1. Catalogs
  2. Tongdy Control Technology
  3. F2000TSM-CO2 series PID CO2 Controller | Tongdy®

F2000TSM-CO2 series PID CO2 Controller | Tongdy®

F2000TSM-CO2 series PID CO2 Controller | Tongdy®

F2000TSM-CO2 series PID CO2 Controller | Tongdy®

Product catalog summary
Features
  • Real-time CO2 detection using an NDIR infrared module with self-calibration and a lifespan of over 10 years.
  • Optional 6 LED lights to indicate CO2 levels.
  • Analog output options of 0~10VDC or 2~10VDC.
  • PID output for VAV terminal with a setpoint for minimum opening.
  • Linear output available for CO2 measurements.
  • Optional Modbus RS485 interface for communication.
  • Four selectable CO2 setpoints for PID output via jumpers.
  • Minimum opening adjustable via RS485.
  • Suitable for ventilation systems, BAS, and single fan control.
  • CE-approved with a smart structure for easy mounting.
Specifications
  • Gas Detected: Carbon Dioxide (CO2).
  • Sensing Element: Non-Dispersive Infrared Detector (NDIR).
  • Accuracy: ±40ppm + 3% reading at 25℃ (77℉), 2000ppm.
  • Stability: Less than 2% of FS over the sensor's life (15 years typical).
  • Calibration: ABC Logic Self Calibration System.
  • Response Time: Less than 2 minutes for 90% step change.
  • Warm-up Time: 2 hours initially, 2 minutes for operation.
  • CO2 Measuring Range: 0~2,000ppm (default), 0~5,000ppm available.
  • Power Supply: 24VAC/24VDC.
  • Consumption: 1.5 W max, 0.8 W avg.
  • Output: Selectable PID control or linear output via jumpers.
  • Setpoints: Four CO2 setpoints for PID control (600ppm, 800ppm, 1000ppm, 1200ppm).
  • Modbus Interface: RS485, 19200bps, 15KV antistatic protection.
  • LED Indicators: Six LEDs indicating CO2 levels from green to red.
  • Operating Conditions: 0~50℃ (32~122℉), 0~95% RH, non-condensing.
  • Storage Conditions: 0~60℃ (32~140℉), 0~80% RH.
  • Dimensions: 100mm x 80mm x 28mm.
  • Installation: Standard 65mm x 65mm or 2” x 4” wire box.
Models Guide
  • F2000TSM-CO2-S100-PID-02/05: Analog output with PID, CO2 range 0~2,000ppm/0~5,000ppm.
  • F2000TSM-CO2-S101-PID-02/05: Analog output with PID, Modbus interface, CO2 range 0~2,000ppm/0~5,000ppm.
  • F2000TSM-CO2-L100-PID-02/05: 6 LED lights, analog output with PID, CO2 range 0~2,000ppm/0~5,000ppm.
  • F2000TSM-CO2-L101-PID-02/05: 6 LED lights, analog output with PID, Modbus interface, CO2 range 0~2,000ppm/0~5,000ppm.
Wiring Diagram and Mounting

The document includes a wiring diagram and mounting instructions, emphasizing the use of 24VAC/VDC power supply and connections for RS-485 and analog outputs.

See more

Catalog excerpts

F2000TSM-CO2 series PID CO2 Controller | Tongdy®-1

CARBON DIOXIDE CONTROLLER Model: F2000TSM-CO2-PID CE Approval Optional Modbus RS485 interface NDIR infrared CO2 module with self-calibration Four CO2 setpoints selectable via jumpers for PID and more than 10 years lifetime Optional 6 LED lights indicating CO2 ranges Application for ventilation systems, BAS and single PID output for a VAV terminal with the setpoint of Smart structure and easy mounting Linear output available for CO2 measurements Sensing element Non-Dispersive Infrared Detector (NDIR) <2% of FS over life of sensor (15 yr typical) Calibration interval ABC Logic Self Calibration System Response time <2 minutes for 90% step change 2 hours (first time) 2 minutes (operation) 02,000ppm (default) 05,000ppm available More than 10 years Power supply Analog output Output select PID control output or Linear output for CO2 measurement selectable via jumpers Minimum opening 2V default and can be preset via RS485 Provide 4 CO2 setpoints for PID control: Modbus interface Modbus RS485 interface, 19200bps, 15KV antistatic protection.

 Open the catalog to page 1
F2000TSM-CO2 series PID CO2 Controller | Tongdy®-2

From left to right: Operation conditions Storage conditions Installation standard Models Guide Type Description 1Xanalog output with PID (linear output selectable), CO2 range: 0~2,000ppm/0~5,000ppm 1Xanalog output with PID (linear output selectable), Modbus interface. 6 LED lights indicates CO2 ranges. 1Xanalog output with PID (linear output selectable), CO2 range: 0~2,000ppm/0~5,000ppm 6 LED lights indicates CO2 ranges. 1Xanalog output with PID (linear output selectable), Modbus interface. CO2 range: 0~2,000ppm/0~5,000ppm Wiring Diagram