Design Specifications
  • Conductor: Aluminium, class 2 based on EN 60228 and IEC 60228.
  • Insulation: Cross-linked polyethylene (XLPE).
  • Outer Sheath: Flexible PVC, available in black or grey.
Applications

This aluminium cable is suitable for underground networks for public power distribution and low voltage connections in industrial plants, urban networks, and buildings. It is recommended for installations with simple configurations where flexibility is not required.

Characteristics
  • Electrical Performance: Low voltage 0.6/1kV, compliant with UNE-HD 603-5N / NF C 32-321 standards.
  • Approvals: CE, NF-USE, AENOR, RoHS.
  • Thermal Performance: Maximum service temperature of 90ºC, short-circuit temperature of 250ºC (max. 5 seconds), and minimum service temperature of -40ºC for fixed and protected installations.
  • Fire Performance: Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1, with reduced halogen emissions (Chlorine <15%).
  • Mechanical Performance: Minimum bending radius is five times the cable diameter, with medium severity impact resistance (AG2).
  • Chemical Performance: Good resistance to chemicals and oil, UV resistant as per UNE 211605 and NF-C 32-323.
  • Water Performance: Water resistance rated at AD7 for immersion.
  • Other Features: Meter by meter marking for easy measurement.
Installation Conditions
  • Suitable for open air, buried, and conduit installations.
Applications
  • Industrial use and distribution networks.
See more

Catalog excerpts

TOPCABLE_POWERHARD_RV_AL_U1000_AR2V_EN-1

POWERHARD RV AL / U-1000 AR2V Aluminium cable for power transmission. 1. Conductor Aluminium, class 2 based on EN 60228 and IEC 60228. 2. Insulation Cross-linked polyethylene (XLPE) 3. Outer sheath Flexible PVC, Black or grey colour. This Aluminuim cable is suitable for all types of underground networks for public power distribution, as well as low voltage connexions in industrial plants, urban networks, buildings, etc. Due to its rigidity, its use is recommended in installations with a simple configuration where a flexible cable is not needed. This cable render is an example from this product does not neccesarily match the selected core size or number of cores.

 Open the catalog to page 1
TOPCABLE_POWERHARD_RV_AL_U1000_AR2V_EN-2

Electrical performance LOW VOLTAGE 0,6/1kV Standard UNE-HD 603-5N / NF C 32-321 Approvals CE NF-USE AENOR RoHS Thermal performance Maximum service temperature: 90°C. Maximum short-circuit temperature: 250°C (max. 5 s). Minimum service temperature: -40°C (fixed and protected installations). Fire performance Flame non-propagation based on UNE-EN 60332-1 and IEC 60332-1. Reduced emission of halogens. Chlorine <15%. O Mechanical performance Minimum bending radius: x 5 cable diameter. Impact resistance: AG2 Medium severity. O Chemical performance Chemical & Oil resistance: Good. UV Resistant: UNE...

 Open the catalog to page 2

All Top Cable catalogs and technical brochures

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.