1. Catalogs
  2. Top Cable
  3. TOPCABLE_X-VOLT_RHZ1_6,35-11KV_AL_EN

TOPCABLE_X-VOLT_RHZ1_6,35-11KV_AL_EN

TOPCABLE_X-VOLT_RHZ1_6,35-11KV_AL_EN

TOPCABLE_X-VOLT_RHZ1_6,35-11KV_AL_EN

Product catalog summary
Design Specifications
  • Conductor: Aluminium, class 2, compliant with EN 60228 and IEC 60228.
  • Internal Semiconductor: Thermosetting semiconductor material screen over the conductor.
  • Insulation: Cross-linked polyethylene (XLPE) applied through a triple layer extrusion process.
  • External Semiconductor: Non-strippable thermosetting semiconductor material screen over the insulation.
  • Metallic Screen: Copper wires and tape with a minimum cross-section of 32mm2.
  • Longitudinal Sealing: Hygroscopic tape over the metallic screen.
  • External Sheath: Halogen-free polyolefin, red color.
  • Assembly: Three stranded single-core cables in triplex formation.
Applications
  • Medium Voltage aluminium cables for electricity transmission and distribution.
  • Halogen-free, suitable for medium voltage applications with XLPE insulation.
Electrical Performance
  • Voltage: 6,35/11 kV.
  • Standards: BS 7870-4.10 / IEC 60502-2.
Thermal Performance
  • Maximum service temperature: 90ºC.
  • Maximum short-circuit temperature: 250ºC (max. 5 s).
  • Minimum service temperature: -15ºC.
Fire Performance
  • Halogen-free based on UNE-EN 50267.
Mechanical Performance
  • Minimum bending radius: 15 times the cable diameter.
Installation Conditions
  • Suitable for open air, buried, and conduit installations.
Applications
  • Distribution networks.
Other Characteristics
  • Meter by meter marking.
See more

Catalog excerpts

TOPCABLE_X-VOLT_RHZ1_6,35-11KV_AL_EN-1

Medium Voltage aluminium cable, XLPE insulation, halogen free, in triplex formation. Aluminium conductor, class 2, based on EN 60228 and IEC 60228. 2. Internal semiconductor Screen over the conductor, made of thermosetting semiconductor material. 3. Insulation Cross-linked polyethylene (XLPE), in dry atmosphere catenary tube, through a triple layer extrusion process. 4. External semiconductor Screen over the insulation, made of thermosetting non-strippable semiconductor material. 4. Metallic screen Screen of copper wires and copper tape, applied over the outer semiconductirng layer, with a minimum cross-section of 32mm2. 5. Longitudinal sealing Hygroscopic tape applied over the metallic screen. 6. External sheath External sheath of halogen-free polyolefin, red colour. Assembly of single-core cables Three stranded single-core cables in triplex formation. APPLICATIONS Medium Voltage aluminium cables for transmission and distribution of electricity. Halogen free. This cable render is an example from this product does not neccesarily match the selected core size or number of cores.

 Open the catalog to page 1
TOPCABLE_X-VOLT_RHZ1_6,35-11KV_AL_EN-2

CHARACTERISTICS O Electrical performance MEDIUM VOLTAGE 6,35/11 kV. Standard BS 7870-4.10 / IEC 60502-2. O Thermal performance Maximum service temperature: 90°C. Maximum short-circuit temperature: 250°C (max. 5 s). Minimum service temperature: -15°C Fire performance Halogen free: based on UNE-EN 50267. Mechanical performance Minimum bending radius: x15 cable diameter. Installation conditions Open Air. Buried. In conduit. Applications Distribution networks. Other Meter by meter marking.

 Open the catalog to page 2

All Top Cable catalogs and technical brochures

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.