TSP-CO2 Series

TSP-CO2 Series

TSP-CO2 Series

Product catalog summary
Overview
The TSP-CO2 Series is a versatile carbon dioxide detector designed for real-time monitoring and control of CO2 levels, with optional temperature and relative humidity (RH) detection. It features a Non-Dispersive Infrared (NDIR) CO2 sensor with patented self-calibration for enhanced accuracy and reliability.

Key Features
  • Real-time CO2, temperature, and RH measurement capabilities.
  • NDIR infrared CO2 sensor with self-calibration, offering up to 10 years of sensor life.
  • Selectable PID control output for CO2 measurement.
  • Optional OLED display for CO2, temperature, and RH readings.
  • RS485 communication interface supporting Modbus or BACnet protocols.
  • Optional relay output for controlling a fan or CO2 generator.
  • 3-color LED indicator for CO2 level ranges and operational status.
  • Buzzer alarm available for models with relay output.

Specifications
  • Power Supply: 24VAC/VDC ± 10%
  • Consumption: Max 3.5 W; Avg 2.0 W
  • Analog Outputs: One or two 0~10VDC/4~20mA for CO2 or CO2/Temp.
  • Relay Output: One passive relay output (max. 5A).
  • Communication: RS485 interface with Modbus or BACnet protocol.
  • LED Light Modes: 3-color mode and working light mode.
  • Operating Conditions: 0~50℃; 0~95%RH, non-condensing.
  • Storage Conditions: -10~60℃, 0~80%RH.
  • Dimensions: 117mm(H)×95mm(W)×36mm(D); Weight: 190g.
  • Housing: PC/ABS fireproof plastic, IP30 protection class.

CO2 Sensor Details
  • Measuring Range: 0~2000ppm (default), 0~5000ppm (advanced setup).
  • Accuracy: ±60ppm + 3% of reading or ±75ppm.
  • Response Time: <2 minutes for 90% step change.
  • Calibration: ABC Logic Self Calibration Algorithm.

Temperature and RH Sensor (Optional)
  • Temperature Sensor: Digital integrated or NTC thermistor.
  • Measuring Range: -20~60℃/-4~140F; 0~100%RH.
  • Accuracy: Temp. <±0.5℃@25℃; RH <±3.0%RH (20%~80%RH).

Model Guide
  • OLED Display: Available with or without buttons.
  • Analog Output: Options for no output, 1x or 2x outputs.
  • Relay Output: Available or not available.
  • Communication Interface: Options for no interface, Modbus, or BACnet.
  • Temperature and RH Detection: Options for temperature only, temperature & RH, or none.
  • Analog Output Type: Options for 0~10VDC, 4~20mA, or PID output.

Installation and Wiring
The device is designed for wall mounting with a 65mm×65mm or 2”×4” wire box. Detailed wiring diagrams are provided for installation.
See more

Catalog excerpts

TSP-CO2 Series-1

Tongdy Sensing Technology Corporation www.tongdy.com Carbon Dioxide Detector —A powerful monitor and controller Model#: TSP-CO2 Series ■ A new carbon dioxide detector with powerful functions ■ Perfect CO2 transmitter/controller ■ Temperature and RH detection is optional ■ NDIR infrared CO2 sensor with patented self calibration ■ One or two 0~10VDC/4~20mA linear outputs for CO2 or CO2/Temp. ■ PID control output selectable for CO2 measurement ■ LED light selectable between 3-color mode and working mode ■ RS485 communication interface with Modbus or BACnet optional ■ Optional OLED screen displays measurements ■ One relay output optional for a ventilator or a CO2 generator ■ Buzzer alarm provided for the models with relay ■ EMC approval ■ Features ♦ Design for real time measuring ambiance carbon dioxide and temperature and relative humidity ♦ NDIR infrared CO2 sensor inside with special Self Calibration. It makes CO2 measurement more accurate and more reliable. ♦ Up to 10 years lifetime of CO2 sensor ♦ Provide one or two 0~10VDC/4~20mA linear output for CO2 or CO2/temp. ♦ PID control output can be selected for CO2 measurement ♦ One passive relay output is optional. It can control a fan or a CO2 generator. The control mode is easily selected. ♦ The 3-color LED indicates three CO2 level ranges ♦ Optional OLED screen displays CO2/Temp/RH measurements ♦ Buzzer alarm provided for the models with relay ♦ RS485 communication interface with Modbus or BACnet protocol ♦ 24VAC/VDC power supply Add: Building #8, Courtyard #9, Dijin Road, Haidian District, Beijing, 100095, China Tel: (86 10) 59738930/31/32 Fax: (86 10) 59738935 E-Mail:

 Open the catalog to page 1
TSP-CO2 Series-2

Tongdy Sensing Technology Corporation www.tongdy.com Add: Building #8, Courtyard #9, Dijin Road, Haidian District, Beijing, 100095, China Tel: (86 10) 59738930/31/32 Fax: (86 10) 59738935 E-Mail: [email protected]

 Open the catalog to page 2
TSP-CO2 Series-3

Tongdy Sensing Technology Corporation www.tongdy.com A: OLED display with buttons D- with OLED and buttons (for Y=1) B- no OLED and buttons 2- 2x analog output (for CO2 & Temp.) 1- 1x relay output Z: communication interface 0- no communication interface 1- Modbus RS485 interface 2- BACnet protocol T/TH: temperature and RH option T- temperature detection TH- temperature & RH detection No T/TH suffix indicates no temperature or/and RH detection P: type of analog output V- 0~10VDC output (default) A- 4~20mA output P- PID output Add: Building #8, Courtyard #9, Dijin Road, Haidian District, Beijing,...

 Open the catalog to page 3
TSP-CO2 Series-4

Tongdy Sensing Technology Corporation www.tongdy.com Add: Building #8, Courtyard #9, Dijin Road, Haidian District, Beijing, 100095, China Tel: (86 10) 59738930/31/32 Fax: (86 10) 59738935 E-Mail: [email protected]

 Open the catalog to page 4

All Tongdy Control Technology catalogs and technical brochures

  1. MSD

    6  Pages

  2. TSP-16

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.