1. Catalogs
  2. Tongdy Control Technology
  3. F2000IAQ-O3 Ozone Gas Monitor/ Controller | Tongdy®

F2000IAQ-O3 Ozone Gas Monitor/ Controller | Tongdy®

F2000IAQ-O3 Ozone Gas Monitor/ Controller | Tongdy®

F2000IAQ-O3 Ozone Gas Monitor/ Controller | Tongdy®

Product catalog summary
Overview: The F2000IAQ-O3 is an ozone gas monitor and controller designed by Tongdy Control Technology Co., Ltd. It is equipped with features for real-time detection of ozone levels, temperature, and humidity, and includes options for controlling external devices such as ozone generators or fans.
Key Features:
  • Real-time detection of ozone gas, temperature, and humidity.
  • Wall-mounted design with an LCD display showing ozone levels, temperature, humidity, and device status.
  • Ozone measurement range: 10ppb to 500ppb; Temperature range: 5°C to 50°C; Humidity range: 0% to 80% RH.
  • High sensitivity semiconductor sensor for ozone detection.
  • Compensation for environmental temperature and humidity in ozone measurements.
  • Easy zero calibration method.
  • Modbus RS-485 interface with 15KV antistatic protection.
  • Optional relay dry-contact output and analog linear output for device control.
  • CE-Approval certified.
Specifications:
  • Gas Detected: Ozone gas using a semiconductor sensor with a lifespan of over 5 years.
  • Temperature Sensor: NTC; Humidity Sensor: HS series capacitive sensor.
  • Power Supply: 24VAC/VDC.
  • Display Resolution: 1 ppb; Measurement Precision: ±10ppb + 20% reading at 10-35°C/20-80% RH.
  • Warm-up Time: 96 hours initially, 1 hour for operation.
  • Analog Output: 0-10VDC linear output with 10-bit resolution.
  • Relay Output: One dry contact output with a rated switching current of 2A resistance load.
  • RS485 Interface: Modbus protocol with 19200bps and independent base address.
  • Operating Conditions: 5-50°C, 0-80% RH, non-condensing.
  • Dimensions: 120mm x 90mm x 24mm; Net Weight: 260g.
Models:
  • F2000IAQ-O3-1001C: Includes 1X on/off relay output and Modbus RS485 interface.
  • F2000IAQ-O3-1010C: Includes 1X analog output and Modbus RS485 interface.
  • F2000IAQ-O3-1011C: Includes both 1X on/off relay output and 1X analog output with Modbus RS485 interface.
  • F2000IAQ-O3-1000C: Includes Modbus RS485 interface only.
See more

Catalog excerpts

F2000IAQ-O3 Ozone Gas Monitor/ Controller | Tongdy®-1

F2000IAQ-O3 Ozone Gas Monitor/ Controller Real time detecting environment ozone gas Temperature & Humidity detection The compensation of ozone measurements for air temperature and RH% Wall mount with LCD display Easy zero calibration way Optional one on/off dry contact output to control an ozone generator or a fan Optional an analog output for ozone measurement Real time detect ambiance ozone gas level Detect temperature and humidity at the same time Wall mounted with LCD display Provide an easy zero calibration way LCD can display ozone, temperature and humidity, Modbus RS-485 interface with 15KV antistatic environment temp.&RH% protection, independent base address setting also controlled device status etc. Optional 1X relay dry-contact output for an ozone generator or a fan optional Temperature range: 5~50℃ and relative humidity Special design compensation of ozone measurements for Optional 1Xanalog linear output (0~10VCD) for the ozone measurement Semiconductor sensor inside, high sensitivity to ozone gas humidity temperature relay on ozone level setting switch turn on/off down Sensing element Life time of ozone sensor More than 5 years Temperature sensor Tongdy Control Technology Co., Ltd add: Building #8, Courtyard #9 Dijin Rd. of Zhongguancun Environmental Protection Science and Technology Park, No.156 Beiqing Rd. Beijing 100095 tel: +86 10 59738930/31/32 http: www.tongdy.com email: [email protected]

 Open the catalog to page 1
F2000IAQ-O3 Ozone Gas Monitor/ Controller | Tongdy®-2

Humidity sensor HS series capacitive sensor Power supply Display resolution Temperature measurement range Humidity measurement range 96 hours(first time) 1 hour(operation) Analog output (option) Output resolution One dry contact output to control an ozone device or a ventilation device Rated switching current 2A resistance load Modbus protocol with 19200bps. 15KV antistatic protection, independent base address Operation conditions/ Storage conditions Installment standard Wiring standard Wire section area <1.5mm Relay output (option) Models Model Ozone monitor & controller with 1Xon/Off relay...

 Open the catalog to page 2

All Tongdy Control Technology catalogs and technical brochures

  1. MSD

    6  Pages

  2. TSP-16

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.