General Description: The TYCO Model ESFR-17 Dry Type Pendent Sprinklers are designed for Early Suppression, Fast Response (ESFR) with a nominal K-factor of 16.8. They are ideal for high-piled refrigerated storage areas, eliminating the need for in-rack sprinklers. These sprinklers are FM Approved and suitable for freezing temperatures, with water supplied from a wet pipe system outside the refrigerated area.
Specifications: The sprinkler features a grooved and threaded inlet, bronze casing, and galvanized steel pipe frame. It operates with a fusible link assembly that activates at a rated temperature, allowing water flow. It is UL Listed and FM Approved, with a maximum working pressure of 175 psi (12 bar).
Design Criteria: Designed for ceiling-only protection, these sprinklers cover a maximum area of 100 ft² and require a minimum clearance of 36 inches to the commodity. Installation must comply with NFPA standards and other applicable guidelines.
Installation and Maintenance: Installation must adhere to NFPA standards. Insulating Seal Assemblies are recommended to prevent condensation and ice buildup. Proper maintenance is essential for functionality.
Technical Data: The sprinkler has a K-factor of 16.8 gpm/psi½, with a threaded size of 1-1/4 in. NPT or ISO 7-R 1-1/4. It is suitable for various storage types, including solid pile, palletized, and rack storage of plastics and other materials, as per NFPA and FM Global standards.
Installation Guidelines: Detailed instructions include using specific fittings and couplings, sealing the clearance hole around the sprinkler barrel, and handling the fusible link assembly carefully to avoid damage.
Installation Instructions: Handle the fusible link assembly using only the casing and appropriate sprinkler wrench. Damaged sprinklers must be replaced. Install in fittings that meet design criteria, ensuring proper sealing of the clearance space.
Threaded Connection Instructions: Ensure a leak-tight 1-1/4 in. NPT sprinkler joint by applying a torque of 45 to 65 lb-ft. Use a non-hardening pipe thread sealant and the W-Type 26 Sprinkler Wrench for installation.
Grooved Connection Instructions: Use the 2 in. Figure 705 Grooved Flexible Coupling or the 2 in. Figure 577 Grooved Rigid Coupling. Ensure proper engagement and alignment, and torque bolts to 30 lb-ft.
Care and Maintenance: Maintain and service according to guidelines. Replace any leaking or corroded sprinklers. Inspect the vent hole for leakage and replace damaged components as needed.
Ordering Procedure: Contact a local distributor for availability. Specify the full product name and part number when ordering. Options include different lengths and temperature ratings.
Warranty and Contact Information: For warranty terms, visit the Tyco Fire website. For inquiries, contact Johnson Controls at the provided address and phone number.
See more

Catalog excerpts

ESFR-17-1

Worldwide Contacts Model ESFR-17 16.8 K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. General Description TYCO Model ESFR-17 Dry Type Pendent Sprinklers are Early Suppression, Fast Response (ESFR) sprinklers having a nominal K-factor of 16.8. They are suppression mode sprinklers that are especially advantageous as a means of eliminating in-rack sprinklers when protecting high-piled box-in-box refrigerated storage areas. The Model ESFR-17 Dry Type Pendent Sprinkler is FM Approved and has successfully undergone full-scale fire testing at fM Global, when used in conformance with applicable FM Global Property Loss Prevention Data Sheets. The Model ESFR-17 Dry Type Sprinkler consists of an ESFR sprinkler permanently secured to a sprinkler drop featuring an inlet with both grooved and threaded connections. The drop between the inlet and sprinkler remains dry until the sprinkler operates, allowing for a pendent sprinkler installation on a wet pipe sprinkler system where the dry drop and sprinkler are located in an area subjected to freezing temperatures. The Model ESFR-17 Dry Type Sprinklers are primarily used for ceiling only sprinkler protection (i.e., no need for in-rack sprinklers) and used to protect solid piled, palletized, and rack storage that is subject to freezing temperatures. The water supply is provided from a wet pipe system located outside of the refrigerated storage area. The Model ESFR-17 Dry Type Sprinklers feature all of the same design criteria as 16.8 K-factor ESFR Pendent Sprinklers, and substantially lowers the end head pressure requirement as compared to the 14.0 K-factor ESFR Dry Type Pendent Sprinklers. Combining a 16.8 K-factor with a dry-type sprinkler design, the Model ESFR-17 Dry Type Sprinkler provides the system designer with features that offer flexibility when sizing system piping, as well as possibly reducing or eliminating the need for a system fire pump when protecting high-piled box-in-box refrigerated storage areas. The ESFR-17 Dry Type Sprinkler also includes two Insulating Seal Assemblies that help seal the clearance space around the sprinkler casing. The seal assemblies are intended to slow the exchange of air between the heated area and the protected area to help prevent humidity and temperature differential in the area around the sprinkler. Condensation on the sprinkler and subsequent ice buildup on or around the sprinkler can occur that might damage the sprinkler or prevent proper operation in a fire situation. To install the Insulating Seal Assemblies, follow the installation instructions in this data sheet. The Insulating Seal Assemblies are recommended to be installed on smooth, flat, and clean surfaces. If it is expected that environmental conditions may result in excessive condensation, additional sealing of the assembly is recommended. There are specific situations, such as corrugated surfaces where alternate methods to seal the clearance hole are recommended. The Model ESFR-17 Dry Type Pendent Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintaining their fire protection system and devices in proper operating condition. Contact the installing contractor or product manufacturer with any questions. Sprinkler Identification Number (SIN) See Table B for sprinkler identification number.

