Design Specifications
  • Conductor: Aluminium, class 2, compliant with EN 60228 and IEC 60228.
  • Internal Semiconductor: Thermosetting semiconductor material screen over the conductor.
  • Insulation: High module ethylene propylene rubber (HEPR) applied through a triple layer extrusion process, with a lead-free option available.
  • External Semiconductor: Thermosetting and strippable semiconductor material screen over the insulation.
  • Metallic Screen: Composed of copper wires and tape, with a minimum cross-section of 16m².
  • Separator: Polyester tape covering the screen, optionally replaced by hygroscopic tape for longitudinal sealing.
  • External Sheath: Halogen-free polyolefin, red in color.
Applications
  • Medium Voltage aluminium cable for electricity transmission and distribution, halogen-free.
Electrical Performance
  • Voltage Ratings: 12/20 kV and 18/30 kV.
  • Standard: UNE-HD 620-9E (type 9E-1).
  • Approvals: AENOR certified.
Thermal Performance
  • Maximum service temperature: 105ºC.
  • Maximum short-circuit temperature: 250ºC (max. 5 seconds).
  • Minimum service temperature: -15ºC.
Fire Performance
  • Halogen-free as per UNE-EN 50267.
Mechanical Performance
  • Minimum bending radius: 15 times the cable diameter.
  • Abrasion and tear resistant.
Chemical Performance
  • UV Resistant according to UNE 211605.
Installation Conditions
  • Suitable for open air, buried, and conduit installations.
Applications
  • Designed for distribution networks.
Other Characteristics
  • Meter by meter marking for easy measurement.
See more

Catalog excerpts

TOPCABLE_X-VOLT_HEPRZ1_AL_EN-1

Medium Voltage aluminium cable, HEPR insulation, halogen free. UNE-HD 620-9E (type 9E-1) Aluminium conductor, class 2, based on EN 60228 and IEC 60228. 2. Internal semiconductor Screen over the conductor, made of thermosetting semiconductor material. 3. Insulation High module ethylene propylene rubber (HEPR), in dry atmosphere catenary tube, through a triple layer extrusion process. Lead-Free version available on request. Screen over the insulation, made of thermosetting and strippable semiconductor material. 4. Metallic screen Screen of copper wires and copper tape, with a minimum cross-section of 16m2. Polyester tape completely covering the screen to facilitate the stripping of the outer sheath. Optionally, substituted by hygroscopic tape (cables with longitudinal sealing, type -OL and -2OL) 6. External sheath External sheath of halogen-free polyolefin, red colour. APPLICATIONS Medium Voltage aluminium cable for the transmission and distribution of electricity. Halogen free. This cable render is an example from this product does not neccesarily match the selected core size or number of cores.

 Open the catalog to page 1
TOPCABLE_X-VOLT_HEPRZ1_AL_EN-2

CHARACTERISTICS O Electrical performance MEDIUM VOLTAGE 12/20 kV and 18/30 kV. Standard UNE-HD 620-9E (type 9E-1). Approvals AENOR Thermal performance Maximum service temperature: 105°C. Maximum short-circuit temperature: 250°C (max. 5 s). Minimum service temperature: -15°C Fire performance Halogen free: based on UNE-EN 50267. Mechanical performance Minimum bending radius: x15 cable diameter. Abrasion resistant. Tear resistant. Installation conditions Open Air. Buried. In conduit. Applications Distribution networks. Other Meter by meter marking.

 Open the catalog to page 2

All Top Cable catalogs and technical brochures