glass bulb automatic sprinklers typically used where: Sprinkler Identification Numbers (SINs) • pendent sprinklers are required on dry pipe systems that are exposed to freezing temperatures (e.g., sprinkler drops from unheated portions of buildings) TY5255 – Standard Response TY5235 – Quick Response • sprinklers and/or a portion of the connecting piping may be exposed to freezing temperatures (e.g., sprinkler drops from wet systems into freezers) NOTICE Series DS-2 Dry-Type Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. Contact the installing contractor or product manufacturer with any questions. IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Technical Data Approvals UL and C-UL Listed NYC Approved under MEA 173-02-E Refer to Table A. Maximum Working Pressure 175 psi (12,1 bar) Inlet Thread Connections 1 Inch NPT ISO 7-R 1 Discharge Coefficient Refer to Table C. Temperature Ratings Refer to Table A. Finishes Sprinkler: Refer to Table D. Escutcheon: Refer to Table D. Physical Characteristics Inlet ���������������������������������������������������������� Copper Plug ��������������������������������������������������������� Copper Yoke. . . . . . . . . . . . . . . . . . . . . . . . Stainless Steel Casing. . . . . . . . . . . . . . Galvanized Carbon Steel Insert ���������������������������������������������������������Bronze Bulb Seat ���������������������������������������������������Bronze Bulb ������������������������������������������������������������� Glass Compression Screw. . . . . . . . . . . . . . . . . Bronze Deflector ���������������������������������������������������Bronze Frame �������������������������������������������������������Bronze Guide Tube ���������������������������������� Stainless Steel Water Tube ��������������������������������� Stainless Steel Spring. . . . . . . . Stainless Steel Gasketed Spring Plate Seal . . . . . . . . Beryllium Nickel w/TEFLON Pin. . . . . . . . . . . . . . . . . . . . . . . . . Stainl

 Open the catalog to page 1
Series DS-2 Dry-Type Sprinklers 11.2K Pendent Standard and Quick Response, Standard Coverage-2

Temperature Rating Design Criteria TYCO Series DS-2 Dry-Type Sprinklers, 11.2K Pendent, Standard (5 mm bulb) and Quick Response (3 mm bulb), and Standard Coverage are intended for use in fire sprinkler systems designed in accordance with the standard coverage installation rules recognized by the applicable listing agency (e.g., uL Listing is based on NFPA 13 requirements). Sprinkler Fittings Install 1 inch NPT Series DS-2 Dry-Type Sprinklers in the 1 inch NPT outlet or run of the following fittings: • malleable or ductile iron threaded tee fittings that meet the dimensional requirements of ANSI...

 Open the catalog to page 2
Series DS-2 Dry-Type Sprinklers 11.2K Pendent Standard and Quick Response, Standard Coverage-3

Notes: 1. For protected area temperatures that occur between values listed above, use the next cooler temperature. 2. These lengths are inclusive of wind velocities up to 30 mph (18,6 kph). TABLE B EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS MINIMUM RECOMMENDED LENGTHS TFP530 Page 3 of 8 Clearance Space In accordance with Section 8.4.9.2 of the 2010 edition of NFPA 13, when connecting an area subject to freezing and an area containing a wet pipe sprinkler system, the clearance space around the sprinkler barrel of dry-type sprinklers must be sealed. Due to temperature differences between two...

 Open the catalog to page 3
Series DS-2 Dry-Type Sprinklers 11.2K Pendent Standard and Quick Response, Standard Coverage-4

K-factor Length, Inches (mm)

 Open the catalog to page 4
Series DS-2 Dry-Type Sprinklers 11.2K Pendent Standard and Quick Response, Standard Coverage-5

FACE OF ORDER LENGTHS: SPRINKLER FITTING 1" to 45-1/4" (25,4 to 1149,4 mm) IN 1/4" (6,4 mm) INCREMENTS FACE OF CEILING FOR ORDER LENGTHS < 3-1/4" (82,6 mm): 4-7/8±1/8" (123,8±3,2 mm) * -orFOR ORDER LENGTHS ≥ 3-1/4" (82,6 mm): 5-5/8±1/8" (142,9±3,2 mm) ** SPRINKLER WRENCHING AREA SPRINKLER FITTING (REFER TO DESIGN CRITERIA SECTION) WRENCH RECESS WILL PERMIT ±5/8" (15,9 mm) ADJUSTMENT PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 6 W-TYPE 17 SPRINKLER WRENCH WILL PERMIT ±1-3/8" (34,9 mm) ADJUSTMENT FIGURE 4 SERIES DS-2 DRY-TYPE PENDENT WITH EXTENDED ESCUTCHEON STANDARD...

 Open the catalog to page 5
Series DS-2 Dry-Type Sprinklers 11.2K Pendent Standard and Quick Response, Standard Coverage-6

HEATED AREA SIDE OUTLET PLUGGED SPRINKLER FITTING (SEE DESIGN FACE OF SPRINKLER FITTING HEATED AREA EXPOSURE LENGTH (SEE DESIGN CRITERIA FIGURE 10 EXPOSURE LENGTH AREA SUBJECT TO FREEZING FITTING (SEE DESIGN CRITERIA SECTION) Lxd FIGURE 9 SPRINKLER FITTING UNHEATED AREA STRAP TIES (ENDS ON OPPOSING SIDES OF BOOT) DSB-2 BOOT ADHESIVE 2-3/4" DIA. (69,9 mm) CLEARANCE HOLE INSULATED FREEZER STRUCTURE DS-2 SHOWN WITH FLUSH ESCUTCHEON Installation TYCO Series DS-2 Dry-Type Sprinklers, 11.2K Pendent, Standard (5 mm bulb) and Quick Response (3 mm bulb), and Standard Coverage must be installed in accordance...

 Open the catalog to page 6
Series DS-2 Dry-Type Sprinklers 11.2K Pendent Standard and Quick Response, Standard Coverage-7

Care and Maintenance TYCO Series DS-2 Dry-Type Sprinklers, 11.2K Pendent, Standard (5 mm bulb) and Quick Response (3 mm bulb), and Standard Coverage must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, may delay the...