 Open the catalog to page 1
ESFR-17-2

TFP320 Page 2 of 8 GROOVED COUPLING GASKET SEALING SURFACE 1-1/4" NPT OR ISO 7-R 1-1/4 PIPE THREADED CONNECTION 2" (DN50) GROOVED CONNECTION THREADED AND GROOVED INLET INLET WRENCH HEX Technical Data Approvals UL Listed FM Approved (See Table D for specific details on Laboratory listings and approvals.) Grooved Connection 2 in. Standard Cut Grooved per Technical Data Sheet TFP1898 Physical Characteristics Threaded and Grooved Inlet Bronze Casing. . . . . . . . . . . . . . . . Galvanized Steel Pipe Frame ���������������������������������������������������������Brass Deflector ���������������������������������������������������Bronze...

 Open the catalog to page 2
ESFR-17-3

Notes: 1. UL Listed 2. FM Approved TABLE D LABORATORY LISTINGS AND APPROVALS Ceiling Construction Unobstructed or non-combustible obstructed construction, such as smooth ceiling, bar joists, beam and girder. Ceiling Slope Maximum 2 in. rise for 12 in. run (16.7%) Maximum Coverage Area 100 ft2 (9,3 m2) In some cases, the installation standards permit a greater coverage area. Minimum Coverage Area 64 ft2 (5,8 m2) Maximum Spacing 12 ft (3,7 m) for ceiling heights up to 30 ft (9,1 m) 10 ft (3,1 m) for ceiling heights greater than 30 ft (9,1 m) Minimum Spacing 8 ft (2,4 m) Minimum Clearance to Commodity...

 Open the catalog to page 3
ESFR-17-4

EXPOSED BARREL LENGTH (REFER TO TABLE D AND DESIGN CRITERIA) HEATED AREA DIM. A TABLE A Ambient Temp. of Protected Area(a) EXPOSED BARREL LENGTH (REFER TO TABLE D AND DESIGN CRITERIA) HEATED AREA DIM. A TABLE A GROOVED FITTING AND RIGID OR FLEXIBLE COUPLING (REFER TO DESIGN CRITERIA) INSULATING SEAL ASSEMBLIES Notes: a. The area below the ceiling is referred to as the protected area. Ambient temperature is the temperature at the discharge end of the sprinkler. For protected area temperatures that range between the listed temperatures, use the next cooler temperature. b. Lengths are inclusive...

 Open the catalog to page 4
ESFR-17-5

THREADED SPRINKLER FITTING W-TYPE 26 WRENCH "INLET SIDE" MODEL ESFR-17 DRY PENDENT SPRINKLER GROOVED RIGID OR FLEXIBLE COUPLING (REFER TO DESIGN CRITERIA) WELDED GROOVED OUTLET MODEL ESFR-17 DRY PENDENT SPRINKLER GROOVED RIGID OR FLEXIBLE COUPLING (REFER TO DESIGN CRITERIA) GROOVED DROP NIPPLE MODEL ESFR-17 DRY PENDENT SPRINKLER SYSTEM PIPE SPRINKLER FITTING WRENCH JAW APPLY WRENCH JAW TO INLET WRENCH HEX FIGURE 5 W-TYPE 26 SPRINKLER WRENCH Sprinkler Grooved Connection The Model ESFR-17 Dry Type Sprinklers can be installed in typical grooved connection scenarios illustrated in Figure 4. For flexible...

 Open the catalog to page 5